This prevents any amount of condensed or liquid creosote from running down the outside of the
pipe or the stovetop. All joints, including the flue collar connection, must be secured with three
sheet metal screws to ensure that the sections do not separate.
For the best performance, the chimney connector should be as short and direct as possible,
with no more than two 90° elbows. The maximum horizontal run is 36" (91.44 cm) and a
recommended total length of stovepipe should not exceed 10 feet (3m). Always slope horizontal
runs upward ¼" (6.35mm) per foot toward the chimney.
No part of the chimney connector may pass through an attic or roof space, closet or other
concealed space, or through a floor or ceiling. All sections of the chimney connectors must be
accessible for cleaning. Where passage through a wall or partition of combustible construction
is desired, the installation must conform to National Fire Protection Association (NFPA) 211,
and is also addressed in this manual.

Chimney

DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
DO NOT CONNECT TO ANY AIR DISTRIBUTION DUCT OR SYSTEM.
This room heater must be connected to a 6" (152.4mm) factory-built UL 103 HT chimney or a
code-approved masonry chimney with a flue liner.
Chimney Height
A masonry chimney or a listed factory-built chimney must be the required height above the roof
and any other nearby obstructions. The chimney must be at least 3 feet (91 cm) higher than the
highest point where it passes through the roof and at least 2 feet (61 cm) higher than the
highest part of the roof or structure that is within 10 feet (305 cm) of the chimney, measured
horizontally.
9