Concealed duct air conditioner

Advertisement

Put the installation paper on the place and
determine the position and height of the fixing
screws of the deluxe wired remote controller.
• Refer to the printed side of the installation
paper.
Remove the installation paper before
installing the remote controller so that
it can fit into the right place.
* When installing the deluxe wired remote controller, do not install it so that it is buried to the wall.
(This can cause error in the temperature sensor)
* When installing multiple deluxe wired remote controllers horizontally in one location, leave a
minimum distance apart (2cm). (This can cause error in the temperature sensor)
* Do not install the cable with a distance of 50 m or longer. (This can cause communication error.)
* When installing the cable, check whether the connector between the remote controller and the
product is installed properly. The connector will not be connected when installed in opposite sides.
Wall
Installation paper
The position of the fixing screws
Fixing the
remote controller
Fixing the
connecting cable