DPR RACK
1. These products are intended for use only as a secondary protector on data
circuits.
2. Mounting the DPR Rack Protection Modules: Mount the module(s) as
close to the equipment to be protected as possible.
2.1. DIN Rail Mounting: Attach the mounting clip on the DPR protection
module to a piece of 35mm DIN rail. To remove the protection module,
lift up on the lever portion of the mounting clip.
2.2. Wall Mounting: Rotate the mounting clip on the DPR protection
module to expose the auxiliary mounting hole. Attach the DPR protection
module to the desired surface using the auxiliary mounting hole and a #8
screw.
2.3. Rack Mounting: First, mount the DPR Rack Housing Kit to a standard
equipment rack using 10-32 screws. Then, remove the mounting clip
from each DPR protection module to be installed and populate the rack
with protection modules by re-using the mounting screw that retained the
mounting clip.
3. Wiring the DPR Rack
3.1. Connect the mounting clip of each DIN Rail/Wall mounted DPR
protection module to a nearby grounded location using the shortest wire
length possible. Alternatively, connect the ground wire assembly on the
front of the DPR Rack Housing Kit to a properly grounded location on the
equipment rack. Suppressor(s) must be grounded for proper operation!
3.2. Connect the corresponding incoming data lines to the connectors
labeled 'LINE' on the appropriate protection modules (T1/E1, xDSL,
10/100Base-T Ethernet or 1000Base-T Ethernet).
3.3. Connect the out going data lines to the connectors labeled
"EQUIP".
800.882.9110 | 208.772.8515 | www.transtector.com
1200-334 Rev H