Stephill SSDP30-70 Series User & Fault Finding Manual

Stephill SSDP30-70 Series User & Fault Finding Manual

Control module

Advertisement

Quick Links

SSDP30-70 Range - DSE 6110 MK3 Control Module
User & Fault Finding Guide
Issue 3 June 2020

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SSDP30-70 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Stephill SSDP30-70 Series

  • Page 1 SSDP30-70 Range - DSE 6110 MK3 Control Module User & Fault Finding Guide Issue 3 June 2020...
  • Page 2: Table Of Contents

    Issue 3 User Guide Contents Description Page No. Description of the DSE 6110 Mk2 control module lay-out General Operation ● How to Start the Generator ● How to Stop the Generator Button Description Generator Locked Out Status Display Typical No-Load Values - Status How to Check the Generator AC Voltage is Correct How to Check the Current Applied is Balanced How to Check the Load Applied is Balanced and the Total Load...
  • Page 3: How To Start The Generator

    Stephill Generators SSDP30-70 - DSE 6110 Module User Guide This user guide has been assembled to aid with the basic aspects of the DSE6110 MK3 module as configured on Stephill Generators and to gain access to the information available. It has been produced as a "How to" guide.
  • Page 4: Button Description

    Issue 2 Stephill Generators SSDP30-70 - DSE 6110 Module User Guide Button Description Icon Description Stop/Reset Mode This button places the module into its Stop/Reset Mode. This clears any alarm conditions for which have triggered and criteria have been removed. If the engine is running and the module is put into Stop mode, the fuel supply de-energises and the engine comes to a standstill.
  • Page 5: Generator Locked Out

    Issue 2 Stephill Generators SSDP30-70 - DSE 6110 Module User Guide Generator Locked Out If Generator Locked Out is displayed on the screen - Fig.2 then this indicates that the generator cannot be started due to an active Shutdown on the module.
  • Page 6: How To Check The Generator Ac Voltage Is Correct

    Issue 2 Stephill Generators SSDP30-70 - DSE 6110 Module User Guide How to Check the Generator AC Voltage is Correct To check the AC voltage output from the generator is correct, firstly you must isolate the load from the generator (remove any AC plugs connected to the generator outputs). Either before you start the generator or while the generator is running, use the Next or Previous page button until across the top of the screen it reads Generator .
  • Page 7 Using the generator serial plate on the generator control panel door as a reference, you can check the maximum kW load that can be applied to the model type of Stephill Generator. Fig.8 below is an example of a standard SSDP70A, highlighted are the two values to be most aware of.
  • Page 8: How To Check The Engine Instruments

    Issue 2 Stephill Generators SSDP30-70 - DSE 6110 Module User Guide How to Check Generator Frequency - Hz The generator frequency can be found on two pages, on the Status page, as shown in Fig.3 Status display. Also the frequency has it's own instrument screen in the Generator page(s).
  • Page 9: Engine Run Time

    Issue 2 Stephill Generators SSDP30-70 - DSE 6110 Module User Guide Engine Battery Voltage Engine Battery Voltage 14 . 4 Battery 14 . 5 Charge Alt Fig.15 Engine Run Time Engine Run Time 196h 12m Start(s) Fig.16 Engine Fuel Level...
  • Page 10: How To Check Which Alarms Have Been Triggered

    Issue 2 Stephill Generators SSDP30-70 - DSE 6110 Module User Guide How to Reset the "Service Hours Alarm " Warning The Service Hours Alarm screen is a count down timer, when the timer reaches zero hours a Warning Alarm will be issued and displayed on the screen. The Warning Alarm will allow the user to operate the generator as normal but the Warning Alarm will be present until a service reset has been performed.
  • Page 11: How To Check The Control Module "Event Log

    Issue 2 Stephill Generators SSDP30-70 - DSE 6110 Module User Guide How to Check the Control Module "Event Log" The module maintains a log of past alarms and selected status changes. Currently the module is capable of storing the last 250 log events. This is always subject to change with module updates.
  • Page 12 Issue 2 Fault Finding Contents Description Page No. Before Starting the Generator Generator Not Starting ● Use "Generator Not Starting" flow chart. Generator Running Generator Stops ● Fail to Start shutdown ● AC Voltage shutdown 14/15 ● Frequency shutdown Common Fault Conditions ●...
  • Page 13: Before Starting The Generator

    Stephill Generators SSDP30-70 - DSE 6110 Fault Finding Guide Issue 3 This basic fault finding guide has been complied to assist with the operation on Stephill Generators that use a DSE 6110 Mk3 control module. STEPHILL GENERATORS LTD STRESS THAT THE ULTIMATE RESPONSIBILTY FOR THE SAFE USE OF THE GENERATOR RESTS WITH THE USER.
  • Page 14: Fail To Start Shutdown

    Stephill Generators SSDP30-70 - DSE 6110 Fault Finding Guide Issue 3 Generator Alarms DSE 6110 MK3 Failed to Start - Shutdown Alarms The module will display Failed to Start after 3 attempts to start. Failed to Start Shutdown Fig.2 This shutdown is issued if the AC frequency measured on the DSE 6110 MK3 hasn’t reached the desired level - Fig.2.
  • Page 15: Frequency Shutdown

    Stephill Generators SSDP30-70 - DSE 6110 Fault Finding Guide Issue 3 No Frequency If no frequency can be seen on the DSE 6110 display then follow the checks listed above on Gen Under Voltage . The frequency, in most cases, is dependant directly by the rotational speed of the engine. The slower the engine runs, the lower the frequency.
  • Page 16: Common Fault Conditions

    Stephill Generators SSDP30-70 - DSE 6110 Fault Finding Guide Issue 3 Common Fault Conditions Below is a general guide for the most common fault conditions on a Stephill Generator using a DSE 6110 Mk3 control module. Fault Condition Checks & Tests •...
  • Page 17: Charge Alternator Failure

    Stephill Generators SSDP30-70 - DSE 6110 Fault Finding Guide Issue 3 • Check engine temperature display on the DSE 6110 - Engine page. High engine temperature shutdown is set at 110 °C. • Check water/antifreeze level in the radiator. Caution hot steam can burn! •...
  • Page 18 Issue 2 Start "Jump" or change 12V battery Generator battery Replace 12V fuel lift Check/replace voltage is 12.4V or pump starter motor By-pass emergency more at standstill stop switch 12V present between 12v DC between wire 50 wires 51 & 1 on the on the starter motor and Emergency Stop is fuel pump plug when...