This part of the manual describes the functions of the secondary substation measuring and monitoring unit WIMO 6CP10 and includes the unit operation instructions. It also contains instructions for parameterization and configuration of the unit and instructions for changing settings.
Operation and configuration User interface 2.1. General WIMO 6CP10 secondary substation measuring and monitoring unit can be controlled in three ways: Locally with the push-buttons on the device front panel • Locally using a PC connected to the serial port on the front •...
Operation and configuration 2.2.1. Display WIMO 6CP10 is provided with a backlit LCD dot matrix display. The display has 128 x 64 dots, which enables showing 21 characters in one row and eight rows at the same time. The display is divided into sections as shown in the next figure Figure 2.2.1-1 Sections of the LCD dot matrix display...
WImotec Ltd Measuring and monitoring unit WIMO 6CP10 Operation and configuration 2.2.2. Keypad You can navigate in the menu and set the required parameter values using the keypad and the guidance given in the display. The key pad is composed of four arrow keys, one cancel key and one enter key.
WIMO 6CP10 Measuring and monitoring unit Wimotec Ltd Operation and configuration Local panel operations The local panel is being used to read measured values, to set parameters and to configure unit functions. Some parameters, however, can only be set by means of a PC connected to one of the local communication ports.
Page 9
WImotec Ltd Measuring and monitoring unit WIMO 6CP10 Operation and configuration Figure 3.1-1. Principles of the menu structure and navigation in the menus 6. Push the INFO key to obtain additional information about any menu item. 7. Push the CANCEL key to revert to the normal display.
WIMO 6CP10 Measuring and monitoring unit Wimotec Ltd Operation and configuration 3.2. Operating levels User level Configuration The unit has two operating levels: level . The purpose of the configuration level is to prevent accidental change of unit configurations, parameters or settings.
WImotec Ltd Measuring and monitoring unit WIMO 6CP10 Operation and configuration 3.2.2. Password handling The passwords can only be changed using VAMPSET software connected to the local RS-232 port on the unit. It is possible to restore the password(s) in case the password is lost or forgotten.
1 to 3 in this manual before taking any operating measures or changing any unit settings or functions. WIMO 6CP10 can be controlled via the unit front panel, a PC running the VAMPSET software, a PC running suitable unit software or via a remote control system.
Page 13
WImotec Ltd Measuring and monitoring unit WIMO 6CP10 Operation and configuration Value Menu/Submenu Description Srmsda RMS POWER DEMAND Apparent power RMS demand value P/POWER/PHASE 1 Active power of phase 1 [kW] P/POWER/PHASE 1 Active power of phase 2 [kW] P/POWER/PHASE 1...
Page 14
WIMO 6CP10 Measuring and monitoring unit Wimotec Ltd Operation and configuration Value Menu/Submenu Description E/E-PULSE SIZES Pulse size of imported energy [kWh] E/E-PULSE SIZES Pulse duration of imported reactive energy [ms] E/E-PULSE DURATION Pulse duration of exported energy [ms] E/E-PULSE DURATION...
Page 15
WImotec Ltd Measuring and monitoring unit WIMO 6CP10 Operation and configuration Value Menu/Submenu Description Diagram I/IL2 WAVEFORM Waveform of IL2 Diagram I/IL3 WAVEFORM Waveform of IL3 Diagram I/IL1 TREND Trend of IL1 Diagram I/IL2 TREND Trend of IL2 Diagram I/IL3 TREND...
Page 16
WIMO 6CP10 Measuring and monitoring unit Wimotec Ltd Operation and configuration Value Menu/Submenu Description SagOff U/VOLTAGE SAG & Sag off event SWELL SwelOn U/VOLTAGE SAG & Swell on event SWELL SwelOf U/VOLTAGE SAG & Swell off event SWELL Status U/SAG & SWELL CNTRS High Count U/SAG &...
WImotec Ltd Measuring and monitoring unit WIMO 6CP10 Operation and configuration Value Menu/Submenu Description Time U/ VOLT INT SETTING Hours-minutes-seconds Event U/ VOLT INT SETTING Enabled I_On U/ VOLT INT SETTING Interrupt on event I_Off U/ VOLT INT SETTING Interrupt off event Figure 4.2-1.
WIMO 6CP10 Measuring and monitoring unit Wimotec Ltd Operation and configuration 4.4. Reading event register The event register can be read from the Evnt submenu: 1. Push the RIGHT key once. 2. The EVENT LIST appears. The display contains a list of all the events that have been configured to be included in the event register.
WImotec Ltd Measuring and monitoring unit WIMO 6CP10 Operation and configuration Configuration and parameter setting Operating level: CONFIGURATION Choose and configure the digital inputs in the DI submenu. • Configure the NO relay output in the DO submenu. • Set the ”Device Setup”, the scaling (for example Inom, Isec, •...
WIMO 6CP10 Measuring and monitoring unit Wimotec Ltd Operation and configuration 5.1. Principle of parameter setting 1. Move to the setting state of the desired menu (for example CONF/CURRENT SCALING) by pushing the ENTER key. The Pick text appears in the upper-left part of the display.
WImotec Ltd Measuring and monitoring unit WIMO 6CP10 Operation and configuration 5.2. Disturbance recorder menu DR Via the submenus of the disturbance recorder menu the following functions and features can be read and set: DISTURBANCE RECO Recording mode (Mode) •...
WIMO 6CP10 Measuring and monitoring unit Wimotec Ltd Operation and configuration 5.3. Configuring digital inputs DI The following functions can be read and set via the submenus of the digital inputs menu: The status of digital inputs (DIGITAL INPUTS 1-3) •...
WImotec Ltd Measuring and monitoring unit WIMO 6CP10 Operation and configuration UNITS FOR MIMIC Unit for voltage (V/kV) • Unit for power (kW/MW) • FUNDAMENTAL/RMS Energy calculation mode • Display fundamental measurements • Display RMS measurements • DEVICE INFO (only display) Unit type •...
Page 24
WIMO 6CP10 Measuring and monitoring unit Wimotec Ltd Operation and configuration MODBUS The device slave number at Modbus Slave Protocol or • the target slave number at Modbus Master Protocol (Addr) Modbus transfer rate (bit/s) • Modbus parity check (Parity) •...
Page 25
WImotec Ltd Measuring and monitoring unit WIMO 6CP10 Operation and configuration DNP 3.0 Transfer rate (bit/s) • Parity • Slave address (SlvAddr) • Master address (MstrAddr) • Link layer confirmation timeout (LLTout) • Link layer retry counter (LLRetry) • Application layer confirmation timeout (APLTout) •...
WIMO 6CP10 Measuring and monitoring unit Wimotec Ltd Operation and configuration PC software 6.1. PC user interface The PC user interface can be used for: On-site parameterization of the unit • Loading unit software from a computer • Reading measured values to a computer •...
Commissioning configuration 7.1. Factory settings When delivered from the factory, WIMO 6CP10 has got either factory default settings or settings defined by the customer. The configuration can be read from the workshop test reports or from the final test reports.
Page 28
WIMO 6CP10 Measuring and monitoring unit Wimotec Ltd Operation and configuration Figure 7.1.1-2. Choose measurements to local panel display Wimotec 24h support phone +358 (0)20 753 3264 WM6CP10.EN001...
Page 29
4.5. Serial communication connection ......19 4.5.1. Pin assignments of communication ports ... 19 4.5.2. Protocols..............20 4.6. Connection examples............ 23 4.6.1. WIMO 6CP10 secondary substation measuring and monitoring unit ............23 5. Technical data ..............24 5.1. Connections ..............24 5.1.1.
Page 30
5.2.5. Casing ..............26 5.2.6. Package..............27 6. Construction .................28 6.1. Dimensional drawing............28 7. Order information..............29 7.1. Ordering codes of WIMO 6CP10 measuring and monitoring unit................29 8. Reference information ............30 Wimotec 24h support phone +358 (0)20 753 3264 WM6CP10.EN001...
Earth fault, short circuit and many other special designed indicators can be attached into WIMO 6CP10 digital inputs. Digital input alarms are also reported for user in real time.
Communications GPRS, SPA, OPC etc. • Leased modem line. • In case of earth-fault, WIMO 6CP10 registers the fault • current which helps customer to locate the earth-fault. Wimotec 24h support phone +358 (0)20 753 3264 WM6CP10.EN001...
Wimotec Ltd Measuring and monitoring unit WIMO 6CP10 Technical description Functions 2.1. WIMO 6CP10 function dependencies 2.1.1. Unit function reference guide Table of the unit dependent functions: IEC symbol Function name Three-phase current Neutral current Current unbalance Average and maximum demand current...
Wimotec Ltd Technical description 2.2. Programmable stage WIMO 6CP10 has eight identical programmable stages (PROGRAMMABLE STAGE 1-8). All programmable stages can be enabled or disabled one by one from the menu to fit the intended application. All the enabled programmable stages...
Wimotec Ltd Measuring and monitoring unit WIMO 6CP10 Technical description Figure 2.2-2 Programmable stages in the output matrix 2.3. Measurement functions 2.3.1. Fundamental frequency measurement All the measurements, except frequency, are based on fundamental frequency values. They are not RMS values.
Page 36
WIMO 6CP10 Measuring and monitoring unit Wimotec Ltd Technical description Phase to neutral voltages measured Active power calculation for one phase: ϕ ⋅ ⋅ Reactive power calculation for one phase: ϕ ⋅ ⋅ where, Measured L1 phase voltage Measured L1 current ϕ...
This is due to the nature of digital sampling.) 2.3.4. Voltage interruptions WIMO 6CP10 includes a simple function to detect and measure voltage sags. The function calculates the number of voltage interruptions and the total time of the voltage interruptions within a period.
Page 38
WIMO 6CP10 Measuring and monitoring unit Wimotec Ltd Technical description If the voltage has been significantly over the limit U < and then there is a small and short under swing, it will not be recognized (Figure 2.3.4-1). Figure 2.3.4-1. Short voltage sag which is probably not recognized On the other hand, if the limit U <...
Wimotec Ltd Measuring and monitoring unit WIMO 6CP10 Technical description Recorded Parameter Value Unit Description values Total Total (summed) time of voltage sags during the current observation period Prev Total (summed) time of voltage sags during the previous observation period 2.3.5.
WIMO 6CP10 Measuring and monitoring unit Wimotec Ltd Technical description Parameter Value Unit Description Recorded Time Duration of the sag/swell values Min1 %Un Minimum voltage value during the sag/swell in the input 1 Min2 %Un Minimum voltage value during the sag/swell in the input 2...
Page 41
Wimotec Ltd Measuring and monitoring unit WIMO 6CP10 Technical description The recorder can be triggered by a digital input. The trig signal is selected in the output matrix (signal DR). The recording can also be triggered manually. When a recording is made, also the time stamp will be memorized.
Page 42
WIMO 6CP10 Measuring and monitoring unit Wimotec Ltd Technical description Disturbance recorder parameters Parameter Value Unit Description Setting Mode Saturated; Mode of the recording values Overflow Rate Sample rate samples/cycle; samples/cycle; 8 samples/cycle; 10ms; 20ms; 200ms; 10s; 15s; 30s; 1min;...
WIMO unit includes three-phase voltage, three-phase current and earth fault measuring. Unit measures also the temperature of the transformer. WIMO 6CP10 is included with three digital inputs for various alarm stages as short circuit measurement or smoke detector. 3.2. Accessories It is possible to connect various alarm indicators to WIMO 6CP10’s digital inputs.
Earth fault alarm Earth fault location in ungrounded networks is difficult. By using a Cabletroll 2000 earth fault sensor in WIMO 6CP10 devices installed in the network makes it possible to locate the earth faults. The Cabletroll 2000 is connected to terminals X2B 1-2.
Measuring and monitoring unit WIMO 6CP10 Technical description Connections 4.1. Rear panel view 4.1.1. WIMO 6CP10 Figure 4.1.1-1 Connections on the rear panel of the WIMO 6CP10 Terminal X1 Symbol Description Phase current L1 Phase current L1 Phase current L2 Phase current L2...
Further, the unit can collect status information and alarm signals via 3 digital inputs (terminals X2B: 3-5). The three digital inputs in WIMO use an internal 12 V dc auxiliary voltage of the unit (terminal X2B: 8). Potential-free contacts must be available in the protected object for transferring status information to the unit.
Wimotec Ltd Measuring and monitoring unit WIMO 6CP10 Technical description 4.5. Serial communication connection RS 232 serial communication connection for computers, • connector LOCAL (RS 232), the connectors on the front and rear panel are connected in parallel. Remote control connection with the following options: •...
NOTE! DSR must be connected to +12V to activate the front panel interface. 4.5.2. Protocols SPA bus WIMO 6CP10 has full support for the SPA bus protocol including the following features: event transfer • the transfer of status data •...
Page 49
Measuring and monitoring unit WIMO 6CP10 Technical description Modbus RTU WIMO 6CP10 is also available with Modbus RTU slave or Modbus RTU master. These are often used in power plants or in industrial applications. The protocols enable the transfer of the following data: events •...
Page 50
• It is not possible to transfer parameter data or disturbance recordings via the IEC 103 protocol interface. DNP 3.0 WIMO 6CP10 supports communication using DNP 3.0 protocol. The following DNP 3.0 data types are supported: binary input • binary input change •...
WIMO 6CP10 Measuring and monitoring unit Wimotec Ltd Technical description Technical data 5.1. Connections 5.1.1. Measuring circuitry Rated current I - Current measuring range 0-5 A - Thermal withstand 6 A (continuously) 25 A (for 10 s) 100 A (for 1 s) - Burden <...
Wimotec Ltd Measuring and monitoring unit WIMO 6CP10 Technical description 5.1.4. Alarm contact Number of contacts: 1 change-over contact relay Rated voltage 48 V ac Max. make current N.O. 10 A / N.C. 3 A Continuous carry Breaking capacity, ac N.O.
Wimotec Ltd Measuring and monitoring unit WIMO 6CP10 Technical description 5.2.6. Package Dimensions (W x H x D) 105 x 105 x 175 mm Weight (Unit and Package) 1.4 kg WM6CP10.EN001 Wimotec 24h support phone +358 (0)20 753 3264...
Technical description Order information When ordering, please state: Type designation: WIMO 6CP10 Quantity : Options ( see respective ordering code): 7.1. Ordering codes of WIMO 6CP10 measuring and monitoring unit WIMO 6CP10 ORDERING CODE WIMO 6CP10 Accessories : Order Code Explanation...
WIMO 6CP10 Measuring and monitoring unit Wimotec Ltd Technical description Reference information Manufacturer / Service data: Wimotec Ltd. P.O.Box 810 FIN-65101 Vaasa, Finland Visiting address: Yrittäjänkatu 15 Phone: +358 (0)20 753 3200 Fax: +358 (0)20 753 3205 URL: http://www.wimotec.com 24h support phone: Tel.