Veeder-Root FUELQUEST Insite360 Connect Installation And Setup Manual
Veeder-Root FUELQUEST Insite360 Connect Installation And Setup Manual

Veeder-Root FUELQUEST Insite360 Connect Installation And Setup Manual

Advertisement

Quick Links

Manual No: 577014-326
Revision: B
Insite360 Connect
Installation And Setup Manual

Advertisement

loading

Summary of Contents for Veeder-Root FUELQUEST Insite360 Connect

  • Page 1 Manual No: 577014-326 ● Revision: B Insite360 Connect Installation And Setup Manual...
  • Page 2 Notice Veeder-Root makes no warranty of any kind with regard to this publication, including but not limited to, the implied warranties of merchantability and fitness for a particular purpose. Veeder-Root shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this publication.
  • Page 3 Introduction 1 Safety Precautions ................................ 1 Related Manuals ................................1 Insite360 Connect Description ..........................2 Installation 3 Mounting The Insite360 Connect ..........................3 Insite360 Connect Installation Option - Scenario 1 ..................... 4 Insite360 Connect Installation Option - Scenario 2 ..................... 7 Insite360 Connect Installation Option - Scenario 3 .....................
  • Page 4: Safety Precautions

    Introduction The Insite360 Connect transfers station data (such as inventory, alarm history, dispenser volume events, etc.) from an Automatic Tank Gauge (ATG) TLS-300 or TLS-350 having software version 24 or later, to secure Cloud storage where it can be used for Insite360 FuelQuest services such as Insite360 Visibility, Inventory Forecasting, Advanced Variance Analysis services, and more.
  • Page 5 Insite360 Connect Description Table 1 lists the kits required for Insite360 Connect installation and Figure 1 describes the Insite360 Connect’s communication ports and indicator LEDs. Table 1. Kits Required For Insite360 Connect Installation Part Number Description 330020-833 Insite360 Connect, cables and mounting fasteners for ATG with no POS connection 330020-834 POS Upgrade kit (additional cables and adapters for ATG with POS connection) USB 1...
  • Page 6: Installation

    Installation Mounting The Insite360 Connect The Insite360 Connect must be installed within 7 feet of, and in the same area and environment as, your ATG. The Insite360 Connect requires access to a 100 to 240Vac wall outlet for its power supply. Mount the Insite360 Connect using either the provided screws (Method A) or the hook and loop self-fastening strips (Method B).
  • Page 7 Insite360 Connect Installation Option - Scenario 1 Scenario 1 applies to sites where the Insite360 Connect connects to a free serial port in the TLS-300 or TLS- 350. If the TLS-350 has the optional BIR and a Dispenser Interface Module (DIM), Dispenser Volume Events will be sent to the GVR cloud.
  • Page 8 ALARM ( TLS-350) WARNING POWER T1: PREMIUM UNLEADED VOLUME 4208 GALS ULLAGE 5792 GALS 90% ULLAGE 4792 GALS TC VOLUME 4194 GALS HEIGHT 41.02 INCHES WATER VOL GALS WATER 0.00 INCHES TEMP 65.0 DEG F T1: REGULAR GASOLINE VOLUME 9038 GALS ULLAGE GALS...
  • Page 9 ( TLS-300 or ALARM WARNING TLS-350) POWER T1: PREMIUM UNLEADED VOLUME 4208 GALS ULLAGE 5792 GALS 90% ULLAGE 4792 GALS TC VOLUME 4194 GALS HEIGHT 41.02 INCHES WATER VOL GALS WATER 0.00 INCHES TEMP 65.0 DEG F T1: REGULAR GASOLINE VOLUME 9038 GALS...
  • Page 10 Insite360 Connect Installation Option - Scenario 2 Scenario 2 applies to sites where the ATG has an EDIM module connected to a POS and no free serial port for a dedicated connection to Insite360 Connect. In this scenario, the Insite360 Connect communicates with the ATG through the EDIM to retrieve data to be pushed to the Cloud, while allowing normal communications between the EDIM and the POS to pass through uninterrupted.
  • Page 11 ALARM WARNING POWER ( TLS-350) T1: PREMIUM UNLEADED VOLUME 4208 GALS ULLAGE 5792 GALS 90% ULLAGE 4792 GALS TC VOLUME 4194 GALS HEIGHT WATER VOL 41.02 INCHES WATER GALS TEMP 0.00 65.0 INCHES DEG F T1: REGULAR GASOLINE VOLUME 9038 GALS ULLAGE GALS...
  • Page 12 Insite360 Connect Installation Option - Scenario 3 Scenario 3 applies to sites where the ATG has an RS232 serial comm port connected to a POS and no additional free serial port for a dedicated connection to the Insite360 Connect. In this scenario, the Insite360 Connect communicates with the ATG through the RS232 serial comm port to retrieve data to be pushed to the Cloud, while allowing normal communications between the RS232 serial comm port and the POS to pass through uninterrupted.
  • Page 13 ALARM WARNING POWER ( TLS-300 or T1: PREMIUM UNLEADED VOLUME 4208 GALS ULLAGE 90% ULLAGE 5792 GALS TC VOLUME 4792 GALS HEIGHT 4194 41.02 GALS INCHES WATER VOL GALS WATER 0.00 INCHES TEMP 65.0 DEG F TLS-350)) T1: REGULAR GASOLINE VOLUME 9038 GALS...
  • Page 14 ALARM WARNING POWER (TLS-350)) T1: PREMIUM UNLEADED VOLUME 4208 GALS ULLAGE 5792 GALS 90% ULLAGE 4792 GALS TC VOLUME HEIGHT 4194 GALS WATER VOL 41.02 INCHES WATER GALS TEMP 0.00 65.0 INCHES DEG F T1: REGULAR GASOLINE VOLUME 9038 GALS ULLAGE GALS 90% ULLAGE...
  • Page 15 Insite360 Connect Configuration After physically setting up the Insite360 Connect and powering it up, the device will boot and if the device has already been commissioned for your site (indicated by the presence of a GVR/FMS Site ID number on the Insite360 Connect’s label [see Figure 7]), it will automatically connect to the GVR Cloud to register and configure itself within several minutes.
  • Page 16: Troubleshooting

    Troubleshooting LED Status Lights The Insite360 Connect’s LED status lights indicate operational status (see Table 2). Table 2. Insite360 Connect’s LED Status Lights Status Description Power (Red) Power is connected. Insite360 Connect fully booted, registered and running. Insite360 Connect application not running, reboot Insite360 Connect.
  • Page 17 ATG Serial Port Setup The ATG serial port settings must be configured to 9600 Baud, Data Bits 7, Parity Odd, Stop Bits 1. At the console’s front keypad press the MODE key until the display reads System Setup in the display. Press FUNCTION until you see the message: COMMUNICATIONS SETUP PRESS <STEP>...
  • Page 18 The choices are NONE, ODD, and EVEN. The correct Parity for Insite360 Connect is ODD. If the Parity shown on the message is ODD, press STEP. To choose the correct Parity setting, press CHANGE until you see the correct selection. Press ENTER to confirm your choice. The system displays the message: PARITY: ODD PRESS <STEP>...
  • Page 19 ATG EDIM Comm Port Setup The ATG EDIM Comm port settings must be configured for Insite360 Connect operation. At the console’s front keypad press the MODE key until the display reads Diag Mode in the display. Press FUNCTION until you see the message: SYSTEM DIAGNOSTIC PRESS <STEP>...
  • Page 20 Table 3. EDIM Data String Entries For Insite360 Connect EDIM Data String Selection EDIM Protocol For U.S. Units For Metric Units For Imperial Units VR Protocol No entry - leave blank Gilbarco Passport B9OHVG B9OHV B9OHVI Table 4. DIM Parameter Definitions (Reference) Baud Parity Stop Bits...
  • Page 21 POS connection settings. Configure a laptop PC with a static IP address of 192.168.101.2. to ensure it is on the same sub network as the Insite360 Connect. For more detailed instructions, reference Veeder-Root’s 577013-776 TCP/IP Interface Module Installation Guide at www.veeder.com.
  • Page 22 The Insite360 Connect’s POS communication parameters shown below are defaults and may have changed; these parameters must match the site’s POS communication parameters. Consult the customer’s IT department for the site’s actual POS communication parameters. Veeder Root Network Baud Rate 9600 Data Bits Parity...
  • Page 23 Appendix A - Insite360 Connect Mounting Screw Hole Template Cut along line to remove 3” (Ref.) Template Insite360 Connect 1.25” (32mm) Device (Ref.) Power Port Cut out template and tape to wall in desired location. Drill two pilot holes at center of two marks for two mounting screws or drywall anchors as 4”...
  • Page 24 For technical support, sales or other assistance, please visit: www.veeder.com...