Bryant DURAPACK 558F Installation & Service Instructions Manual
Bryant DURAPACK 558F Installation & Service Instructions Manual

Bryant DURAPACK 558F Installation & Service Instructions Manual

Single package rooftop electric heating/electric cooling units

Advertisement

Quick Links

IMPORTANT - READ BEFORE INSTALLING
Read and become familiar with these installation instruc-
tions before installing this unit.
Be sure the installation conforms to all applicable local and
national codes.
These instructions contain important information for the
proper maintenance and repair of this equipment. Retain
these instructions for future use.
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-53
I. Step 1 - Provide Unit Support. . . . . . . . . . . . . . . . . 1
II. Step 2 - Field Fabricate Ductwork . . . . . . . . . . . . . 1
Condensate Drain. . . . . . . . . . . . . . . . . . . . . . . . . . 2
IV. Step 4 - Rig and Place Unit . . . . . . . . . . . . . . . . . . . 2
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54,55
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56-61
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .61-65
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing air-conditioning equipment can be
hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service per-
sonnel. When working on air-conditioning equipment,
observe precautions in the literature, tags and labels
attached to the unit, and other safety precautions that may
apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguishers available for all brazing operations.
WARNING: Before performing service or mainte-
nance operations on unit, turn off main power switch
to unit and install lockout tag. Electrical shock could
cause personal injury.
CAUTION: Ensure voltage listed on unit data
plate agrees with electrical supply provided for the
unit.
installation, start-up and
service instructions
SINGLE PACKAGE ROOFTOP
ELECTRIC HEATING/ELECTRIC COOLING UNITS
Page
Cancels: II 558F-90-3

INSTALLATION

Unit is shipped in the vertical discharge configuration. To
convert to horizontal configuration, remove screws from hor-
izontal duct opening covers and remove covers. Using the
same screws, install covers on duct openings in basepan of
unit with the insulation-side down. Seals around duct open-
ings must be tight. See Fig. 1.
Confirm before installation of unit that voltage, amperage
and circuit protection requirements listed on unit data plate
agree with power supply provided.
I. STEP 1 - PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble and install accessory roof curb in accordance with
instructions shipped with curb. See Fig. 2. Install insulation,
cant strips, roofing felt, and counter flashing as shown. Duct-
work must be attached to curb, not to unit. If electric control
power is to be routed through the basepan, attach the acces-
sory thru-the-bottom service connections to the roof curb in
accordance with the accessory installation instructions. Con-
nection must be installed before unit is set on roof curb.
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket supplied with the
roof curb as shown in Fig. 2. Improperly applied gasket can
also result in air leaks and poor unit performance.
Curb should be level. This is necessary for unit drain to func-
tion properly. Unit leveling tolerances are shown in Fig. 3.
Refer to Accessory Roof Curb Installation Instructions for
additional information as required.
B. Alternate Unit Support
When the curb or adapter cannot be used, support unit with
sleeper rails using unit curb or adapter support area. If
sleepers cannot be used, support long sides of unit with a
minimum of three 4-in. x 4-in. pads, 2 at the unit's corners
and one at the center of gravity. If more than 3 are used,
equally space out pads along unit side.
C. Slab Mount (Horizontal Units Only)
Provide a level concrete slab that extends a minimum of 6 in.
beyond unit cabinet. Install a 6-in. gravel apron in front of
outdoor-coil air inlet to prevent grass and foliage from
obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
II. STEP 2 - FIELD FABRICATE DUCTWORK
On vertical discharge units, secure all ducts to roof curb and
building structure. Do not connect ductwork to unit. For hori-
zontal applications, field-supplied isolation flanges should be
attached to horizontal discharge openings and all ductwork
attached to the flanges. Insulate and weatherproof all exter-
nal ductwork, joints, and roof openings with counter flashing
and mastic in accordance with applicable codes.
558F
Dura Pac Series
Sizes 090-151
1
1
7
/
to 12
/
Tons
2
2
II 558F-90-4
9/15/05

Advertisement

Table of Contents
loading

Summary of Contents for Bryant DURAPACK 558F

  • Page 1: Table Of Contents

    installation, start-up and service instructions SINGLE PACKAGE ROOFTOP ELECTRIC HEATING/ELECTRIC COOLING UNITS IMPORTANT — READ BEFORE INSTALLING Read and become familiar with these installation instruc- tions before installing this unit. Be sure the installation conforms to all applicable local and national codes.
  • Page 2: Step 3 - Install External Trap For Condensate Drain

    Ducts passing through an unconditioned space must be insu- lated and covered with a vapor barrier. If plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes. If electrical connections are to be routed through the bottom of the unit, attach accessory thru-the-bottom service connections to the basepan in accordance with installation instructions.
  • Page 3 D ALT CONNECTOR DRAIN PKG. ACCY. HOLE CRBTMPWR001A01 CRBTMPWR002A01 ″ ″ 2′-8 1′-10 CRBTMPWR003A01 [827] [583] [44.5] CRBTMPWR004A01 POWER CONTROL ″ [19] NPT ″ ″ [31.7] [19] NPT ″ ″ ″ ″ [19] NPT [12.7] NPT [12.7] NPT ″ ″ [31.7] [19] NPT Fig.
  • Page 4 MAXIMUM ALLOWABLE DIFFERENCE (in.) Fig. 3 — Unit Leveling Tolerance HORIZONTAL DRAIN PLUG DRAIN OUTLET NOTE: Drain plug is shown in factory-installed position. Fig. 4 — Condensate Drain Connection (Side View) NOTES: 1. Dimension in ( ) is in millimeters. 2.
  • Page 5 — —...
  • Page 6 — —...
  • Page 7 Cleanable. Screen size and quantity varies by option selected. 4...16 x 20 x 2 4...16 x 20 x 2 *Evaporator coil fin material/condenser coil fin material. Contact your local Bryant representa- tive for details about coated fins. †Weight of 14-in. roof curb.
  • Page 8 Throwaway 4...16 x 20 x 2 4...16 x 20 x 2 *Evaporator coil fin material/condenser coil fin material. Contact your local Bryant repre- sentative for details about coated fins. †Weight of 14-in. roof curb. NOTE: High-static motor not available on size 150 and 151 units.
  • Page 9: Step 5 - Make Electrical Connections

    (Such operation would invalidate any applica- ble Bryant warranty.) B. Field Control Wiring Install a Bryant-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature in accor- dance with thermostat installation instructions.
  • Page 10 Table 2A — Electrical Data (Units Without Convenience Outlet) (558F090, 102, 120, 150) VOLTAGE COMPRESSOR 558F RANGE NOMINAL UNIT V-Ph-Hz TYPE SIZE 208/230-3-60 14.0 High 460-3-60 High 575-3-60 High 208/230-3-60 16.0 High 460-3-60 High 575-3-60 High ELECTRIC (ea) (ea) HEAT Nominal —...
  • Page 11 Table 2A — Electrical Data (Units Without Convenience Outlet) (558F090, 102, 120, 150) (cont) VOLTAGE 558F RANGE NOMINAL UNIT V-Ph-Hz TYPE SIZE 208/230-3-60 High 460-3-60 High 575-3-60 High LEGEND — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration —...
  • Page 12 Table 2A — Electrical Data (Units Without Convenience Outlet) (558F090, 102, 120, 150) (cont) VOLTAGE 558F RANGE NOMINAL UNIT V-Ph-Hz TYPE SIZE 208/230-3-60 460-3-60 575-3-60 LEGEND — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration — Indoor (Evaporator) Fan Motor —...
  • Page 13 Table 2B — Electrical Data (Units Without Convenience Outlet) (558F091, 103, 121, 151) VOLTAGE COMPRESSOR 558F RANGE (ea) NOMINAL UNIT V-PH-Hz TYPE SIZE 208/230-3-60 HIGH 460-3-60 HIGH 575-3-60 HIGH LEGEND — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration —...
  • Page 14 Table 2B — Electrical Data (Units Without Convenience Outlet) (558F091, 103, 121, 151) (cont) VOLTAGE COMPRESSOR 558F RANGE (ea) NOMINAL UNIT V-PH-Hz TYPE SIZE 208/230-3-60 17.3†† 120†† HIGH 460-3-60 7.9†† HIGH 575-3-60 5.5†† HIGH 208/230-3-60 HIGH 460-3-60 HIGH 575-3-60 HIGH OFM (ea) ELECTRIC HEAT HEATER...
  • Page 15 Table 2B — Electrical Data (Units Without Convenience Outlet) (558F091, 103, 121, 151) (cont) VOLTAGE COMPRESSOR 558F RANGE (ea) NOMINAL UNIT V-PH-Hz TYPE SIZE 208/230-3-60 460-3-60 575-3-60 LEGEND — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration — Indoor (Evaporator) Fan Motor —...
  • Page 16 Table 2C — Electrical Data (Units With Convenience Outlet) (558F090, 102, 120, 150) VOLTAGE COMPRESSOR 558F RANGE NOMINAL UNIT V-Ph-Hz TYPE SIZE 208/230-3-60 14.0 High 460-3-60 High 575-3-60 High 208/230-3-60 16.0 High 460-3-60 High 575-3-60 High ELECTRIC (ea) (ea) HEAT Nominal —...
  • Page 17 Table 2C — Electrical Data (Units With Convenience Outlet) (558F090, 102, 120, 150) (cont) VOLTAGE COMPRESSOR 558F RANGE NOMINAL UNIT V-Ph-Hz TYPE SIZE 208/230-3-60 15.8 High 460-3-60 High 575-3-60 High LEGEND — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration —...
  • Page 18 Table 2C — Electrical Data (Units With Convenience Outlet) (558F090, 102, 120, 150) (cont) VOLTAGE COMPRESSOR 558F RANGE NOMINAL UNIT V-Ph-Hz TYPE SIZE 208/230-3-60 23.0 460-3-60 10.4 575-3-60 LEGEND — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration —...
  • Page 19 Table 2D — Electrical Data (Units With Convenience Outlet) (558F091, 103, 121, 151) VOLTAGE COMPRESSOR 558F RANGE (ea) NOMINAL UNIT V-PH-Hz TYPE SIZE 208/230-3-60 HIGH 460-3-60 HIGH 575-3-60 HIGH LEGEND — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration —...
  • Page 20 Table 2D — Electrical Data (Units With Convenience Outlet) (558F091, 103, 121, 151) (cont) VOLTAGE COMPRESSOR 558F RANGE (ea) NOMINAL UNIT V-PH-Hz TYPE SIZE 208/230-3-60 17.3†† 120†† HIGH 460-3-60 7.9†† 70†† HIGH 575-3-60 5.5†† 50†† HIGH 208/230-3-60 HIGH 460-3-60 62.5 HIGH 575-3-60 HIGH...
  • Page 21 Table 2D — Electrical Data (Units With Convenience Outlet) (558F091, 103, 121, 151) (cont) VOLTAGE COMPRESSOR 558F RANGE (ea) NOMINAL UNIT V-PH-Hz TYPE SIZE 208/230-3-60 460-3-60 575-3-60 LEGEND — Full Load Amps HACR — Heating, Air Conditioning and Refrigeration — Indoor (Evaporator) Fan Motor —...
  • Page 22: Step 6 - Adjust Factory-Installed Options

    Fig. 9 — Conduit Installation DISCONNECT EMT OR RIGID BRACKET AND CONDUIT CONDUIT DRIP MOUNTING LOCATION (FIELD SUPPLIED) BOOT MAIN COM- COM- SINGLE CONTROL PRESSOR PRESSOR POINT NO. 2 NO. 1 LEGEND EMT — Electro-Metallic Tubing Fig. 10 — Typical Component Location COOL STAGE 1 Y1/W2 HEAT STAGE 1...
  • Page 23 FILTER ACCESS PANEL OUTDOOR AIR OPENING PANEL SCREWS (SIDE) MANUAL OUTDOOR-AIR ADJUSTMENT SCREWS Fig. 13 — Damper Panel with Manual Outdoor-Air Damper Installed Fig. 14 — Outdoor-Air Hood Details SCREW HOLES (TOP) HOOD HOOD SCREEN LOCATION (SCREEN SHOWN) Fig. 15 — Optional Manual Outdoor-Air Damper with Hood Attached DAMPER BLADE...
  • Page 24 9. Replace the filter access panel. 10. Install all EconoMi$er IV accessories. EconoMi$er IV wiring is shown in Fig. 23. Barometric flow capacity is shown in Fig. 24. Outdoor air leakage is shown in Fig. 25. Return air pressure drop is shown in Fig.
  • Page 25 LEGEND Potentiometer Defaults Settings: Power Exhaust DCV — Demand Controlled Ventilation Minimum Pos. IAQ — Indoor Air Quality DCV Max. — Low Ambient Lockout Device DCV Set OAT — Outdoor-Air Temperature Enthalpy POT — Potentiometer RAT — Return-Air Temperature 2500 2000 1500 1000...
  • Page 26 SUPPLY AIR TEMPERATURE SENSOR MOUNTING LOCATION SUPPLY AIR TEMPERATURE SENSOR Fig. 27 — Supply Air Sensor Location Table 3 — Supply Air Sensor Temperature/Resistance Values TEMPERATURE (F) RESISTANCE (ohms) –58 –40 –22 –4 The temperature sensor looks like an eyelet terminal with wires running to it.
  • Page 27 Differential Dry Bulb Control For differential dry bulb control the standard outdoor dry bulb sensor is used in conjunction with an additional acces- sory dry bulb sensor (part number CRTEMPSN002A00). The accessory sensor must be mounted in the return airstream. See Fig.
  • Page 28 CONTROL CONTROL POINT CURVE APPROX. °F (°C) AT 50% RH 73 (23) 70 (21) 67 (19) 63 (17) (10) (10) APPROXIMATE DRY BULB TEMPERATURE— °F (°C) Fig. 31 — Enthalpy Changeover Set Points 24 Vac Open Free Cool Fig. 32 — EconoMi$er IV Control (29) (32) (35)
  • Page 29 To determine the minimum position setting, perform the fol- lowing procedure: 1. Calculate the appropriate mixed air temperature using the following formula: ) + (T ) = T = Outdoor-Air Temperature OA = Percent of Outdoor Air = Return-Air Temperature RA = Percent of Return Air = Mixed-Air Temperature As an example, if local codes require 10% outdoor air...
  • Page 30 See Table 5. Use setting 1 or 2 for Bryant equipment. See Table 5. 1. Press Clear and Mode buttons. Hold at least 5 sec- onds until the sensor enters the Edit mode.
  • Page 31: Step 7 - Adjust Evaporator-Fan Speed

    VII. STEP 7 — ADJUST EVAPORATOR-FAN SPEED Adjust evaporator-fan speed to meet jobsite requirements. Table 6 shows fan rpm at motor pulley settings, Table 7 shows motor efficiencies and Table 8 gives accessory static pressure drop. Table 9 shows motor performance. Refer to Tables 10-29 to determine fan speed settings.
  • Page 32 UNIT 558F 090,091† 090,091** 090,091†† 1080 1025 102,103† 102,103†† 1080 1025 120,121† 120,121*** 1085 1060 120,121†† 1130 1112 150,151† 1080 1060 150,151*** 1130 1112 *Approximate fan rpm shown. †Indicates standard motor and drive package. ** Indicates alternate drive package only. ††Indicates high-static motor and drive package.
  • Page 33 2. Values include losses for filters, unit casing, and wet coils. See Table 8 for accessory/FIOP static pressure drop information. 3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative for details. 4. Interpolation is permissible. Do not extrapolate. —...
  • Page 34 Table 10 — Fan Performance 558F090,091 — Vertical Discharge Units; Standard Motor (Belt Drive)* AIRFLOW (Cfm) Watts 2250 0.53 0.56 2300 0.61 2400 0.67 2500 0.71 2550 2600 0.74 0.81 2700 2800 0.89 0.97 2900 3000 1.06 1.15 1071 3100 1.25 1162 3200...
  • Page 35 Table 11 — Fan Performance 558F090,091 — Vertical Discharge Units; Alternate Motor (Belt Drive)* AIRFLOW (Cfm) Watts 2250 0.53 0.56 2300 0.61 2400 0.67 2500 0.71 2550 2600 0.74 0.81 2700 2800 0.89 0.97 2900 3000 1.06 1.15 1071 3100 1.25 1162 3200...
  • Page 36 Table 12 — Fan Performance 558F090,091 — Vertical Discharge Units; High-Static Motor (Belt Drive)* AIRFLOW (Cfm) Watts 2250 0.53 0.56 2300 0.61 2400 0.67 2500 0.71 2550 2600 0.74 0.81 2700 2800 0.89 0.97 2900 3000 1.06 1.15 1071 3100 1.25 1162 3200...
  • Page 37 Table 13 — Fan Performance 558F102,103 — Vertical Discharge Units; Standard Motor (Belt Drive)* AIRFLOW (Cfm) Watts 2200 0.50 2250 0.53 2300 0.56 2400 0.61 2500 0.67 2550 0.71 2600 0.74 2700 0.81 2800 0.89 2900 0.97 3000 1.06 3100 1.15 1071 3200...
  • Page 38 Table 14 — Fan Performance 558F102,103 — Vertical Discharge Units; High-Static Motor (Belt Drive)* AIRFLOW (Cfm) Watts 2200 0.50 2250 0.53 2300 0.56 2400 0.61 2500 0.67 2550 0.71 2600 0.74 2700 0.81 2800 0.89 2900 0.97 3000 1.06 3100 1.15 1071 3200...
  • Page 39 Table 15 — Fan Performance 558F120,121 — Vertical Discharge Units; Standard Motor (Belt Drive)* AIRFLOW (Cfm) Watts 3000 0.64 3100 0.69 3200 0.75 3300 0.81 3400 0.88 3500 0.94 3600 1.02 3700 1.09 3800 1.17 1028 3900 1.25 1101 4000 1.34 1178 4100...
  • Page 40 Table 16 — Fan Performance 558F120,121 — Vertical Discharge Units; Alternate Motor (Belt Drive)* AIRFLOW (Cfm) Watts 3000 0.64 3100 0.69 3200 0.75 3300 0.81 3400 0.88 3500 0.94 3600 1.02 3700 1.09 3800 1.17 1028 3900 1.25 1101 4000 1.34 1178 4100...
  • Page 41 Table 17 — Fan Performance 558F120,121 — Vertical Discharge Units; High-Static Motor (Belt Drive)* AIRFLOW (Cfm) Watts 3000 0.64 3100 0.69 3200 0.75 3300 0.81 3400 0.88 3500 0.94 3600 1.02 3700 1.09 3800 1.17 1028 3900 1.25 1101 4000 1.34 1178 4100...
  • Page 42 Table 18 — Fan Performance 558F150,151 — Vertical Discharge Units; Standard Motor (Belt Drive)* AIRFLOW (Cfm) Watts 3800 1.20 1116 3900 1.28 1197 4000 1.37 1281 4100 1.47 1370 4200 1.57 1462 4300 1.67 1559 4400 1.78 1660 4500 1.89 1766 4600 2.01...
  • Page 43 Table 19 — Fan Performance 558F150,151 — Vertical Discharge Units; Alternate Motor (Belt Drive)* AIRFLOW (Cfm) Watts 3800 1.20 1116 3900 1.28 1197 4000 1.37 1281 4100 1.47 1370 4200 1.57 1462 4300 1.67 1559 4400 1.78 1660 4500 1.89 1766 4600 2.01...
  • Page 44 Table 20 — Fan Performance 558F090,091 — Horizontal Discharge Units; Standard Motor (Belt Drive)* AIRFLOW (Cfm) Watts 2250 0.43 2300 0.45 0.49 2400 0.54 2500 0.56 2550 0.59 2600 0.64 2700 0.70 2800 2900 0.75 0.82 3000 0.88 3100 0.95 3200 1.03 3300...
  • Page 45 Table 21 — Fan Performance 558F090,091 — Horizontal Discharge Units; Alternate Motor (Belt Drive)* AIRFLOW (Cfm) Watts 2250 0.43 0.45 2300 0.49 2400 0.54 2500 0.56 2550 2600 0.59 0.64 2700 2800 0.70 0.75 2900 3000 0.82 0.88 3100 0.95 3200 1.03 3300...
  • Page 46 Table 22 — Fan Performance 558F090,091 — Horizontal Discharge Units; High-Static Motor (Belt Drive)* AIRFLOW (Cfm) Watts 2250 0.43 0.45 2300 0.49 2400 0.54 2500 0.56 2550 2600 0.59 0.64 2700 2800 0.70 0.75 2900 3000 0.82 0.88 3100 0.95 3200 1.03 3300...
  • Page 47 Table 23 — Fan Performance 558F102,103 — Horizontal Discharge Units; Standard Motor (Belt Drive)* AIRFLOW (Cfm) Watts 2200 0.41 2250 0.43 2300 0.45 2400 0.49 2500 0.54 2550 0.56 2600 0.59 2700 0.64 2800 0.70 2900 0.75 3000 0.82 3100 0.88 3200 0.95...
  • Page 48 Table 24 — Fan Performance 558F102,103 — Horizontal Discharge Units; High-Static Motor (Belt Drive)* AIRFLOW (Cfm) Watts 2200 0.41 2250 0.43 2300 0.45 2400 0.49 2500 0.54 2550 0.56 2600 0.59 2700 0.64 2800 0.70 2900 0.75 3000 0.82 3100 0.88 3200 0.95...
  • Page 49 Table 25 — Fan Performance 558F120,121 — Horizontal Discharge Units; Standard Motor (Belt Drive)* AIRFLOW (Cfm) Watts 3000 0.58 3100 0.63 3200 0.68 3300 0.74 3400 0.80 3500 0.86 3600 0.93 3700 1.00 3800 1.07 3900 1.15 1008 4000 1.23 1080 4100 1.32...
  • Page 50 Table 26 — Fan Performance 558F120,121 — Horizontal Discharge Units; Alternate Motor (Belt Drive)* AIRFLOW (Cfm) Watts 3000 0.58 3100 0.63 3200 0.68 3300 0.74 3400 0.80 3500 0.86 3600 0.93 3700 1.00 3800 1.07 3900 1.15 1008 4000 1.23 1080 4100 1.32...
  • Page 51 Table 27 — Fan Performance 558F120,121 — Horizontal Discharge Units; High-Static Motor (Belt Drive)* AIRFLOW (Cfm) Watts 3000 0.58 3100 0.63 3200 0.68 3300 0.74 3400 0.80 3500 0.86 3600 0.93 3700 1.00 3800 1.07 3900 1.15 1008 4000 1.23 1080 4100 1.32...
  • Page 52 Table 28 — Fan Performance 558F150,151 — Horizontal Discharge Units; Standard Motor (Belt Drive)* AIRFLOW (Cfm) Watts 3800 1.07 3900 1.15 1069 4000 1.23 1144 4100 1.31 1223 4200 1.40 1305 4300 1.49 1392 4400 1.59 1482 4500 1.69 1577 4600 1.80 1675...
  • Page 53 Table 29 — Fan Performance 558F150,151 — Horizontal Discharge Units; Alternate Motor (Belt Drive)* AIRFLOW (Cfm) Watts 3800 1.07 3900 1.15 1069 4000 1.23 1144 4100 1.31 1223 4200 1.40 1305 4300 1.49 1392 4400 1.59 1482 4500 1.69 1577 4600 1.80 1675...
  • Page 54: Pre-Start-Up

    PRE-START-UP WARNING: Failure to observe the following warn- ings could result in serious personal injury: 1. Follow recognized safety practices and wear protective goggles when checking or the servic- ing refrigerant system. 2. Do not operate the compressor or provide any electric power to the unit unless the compressor terminal cover is in place and secured.
  • Page 55 2. Energize the compressor. 3. The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up. If the suction pressure does not drop and the discharge pres- sure does not rise to normal levels: 1.
  • Page 56: Service

    SERVICE CAUTION: When servicing unit, shut off all elec- trical power to unit to avoid shock hazard or injury from rotating parts. I. CLEANING Inspect unit interior and exterior at the beginning of each heating and cooling season or more frequently as operating conditions require.
  • Page 57 II. LUBRICATION A. Compressors Each compressor is charged with correct amount of oil at the factory. B. Fan-Motor Bearings Fan-motor bearings are of the permanently lubricated type. No further lubrication is required. No lubrication of condenser-fan or evaporator-fan motors is required. III.
  • Page 58 Refer to Tables 1A and 1B. CIRCUIT NO. 1 XI. REPLACEMENT PARTS A complete list of replacement parts may be obtained from any Bryant distributor upon request. Fig. 41 — Cooling Charging Chart; 558F090 Fig. 42 — Cooling Charging Chart; 558F102 —...
  • Page 59 CIRCUIT NO. 2 CIRCUIT NO. 1 Fig. 43 — Cooling Charging Chart; 558F120 Fig. 44 — Cooling Charging Chart; 558F150 — —...
  • Page 60 Fig. 45 — Cooling Charging Chart; 558F091 Fig. 46 — Cooling Charging Chart; 558F103 (Circuits 1 and 2) — —...
  • Page 61: Troubleshooting

    A functional view of the EconoMi$er is shown in Fig. 50. Typical settings, sensor ranges, and jumper positions are also shown. An EconoMi$er IV simulator program is avail- able from Bryant to help with EconoMi$er IV training and troubleshooting. —...
  • Page 62 A. EconoMi$er IV Preparation This procedure is used to prepare the EconoMi$er IV for troubleshooting. No troubleshooting or testing is done by performing the following procedure. NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm resistor, and a 5.6 kilo-ohm resistor which are not supplied with the EconoMi$er IV.
  • Page 63 — Contactor, Compressor — Capacitor — Circuit Breaker COMP — Compressor Motor EQUIP — Equipment — Freeze Up Protection Thermostat — Ground — Heater Contactor — High-Pressure Switch — Indoor Fan Contactor — Indoor Fan Motor IFMOVL — Indoor Fan Motor Overload Switch —...
  • Page 64 PROBLEM Compressor and Power failure. Condenser Fans Fuse blown or circuit breaker tripped. Will Not start. Defective thermostat, contactor, transformer, or control relay. Insufficient line voltage. Incorrect or faulty wiring. Thermostat setting too high. Compressor Will Not Start Faulty wiring or loose connections in compressor But Condenser Fans Run.
  • Page 65 INPUTS Enthalpy* Demand Control Ventilation (DCV) Outdoor Below set High (DCV LED Off) (Free Cooling LED Off) (Free Cooling LED On) Above set High (DCV LED On) (Free Cooling LED Off) (Free Cooling LED On) *For single enthalpy control, the module compares outdoor enthalpy to the ABCD set point.
  • Page 66: Index

    Access panels Barometric flow capacity Charging chart, refrigerant 58-61 Clearance 2, 5, 6 sensor Configuration Settings 28, 30 Compressor Lubrication Mounting Rotation Condensate drain Cleaning Location 2, 4 Condenser coil 7, 8 Cleaning Condenser fan 7, 8 Adjustment Control circuit Wiring 9, 22 Wiring raceway...
  • Page 67 Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including: • Unit Familiarization • Installation Overview A large selection of product, theory, and skills programs are available, using popular video-based formats and materials.
  • Page 68 Copyright 2005 Bryant Heating & Cooling Systems Printed in U.S.A. CATALOG NO. 04-53558002-01...
  • Page 70: Start-Up Checklist

    VERIFY 3-PHASE SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION GENERAL VERIFY ECONOMI$ER IV MINIMUM VENT POSITION AND CHANGEOVER SETTINGS ARE CONFIGURED TO JOB REQUIREMENTS (IF EQUIPPED) Copyright 2005 Bryant Heating & Cooling Systems START-UP CHECKLIST (Remove and Store in Job File) TECHNICIAN: _________________________________________...

Table of Contents

Save PDF