CEFL PIR DSIP: PIR occupancy switch (presence detection) with DSI
daylight linked dimming (does not require a momentary (retractive wall
switch).

Troubleshooting

The load will not switch on:
• The moving body is not emitting more IR than the background.
(Person wearing insulating clothing in a warm environment)
• Person is too far from the PIR switch, see detection diagram.
• Person is moving unusually slowly (perhaps when testing).
Precautions and Warranty
This product conforms to BS EN 60669-2-1 and BS EN 55015.
Please ensure the most recent edition of the appropriate local wiring regulations are observed
and suitable protection is provided e.g. a 10 amp circuit breaker and voltage surge protection.
Please ensure that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products
Please call for more information or a free catalogue, or visit our website.
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
E-mail: sales@danlers.co.uk
Web: www.danlers.co.uk
Company Registered Number 2570169 VAT Registration Number 543 5491 38
17/08/16
INS265 CEFLA PIR DSIP
PIR occupancy switch with DSI dimming
CEFLA PIR DSIP
DANLERS passive infra-red occupancy (absence detection) switches
with closed loop control (CEFLA PIR DSIP) can be used to control high
frequency DSI dimmable ballasts. The product can be flush mounted into
suspended and plasterboard ceilings (diagram A). It includes two 2 metre
connecting flexes, one 4-core cable for the supply and one 2-core cable
for the DSI control.
These PIR switches incorporate a passive infra-red quad sensor to detect
movement of a warm body within their detection zone (diagram B) and a
photocell to monitor the ambient light level.

Functions

When entering a zone of detection a momentary wall switch must be pressed
to send a signal to the PIR to switch the lights ON at maximum and start
the closed loop control to maintain the preset lux level value (LUX) between
30 and 1000 lux (default value 1000 lux). See diagram D.
NO BACKGROUND ILLUMINANCE RUN ON TIME SET: If no further
movement is detected the lights will switch OFF after the set PIR hold timer
(TIME) has expired. This time lag can be set via the TIME adjuster to 10
seconds, 20s, 40s, 80s, 2m30s, 5m, 10m, 20m or 40 minutes (default value
10 seconds). See diagram C. Alternatively, the momentary switch can be
pressed for more than 2 seconds to switch the lights OFF.
BACKGROUND ILLUMINANCE RUN ON TIME SET: If no further movement
is detected the lights will FADE to minimum after the set PIR hold timer
(TIME) has expired OR if the momentary wall switch is pressed for more
than 2 seconds. The lights will then stay at minimum until the background
hold timer (RUN ON) has expired. The RUN ON time can be set via the
RUN ON adjuster to 0, 1, 2, 5, 10, 15, 20, 30 minutes or infinite (default
value is 0). See diagram D.
If the momentary wall switch is pressed for less than 2 seconds while
the background hold timer is counting down, the lights will switch ON at
maximum and start the closed loop control to maintain the set lux level value.

Loading

These PIR switches can switch up to:
6 amps (1500W) of dimmable fluorescent lamps.
2 amps (500W) of CFL, LED Drivers and LED lamps and fittings.
CEFLA PIR DSIP has an integral DSI Power Supply Unit suitable for use
with up to 12 DSI ballasts, assuming each ballast has a constant current
output of 1mA.