Operating Mode 3 - Relay Not Monitored (Floating) - Honeywell Esser RZT 8000 Installation Instruction

Refurbishment zone transponder
Table of Contents

Advertisement

Available languages

Available languages

6.3

Operating mode 3 - relay not monitored (floating)

When the relay is activated, the switching contacts operate as programmed in the customer data of the
FACP. The available options are: NO and NC.
When a relay is activated, the external AC or DC supply voltage is switched through to the connected
external device, e.g. on optical and/or audible signalling device.
If the relays are used to control inductive loads, appropriate protection by means of a diode or varistor
must be provided.
Arrange jumpers (X10 to X15) for mode selection in accordance with Fig.
settings for relay output 1: jumpers X10, X11, X12
settings for relay output 2: jumpers X13, X14, X15
X1
+12V
0V
Jumper closed
Jumper open
Fig. 12 : Application example – Operating mode 3 (relay not monitored / floating)
When the NO/NC operation mode has been changed the detector data must be programmed
corresponding to this modification (refer to online help for tools 8000 programming software).
Max. contact load of relays K1 and K2: 30 V DC / 1 A or 48 V AC / 0.5 A
FB 789807.10 / 05.17
Refurbishment Zone Transponder RZT 8000
F1
T1,25A
X3
BR1
BR2
BARCODE
X7.2
Isolator
788612
X7.1
X4
K1
K2
25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Esser 80863x.10

Table of Contents