DOK-SUPPL*-VAU*01.1U**-PR03-EN-P
Rexroth IndraControl VAU 01.1U UPS with USB interface
4

Technical Data

4.1

Degree of Protection and Weight

4.2

Input Voltage and Output Voltage

4.2.1

Input Voltage+24 V

4.2.2

Output Voltage

Degree of protection
Weight
Fig.4-1:
Degree of protection and weight
Nominal input voltage
Input voltage range
Emitted interference and surge immunity
Current consumption for U
N
Input fuse
Switch-on threshold
Switch-off threshold
Maximum power consumption
Reverse voltage protection
Fig.4-2:
Input voltage 24 V
Nominal output voltage
Output voltage range
Current output at U
N
Switching time
Bridging time
Max. output power
Short-circuit protection
Max. capacitive load
Fig.4-3:
Output voltage
NOTICE
The maximum power consumption of the connected control cabinet PC or
panel PC must not exceed the maximum output power of the VAU 01.1U.
Bosch Rexroth AG
IP 20
3.5 kg
DC 24 V
DC 24 V +20 %, -15 %
U
= 35 V (for t < 100 ms)
max
Max. 12 A (2 A for charging the battery)
None
22 V ±5 %
19 V ±5 %
288 W (48 W for charging the battery)
Yes
DC 24 V
DC 24 V +20 %, -15 %
10 A max.
< 1 ms
3 minutes max.
240 W
No
5600 μF
Overheating and possible damage to the
VAU 01.1U if the max. power consumption is
exceeded.