Manual 
MDT Temperature Controller
 
 
 
SCN‐RT 6REG.01 
 
SCN‐RT 6AP.01 
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1
1
Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de

Advertisement

Table of Contents
loading

Summary of Contents for MDT Technologies SCN-RT 6REG.01

  • Page 1 10/2011    Manual  MDT Temperature Controller       SCN‐RT 6REG.01    SCN‐RT 6AP.01  MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 2: Table Of Contents

    4.4.4 Blocking objects  ........................ 26  4.5.5 Heating/Cooling request objects  .................. 27  4.5.6 Dead zone  .......................... 28  4.6 Controller settings ........................ 30  4.6.1 Control value ........................ 30  4.6.2 PI control continuous ...................... 31  4.5.3 PI control switching (PWM)  .................... 34  4.6.4 2‐step control (switching)..................... 36  4.6.5 Direction of controller ...................... 38  4.6.6 Additional settings for heating and cooling ................. 39  5 Index .............................. 43  5.1 Register of Illustrations ....................... 43  5.2 List of tables.......................... 44      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 3 6 Attachment  ............................ 45  6.1 Statutory requirements  ....................... 45  6.2 Routine disposal .......................... 45  6.3 Assemblage  .......................... 45  6.4 Controller  ............................. 46  6.4.1 2‐Step control  ........................ 46  6.4.2 PI‐control continuous ...................... 47  6.4.3 PI‐control switching (PWM) .................... 48  6.5 Direction of controller ......................... 49  6.6 Datasheet ............................ 50      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 4: 2 Overview

     SCN‐RT6AP.01 – 6‐fold Temperature controller/sensor, flush mounted  o Controller type: 2 Step, PI‐continuous, PI switching (PWM); surface mounted; Measuring  of temperature by external PT1000 sensors, e.g. SCN‐PTST3.01(standard version), SCN‐ PTAN3.01(strap on installation), SCN‐PTDE3.01(ceiling installation)    2.2 Usage & Areas of use    The room temperature controller has its areas of use at the controlling in home installations and in  the object range.  A lot of different controls can be realized by the room temperature controller. There are three  integrated controllers, which can be adjusted to the present system. The three controllers can  control as well heating systems as cooling systems. There are setting options for up to 4 different  operating modes. Additional levels, blocking functions, alarms and messages can also be adjusted.  The 6‐fold controller has 6 channels; every channel can be deactivated or activated and adjusted  individually. Every channel needs a certain sensor. We have the following external sensors in our  assortment: SCN‐PTST3.01, SCN‐PTAN3.01 and SCN‐PTDE0.01. The SCN‐TS1UP.01 can also be used  for measuring.      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 5: Exemplary Circuit Diagram

    LED.        Illustration 2: Temperature Controller modular      Illustration 3: Temperature Controller surface mounted           SCN‐RT6REG.01                  SCN‐RT6AP.01            MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 6: Functions

    The following sub menus are for every of the 6 channels available and individual parameterize able:     Temperature measurement  The settings for the measurement for the temperature can be made at this menu. Settings  for the min/max values and the sensor configuration are available at this parameter.  All sensors contain of an in‐plant balance.   Alarm/Messages  Alarms and messages can be adjusted at this menu. This alarms and messages report when  the temperature falls below an adjusted value or exceed an adjusted value.   Controller general  At this menu, the desired function (heating, cooling or heating & cooling) can be assigned  and general settings, like setpoints, can be adjusted.   Controller settings  This menu appears as soon as the controller has got a function assigned. Integrated  controllers can be chosen at this menu and the chosen controller can be parameterized  further.      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 7: Übersicht Funktionen

     Cooling   Heating & Cooling  Priority  Order of the operating modes adjustable  Basis‐Setpoint  Reference point of the temperature control  Setpoints  Reference points for operating modes and  controller modes parameterize able   Shift of setpoints  Max. shift parameterize able   Scope of the shift parameterize able   can be saved  Blocking objects  can be used for heating and cooling separately      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 8: Settings At The Ets-Software

      2.7 Starting up   After wiring the allocation of the physical address and the parameterization of every channel follow:  (1) Connect the interface with the bus, e.g. MDT USB interface  (2) set bus power up  (3) Press the programming button at the device(red programming LED lights)  (4) Loading of the physical address out of the ETS‐Software by using the interface(red LED goes  out, as well this process was completed successful)  (5)  Loading of the application, with requested parameterization  (6) Switch the power supply on  (7) If the device is enabled you can test the requested functions(also possible by using the ETS‐ Software)      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 9: Default Settings Of The Communication Objects

      21  Channel 1  Reset setpoint value 1 Bit X    22  Channel 1  DPT_HVAC Status 1 Byte X  23  Channel 1  Error external Sensor 1 Bit X  24  Channel 1  Actual setpoint 2 Byte X  MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 10         191  Channel 1 Chart 2: Communication objects – default settings    *temperature signal of an external sensor must be connected to this communication object    You can see the default values for the communication objects from the upper chart. According to  requirements the priority of the particular communication objects as well as the flags can be  adjusted by the user. The flags allocates the function of the objects in the programming thereby  stands C for communication, R for Read, W for write, T for transmit and U for update.      The communication objects are identical for all channels, but increase their numbers as shown at the  chart. If a channel is deactivated, no objects will be shown for this channel.          MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 11: 4 Reference Ets-Parameter

     SCN‐RT6REG without Sensor  Select hardware  Adjustment of the used device    REG     SCN‐RT6AP with Sensor  Chart 3: General settings      The parameter startup timeout adjusts the time between an upload and the functional start of the  device. The used hardware reacts only after expiration of the adjusted time. All input commands  before the startup timeout expire.  Additional, you have to select the used hardware at this menu.  There are additional settings at the devices with setwheel and display. These settings are described  at the following segments.        MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 12: Channel Selection

    [default value]   inactive  Channel 1‐6  When the channel gets activated, new   active  sub menus appear at the left selection    menu. For a deactivated channel are no  further parameterization options.    Chart 4: Channel selection     If a channel is deactivated, there will be no further parameterization options for this channel and the  sub menus will be hidden. The sub menus, for an activated channel, are shown below its channel. At  these sub menus, the further parameterization can be adjusted.          MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 13: Temperature Measurement

    [0]  (only at RT6AP)   100% intern  Internal/external sensor  Adjustment of the balance between   90% intern/ 10% extern  (only at RT6AP)  internal and external sensor   80 % intern/ 20% extern   …   100% extern  Chart 5: Parameter Temperature measurement    The effects of the settings are described at the following page.        MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 14 The communication objects for an activated external sensor are shown at the chart:   Number  Name  Length Usage 5  External sensor  2 Byte  sends the measured temperature value of the  external sensor  23  Error external sensor  1 Bit  sends an error, when the external sensor sends  no value for more than 30min  Chart 8: Communication objects external sensor      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 15: Alarm/Messages

     not active  Messages  Activation of the message function   active  Message if value >  18°C‐40°C  Dynamic range of the upper message  [26°C]  Adjustment possible if messages are  activated  Message if value <  1°C‐25°C  Dynamic range of the lower message  [13°C]  Adjustment possible if messages are  activated  Chart 9: Parameter Alarm/Messages          MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 16 Number  Name  Length Usage 1  Higher message value  1 Bit  Send the achievement of the higher reporting  limit  2  Below message value  1 Bit  Send the achievement of the lower reporting  limit  Chart 11: Communication objects messages              MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 17: Controller General

    [default value]   Controller off  Controller type  Adjustment of the controller type   Heating  The further settings depent to the adjusted   Cooling  controller type   Heating and Cooling  Chart 12: Setting controller type    The controller type defines the function of the room temperature controller. Target of the control is  to keep an adjusted temperature constant. There are a lot of settings, which can help to achieve this  aim. The settings depend to the adjusted controller type.   By choosing the setting “controller off”, no further settings are possible.      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 18: Operating Modes & Setpoints

    0 K – 10,0 K  mode was chosen  [2,0 K]  The lowering is relative to the basis  comfort setpoint.  Setpoint frost protection  3°C – 12°C  Setpoint of the operating mode frost  [7°C]  protection.  indicated by an absolute value  Setpoint heat protection  24°C – 40°C  Setpoint of the operating mode heat  [35°C]  protection.  indicated by an absolute value  Chart 13: Operating modes & setpoints        MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 19 The chart shows the relevant 1‐Bit communication objects:  Number  Name  Length Usage 12  Mode frost protection  1 Bit  Activation of the operating mode frost protection   12  Mode heat protection  1 Bit  Activation of the operating mode heat protection   12  Mode frost/heat protection  1 Bit  Activation of the operating mode frost/heat  protection   Chart 16: Communication object operating mode frost/heat protection      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 20 1  0  Night  0  0  1  Frost‐/Heat protection  0  0  0  Standby  1  0  1  Frost‐/Heat protection  1  1  0  Comfort  Chart 18: Example changeover of the operating modes via 1 Bit      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 21 4        5  Heating/Cooling  0=Cooling/1=Heating  0x20  6        7  Frost alarm  1=Frost alarm  0x80  Chart 21: Hex‐Values DPT HVAC Status     If you heat at the comfort mode, the communication object will send the value 20 (for heating) +1  (for the comfort mode) =21.      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 22 Mode Night  1 Bit  Activation of the mode night  12  Mode Frost/Heat protection  1 Bit  Activation of the mode Frost/ Heat protection  22  DPT_HVAC Status  1 Byte  Visualization of the chosen operating mode  25  DPT_RHCC Status  2 Byte  Visualization measuring/ status of the controller  26  mode selection  1 Byte  Selection of the operating mode  Chart 23: Communication objects for the operating mode changeover      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 23   Illustration 11: Operating mode after reset    The following chart shows the dynamic range for this parameter:  ETS‐text  Dynamic range  comment  [default value]   Comfort  Operating mode after reset  Adjustment, which operating mode shall   Standby  be switched on after a bus power return  Chart 24: Operating mode after reset    This parameter defines the operating mode, which shall be adjusted after a bus power return. The  controller can start with the comfort mode or with the standby mode.         MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 24: Setpoint Offset

     No  Send setpoint change  Adjustment, whether a change of mode   Yes  should be send or not  Chart 25: Setpoint offset    The setpoint can be changed manual by the setpoint offset without a new parameterization by the  ETS‐Software. Therefore, 2 variants are available. On the one hand a new setpoint can be pretended  by the communication object “Setpoint comfort”. On the other hand the adjusted setpoint can be  increased or decreased manual by the communication object “manual setpoint value offset”.  At the read in of a new absolute comfort setpoint, the controller becomes a new basis comfort  setpoint. The new basic comfort setpoint causes also an adaption of the indirect setpoints at the  other operating modes. Through this function it is for example possible to read the actual room  temperature as new basic comfort setpoint in. The settings “max setpoint offset”, “max setpoint  offset valid for” and “Reset setpoint offset after change of mode” are not valid at this variant of  setpoint offset, because the controller becomes a complete new setpoint. Specifying a new value is  possible by calling the object “Setpoint comfort”.       MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 25 Number  Name  Length Usage 6  Setpoint comfort  2 Byte  Parameterization of a new absolute comfort  setpoint  7  Manual setpoint value offset  2 Byte  Movement of the setpoint depending to the  current adjusted basic comfort setpoint  24  Actual setpoint  2 Byte  Readout of the actual adjusted setpoint  Chart 26: Communication objects setpoint offset        MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 26: Blocking Objects

    If the heating must not start at special situations, for example when a window is opened, the  blocking object can be used. Another usage of this function is for example the manual blocking, for  example by a push button, in case of a cleaning process.  The blocking objects have the size of 1 Bit and blocks by sending a logical 1 at the depending  communication object.    The chart shows the relevant communication objects:  Number  Name  Length Usage 13  Heating disable object  1 Bit  blocks the control value heating  14  Cooling disable object  1 Bit  blocks the control value cooling  Chart 28: Communication objects blocking objects      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 27: Heating/Cooling Request Objects

    A further opportunity for the usage is the central switch of a heating or cooling process. So can be  realized that all heating devices of a building switch on, when a controller gives out a heating  request.  The 1 Bit communication object gives as long a 1‐signal out as the process is active.    The following chart shows the relevant communication objects:  Number  Name  Length Usage 15  Heating request  1 Bit  indicates a beginning heating process  16  Cooling request  1 Bit  indicates a beginning cooling process  Chart 30: Communication objects heating/cooling request      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 28: Dead Zone

    Dead zone between heating  1,0K – 10,0K  Dynamic range for the dead zone  and cooling (K)  [2,0K]  (Range at which the controller does not  activate cooling or heating)  Chart 31: Dead zone      The settings for the dead zone are only available, when the controller type (have a look at 4.4.1  controller type) was set as heating and cooling. Now the dead zone can be parameterized.  The dead zone describes the range at which the controller neither heats nor cools. So the controller  sends no value to the control value, when he is in the dead zone. At the setting for the dead zone, it  is to note, that a value which was chosen too small causes many switches between heating and  cooling. Whereas, a too big chosen value causes a wide range of the current room temperature.  When the controller is set as heating and cooling, the basic comfort setpoint is always the setpoint  for heating. The setpoint for the cooling is given by the summation of basic comfort setpoint and  dead zone. So, when the basic comfort setpoint is set to 21°C and the dead zone is set to 3K, the  setpoint for heating is 21°C and the setpoint for cooling is 24°C.      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 29  Technical Manual Temperature Controller SCN‐RT1   The dependent setpoints for heating and cooling, so the setpoints for the operating modes standby  and night, can be parameterized individually at the controller type heating and cooling. So you can  set different values for the nigh and standby reduction/increase at heating and cooling. These  setpoints are calculated in dependence to the basic comfort setpoints.  The setpoints for the frost and heat protection are individually from the dead zone and the other  setpoints.  The following illustration shows the correlations between dead zone and the setpoints for the single  operating modes.  The following settings are made for this example:  Basic comfort setpoint: 21°C  Dead zone between heating and cooling: 3K  Increase and Reduction standby: 2K  Increase and Reduction night: 4K    Illustration 16: Example dead zone        MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 30: Controller Settings

    1 Bit  8  Control value heating/cooling  1 Byte/  controlling of the combined actuator for  1 Bit  heating and cooling  9  Control value cooling  1 Byte/  controlling of the actuator for cooling  1 Bit  Chart 33: Communication objects control value      According to the adjusted controller type (4.5.1), the control value controls a heating and/or a  cooling process. If the control value is chosen as PI control continuous, the communication objects  will have the size of 1 Byte, because the object can assume several states. If the control value is  chosen as PI control switching or 2‐step control, the communication object will have the size of 1 Bit,  because the communication object can only assume the states on or off.      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 31: Direction Of Controller

    By choosing heating/cooling system as  [150 min]  “Adjustment via control parameter”, the  reset time can be parameterized freely  Send control value cyclic  Disable, 1 min, 2min, 3min, 4 min,  Activation of cyclic sending of the  5min, 10min, 15min, 20min, 30min,  control value with adjustment of the  40min, 50min, 60min  cyclic time  [Disable]   No  Use additional level  Activation of an additional level   Yes  available, only for heating (4.5.6)  Chart 34: PI control continuous      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 32     4.6.2.3 Proportional range   The proportional range describes the P‐amount of the controlling. The P‐amount produces a  proportional increment to the deviation of the control value.  A small proportional range causes a short recovery time of the deviation. The controller reacts  thereby almost immediately and sets the control value already at a small deviation almost to the  maximum value (=100%). If the proportional range is chosen too small, the system will swing across.    The following setting rules can be defined:     small proportional range: swing across possible at change of setpoint; usage at fast systems;  small recovery times   big proportional range: almost no danger of swing across; long recovery times, usage at slow  systems which need huge amplifications (big heating power etc.)          MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 33 To note is, that a reset time, which is adjusted too small, can cause across swinging. In principle you  can say each carrier the system, each bigger the reset time.    The following setting rules can be defined:     small reset time: fast regulating of deviations; usage at fast systems and at places with  changing environmental conditions (disturbance variables like draft); danger of swinging  across   big reset time: slow regulating of deviations; almost no danger for swinging across; usage at  slow systems as underfloor heating      4.6.2.5 Send control value cyclic   The parameter “Send control value cyclic” causes a cyclic sending of the actual control value. The  time shifts between two values can be also parameterized.        MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 34 100%; 90%; 80%; 75%; 70%; 60%;  indicates the output power at maximum  50%; 40%; 30%; 25%; 20%; 10%; 0%  amount  [100%]   Warm water heating (5K/150  Heating system  Adjustment of the used heating system  min)  Individual parameterization available by   Underfloor heating (5K/240  “Adjustment via control parameter”  min)   Split Unit (4K/90min)   Adjustment via control  parameter      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 35 [10min]      At the pulse width modulation, the controller switches the control value according to the calculated  value of the continuous control on and off. Thereby the control watches also the adjusted cycletime.  So the control value is converted to a pulse width modulation with only the two conditions “0” and  “1”.    4.6.3.1 PWM cycletime   The cycletime, „PWM cycletime“, serves the controlling for calculating the length of the on‐pulse and  the off‐pulse. This calculation occurs at the base of the calculated continuous value in percent. One  PWM cycle contains the time, which elapses from one switching on point to the other.    Example: If a control value of 75% is calculated and a cycletime of 10min is adjusted, the  control value will be switched on for 7,5min and switched off for 2,5min.    In principle you can say each carrier the system, each bigger the cycletime.        MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 36 [2,0K]  the switching on point   No  Use additional level  Activation of an additional level   Yes  possible, only for heating (4.5.6)  Chart 36: 2‐step control (switching)      The 2‐step control is the easiest way of controlling. The controller switches the control value only on  and off.  The controller switches the control value (for example at heating) on, when the measured  temperature falls below a certain temperature. By exceeding a certain temperature, the control  value will be switched off again. The points for switching on and off depend to the current adjusted  setpoint and the adjusted hysteresis.  The 2‐step control is used in situations, where the control value can only have two conditions and the  controlled temperature can alternate a bit more.      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 37  Technical Manual Temperature Controller SCN‐RT1 4.6.4.1 Hysteresis   The setting of the hysteresis is used for calculating the points of switching on and off. This occurs  under consideration of the current adjusted setpoint.    Example: The controller is adjusted as heating with and a basic comfort setpoint of 21°C and  a hysteresis of 2K. So the controller switches the control value, at the mode comfort, on at  20°C and off at 22°C.    To note is that a big hysteresis generates big differences of the room temperature. A small hysteresis  can generate an almost permanent switching process, because the points for switching on and off  are very close to each other. This can generate a fast consumption of the control value.        MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 38 An inverted control value is for adaption to normally opened valves at the 2‐Step control and at the  PI‐control switching.  An inverted control value means for the single control values, by controller type heating, the  following adjustments   PI‐control continuous  The control value falls at raising regular difference and rises at falling regular difference.    PI‐control switching  The ratio between duration of switching on to the whole PWM cycletime raise by falling  temperature and falls by raising temperature.   2‐Step control  The controller switches on at the normal point for switching off and switches off at the  normal point for switching on.          MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 39: Additional Settings For Heating And Cooling

     4 Pipe system  and cooling circuits   automatically  Heating/cooling switch  Selection between manual and   via object  over  automatic switch over  Chart 37: Heating & Cooling    When the controller type (4.5.1) is chosen as heating and cooling, the upper shown settings are  available.  By the setting for the system, the used system can be chosen. When a combined heating and cooling  system is used, the setting 2 Pipe system must be chosen. When a divided system for heating and  cooling is used, the setting 4 Pipe system must be chosen.  Furthermore it is possible to choose between an automatic and a manual switch over.        MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 40  Technical Manual Temperature Controller SCN‐RT1 4.6.6.1 ‐ 2 Pipe system   At a common pipe system for heating and cooling, only one communication object for the control  value is available. Before changing between heating and cooling, a switchover must occur. The  control value can also have only one controller (PI‐continuous, PI‐switching, 2‐Step control). Also the  direction must be identical for heating and cooling. But the parameter for the heating and cooling  process can be defined individually (as described from 4.5.2 to 4.5.4).    The following illustration shows the setting option for a 2 Pipe system:    Illustration 23: 2 Pipe system        MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 41  Technical Manual Temperature Controller SCN‐RT1 4.6.6.2 ‐ 4 Pipe system   When a divided pipe system is used, both operations can be parameterized individually.  Consequently two communication objects for the control value exist. So it is possible, to control the  heating process e.g. via a PI‐control continuous and the cooling process e.g. via a 2‐step control,  because both processes are controlled by different devices. So for every of the both processes are  the settings available, which are described from “4.5 controller settings”.    The following illustration shows the setting options for a 4 Pipe system:    Illustration 24: 4 Pipe system        MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 42 By choosing the switchover via object, an additional communication object is shown. By this object  the switchover can be done. The controller stays as long at the adjusted operating mode until it  becomes a signal via the according communication object. As long as the controller is at the heating  mode only the setpoint for the heating is watched, also if the controller is, according to its setpoints,  already at the cooling mode. A start of the cooling mode is also only possible, when the controller  becomes a signal via the communication object.  A “0” switches the heating process on and a “1” switches the cooling process on.    The following chart shows the relevant communication object:  Number  Name  Length Usage 19  Heating/Cooling switchover  1 Bit  Switchover between heating and cooling  0=heating; 1=cooling  Chart 38: Communication object heating and cooling      MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 43 Illustration 23: 2 Pipe system                Page 40  Illustration 24: 4 Pipe system                Page 41          MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 44     Page 36  Chart 37: Heating & Cooling                Page 39  Chart 38: Communication object heating and cooling          Page 42          MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 45: 6 Attachment

      The above‐described devices must not be used with devices, which serve directly or indirectly the  purpose of human, health‐ or lifesaving. Further the devices must not be used if their usage can  occur danger for humans, animals or material assets.  Do not let the packaging lying around careless, plastic foil/ ‐bags etc. can be a dangerous toy for kids.      6.2 Routine disposal    Do not throw the waste equipment in the household rubbish. The device contains electrical devices,  which must be disposed as electronic scrap. The casing contains of recyclable synthetic material.      6.3 Assemblage      Risk for life of electrical power!  All activities on the device should only be done by an electrical specialist. The county specific  regulations and the applicable EIB‐directives have to be observed.        MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 46: Controller

     Technical Manual Temperature Controller SCN‐RT1 6.4 Controller   Three different controller types can be chosen for the control value. These controller types are  described for the heating process by the following illustrations.    6.4.1 2‐Step control           MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 47: Pi-Control Continuous

     Technical Manual Temperature Controller SCN‐RT1 6.4.2 PI‐control continuous         MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 48: Pi-Control Switching (Pwm)

     Technical Manual Temperature Controller SCN‐RT1 6.4.3 PI‐control switching (PWM)       MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 49: Direction Of Controller

     Technical Manual Temperature Controller SCN‐RT1 6.5 Direction of controller   MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 Tel.: +49-2263-880 • Fax: +49-2263-4588 • knx@mdt.de • www.mdt.de...
  • Page 50 • RHCC status and bit/byte objects to declare status • Desired value can be given by visualisation, e.g. MDT VisuControl • Integrated bus coupling unit • 3 years warranty DIN EN ISO 9001 MDT technologies GmbH 51766 Engelskirchen Papiermühle 1 • • TAW Cert Tel.: + 49 - 2263 - 880...
  • Page 51 IP 20 IP 20 Dimensions (W x H x D) 115mm x 64mm x 40mm Examplary circuit diagramm SCN-RT6REG.01 DIN EN ISO 9001 MDT technologies GmbH 51766 Engelskirchen Papiermühle 1 • • TAW Cert Tel.: + 49 - 2263 - 880 Fax: + 49 - 2263 - 4588 knx@mdt.de...