Page 2
Dear Customer, We congratulate you on choosing these product Clivet has been working for years to offer systems able to assure the maximum comfort for a long time with highly-reliable, efficient, high-quality and safe solutions. The target of the company is to offer advanced systems, that assure the best comfort and reduce energy consumption as well as the installation and maintenance costs for the entire life-cycle of the system.
Page 3
I N D E X Safety considerations Configurations Reception Selecting the installation site Water connections Aeraulic connections Electrical connections Start-up Control Maintenance Decommissioning Residual risks Technical information ...
S A F E T Y C O N S I D E R A T I O N S Manual The manual provides correct unit installation, use and maintenance. It is advisable to read it carefully so you will save time during operations.
Modification All unit modifications will end the warranty coverage and the manufacturer responsibility. Breakdown/Malfunction Disable the unit immediately in case of breakdown or malfunction. Contact a certified service agent. Use original spares parts only. Using the unit in case of breakdown or malfunction: ...
Unit identification The serial number label is positioned on the unit and allows to indentify all the unit features. The matriculation plate shows the indications foreseen by the standards, in particular: unit type serial number (12 characters) year of manufacture ...
Page 7
C O N F I G U R A T I O N S CAK configuration Single fan section for full recirculation R. Return air 3 3 2 2 1 1 S. Supply air 1. G4 efficiency filters + electronic filters (option) or F7 filter (option) 2.
Page 8
CCK configuration Double fan section for recirculation, fresh air, exhaust, thermodynamic recovery FA 3 2 1 Return air Supply air Fresh air Exhaust air S 1. G4 efficiency filters + electronic filters (option) or F7 filter (option) 2. Handling exchanger EX ...
Page 9
Supply and return configuration Standard unit Option Option Option Option Option Filters nomenclature according to EN ISO 16890 1° filtering stage - standard ISO 16890 Coarse 60% 2° filtering stage - option ISO 16890 ePM1 55% 2° filtering stage - option FES (electronic filters) ISO 16890 ePM1 90% ...
R E C E P T I O N Saftey Operate in compliance with safety regulations in force. For detailed information (dimensions, weight, technical characteristics etc.) please refer to the TECHNICAL INFORMATION section. Use single protection devices: gloves, glasses etc. Reception You have to check before accepting the delivery: ...
Page 11
Handling Caution Check that all handling equipment complies with local safety regulations (cran, forklifts, ropes, hooks, etc.). Provide personnel with personal protective equipment suitable for the situation, such as helmet, gloves, accident-prevention shoes, etc. Observe all safety procedures in order to guarantee the safety of the personnel present and the of material.
S E L E C T I N G T H E I N S T A L L A T I O N S I T E Positioning The unit must be level. Installation must be in accordance with local regulations. If they do not exist, follow EN378 .
Page 13
Avoid therefore: obstacles to the airflow exchange difficulties leaves or other foreign bodies that can obstruct the exchange batteries winds that hinder or favour the airflow heat or pollution sources close to the unit (chimneys, extractors etc) ...
Page 14
The Costumer is responsible for mounting the chimney kit during installation. Based on the specific installation requirements, the length of the chimney can be increased with suitable joints and fittings (not supplied by Clivet). Gas connection Read the gas heating module manual.
Page 15
A. Apply the flat adhesive gasket15x5 on the Gas Module flange perimeter to guarantee the absence of air bypass. B. Fix with screws the flue supporting bracket to the GM frontal panel C. Fix the extensions with clamps to the flue supporting bracket D.
Page 16
Connections performed by costumer rooftop supply fan gas module connecting cables electrical panel - terminal XG Gas use features...
W A T E R C O N N E C T I O N S Condensate drain The condensate must be disposed in order to avoid damages to people and things. Unit discharge fitting: the connection must not transmit mechanical stresses and must be performed taking care not to damage the unit discharge fitting.
Page 18
Immersed electrode humidifier Option Connexion humidificateur: 1” F Supply water The humidifier must be supplied with mains water having the following features: pressure between 0.1 and 0.8 Mpa (1 – 8 bar) temperature between 1 and 40°C Do not use: ...
A E R A U L I C C O N N E C T I O N S The dimensioning and correct execution of the aeraulic connections are fundamental to guarantee good unit operation and adequate level of silence in the room. When designing and manufacturing the ducting, consider LOAD LOSSES, AIR FLOW AND SPEED that must be consistent with the unit features.
E L E C T R I C A L C O N N E C T I O N S The characteristics of the electrical lines must be determined by specialized personnel able to design electrical installations; moreover, the lines must be in conformity with regulations in force. The protection devices of the unit power line must be able to stop the presumed short circuit current, whose value must be determined in function of system features.
Signals / data lines Do not overpass the maximum power allowed, which varies, according to the type of signal. Lay the cables far from power cables or cables having a different tension and that are able to emit electromagnetic disturbances. Do not lay the cable near devices which can generate electromagnetic interferences.
Page 23
Settable input (mode change / Fan only) Enabling selector to the umidifier manual discharge 910-911 Modulation of supply air flow and extraction (1) (2) Option It must be enabled and set up by personnel trained and authorised by Clivet Not provided by CLIVET ...
P.C. - not supplied Optional keypad RJ45 : standard connection Shift RJ45 from T-IP to T-HI P.C. configuration connect P.C. and main module with LAN cable check in the taskbar that the connection is active Control panel Network and sharing center Open and select Modify board setting...
Page 25
Remote control with user interface Distance up to 350 mt Connections Distance up to 700 mt user interface B = B1 KNX bus, max 350 mt twisted pair with shield, Ø 0,8 mm EIB/KNX cable marking recommended power supply unit N125/11 5WG1 125-1AB11 AC 120...230 V, 50...60 Hz ...
Page 26
MODBUS - RS485 Ogni linea seriale RS485 deve essere realizzata con sistema bus di tipo ‘Entra/Esci’. Non sono ammesse tipologie diverse. Every RS485 serial line must be set up using the 'In/ Out' bus system. Other types of networks are not allowed, such as Star or Ring networks ...
Page 27
BACNET LONWORK LED BSP communication with AP1 module LED BSP communication with AP1 module green communication ok green communication ok yellow software ok but communication with AP1 yellow software ok but communication with AP1 down down flashing : software error flashing : software error fixed : hardware error fixed : hardware error...
S T A R T - U P The indicated operations must be carried out by qualified technicians and specifically trained on the product. Upon request, the after-sales assistance centres execute start-up. The electric, hydraulic connections and the other work of the system are the responsibility of the installer.
Preliminary checks For details refer to the various chapters in the manual. unit ON power supply 1 compressor carter heaters ON from at least 8 hours 2 vacuum voltage measurement 3 phases sequence control 4 shut-off valve refrigerant circuit open (if present) 5 unit ON 6 load voltage measurement and absorptions 7 liquid sight glass check (no bubbles)
Electric Circuit Verify that the unit is connected to the ground plant. Check the conductors are tightened as: the vibrations caused by handling and transport might cause these to come loose. Connect the unit by closing the sectioning device, but leave it on OFF.
Standard mode The fan speed setting must be checked by a service centre authorised by Clivet The real unit flow is according to the aeraulic system features. Before checking, make sure that the system has been completed in all its parts (shunts, dampers, grilles, diffusers etc.).
ECO mode The fan rotation speed (or the delivery air flow if the constant flow option is present) stays constant as the thermal load varies and is shutdown when setpoint is fulfilled. To further increase the energy savings in this condition, it is also possible to set less demanding operation setpoints for the unit in respect to the standard mode.
Page 33
Ambient pressure control CCK or CCKP configurations only. The ambient pressure control device compares the return pressure with the external pressure and compensates any variations by acting on the outdoor air damper. This way, the unit maintains the relevant ambient pressure desired by the user, who can choose between the overpressure, depression or equal-pressure.
Page 34
Complete unit shutdown Fire alarm: configuration unit CAK, CBK, CCK, CCKP The unit cannot be used as smoke extractor. fire detection devices built-in unit must considered as an auxiliary safety system, and, accordingly, must not be a replacement for any fire detection devices in the room.
Demand limit It allows to temporarily limit the electrical capacity absorbed by the unit according to an ext. signal 0 - 10V. Higher is the signal and lower the number of available compressors, that is the electrical capacity absorbed. Enable the function : par 50 EnDemandLimit = Set the set Demand Limit: par 7 SetDL (%)
Page 36
2014/68/UE PED directive DIRECTIVE 2014/68/UE PED gives instructions for installers, users and maintenance technicians as well. Refer to local regulations; briefly and as an example, see the following: Compulsory verification of the first installation: only for units assembled on the installer’s building site (for ex.
C O N T R O L Keypad Keys and function change of status: OFF, ON, ECO, FAN ALARMS menu access (if available) set TIME and DATE set SCHEDULER (prolonged pressure) ...
OPERATIONAL MODES Setpoint MANUAL TEMPERATURE SETPOINT MANUAL The room setpoint can be MANUALLY modified from The choice between HEATING or COOLING mode keyboard at parameter n. 01 ManSet = xx °C . is manually carried out from keyboard, room thermostat or remote selector (see ELECTRIC Starting from this value, the module determines 2 CONNECTIONS chapter).
PARAMETERS MENU MANUAL SET POINT Press To change the manset manual 16.3 C° temperature Setpoint: 16.3 C° the access by password is reserved to press 17:00 qualified personnel, the parameters 17:00 changes can cause malfunctions. The unit: must be On En Climate must be = 0 enter password (0047) _ _ _ _...
Page 40
STATA MENU Press 16.3 C° 17:00 scroll the statuses 011.6 exit wait for 3 sec 16.3 C° when the time is displayed it is possible to carry out other operations 16.3 C° 17:00 Keyboard index STATUS SupplyTemp._B2:AI-687 ...
DATE AND HOUR BUTTON LOCK Press Press for 4 sec. 16.3 C° 16.3 C° 17:00 17:00 HOUR digits start flashing enter password confirm edit _ _ _ _ 17:00 confirm MINUTE digits start flashing example: T0 = "-" key edit ON = active key 17:00 see codes-key table...
Page 42
To visualize alarm in progress Caution Before resetting an alarm identify and remove its cause. Repeated resets can cause irreversible damage. press only if the ALARM symbol is flashing 16.3 C° 17:00 Type of alarm type of alarm (see table) Code Type Restore...
Page 43
SCHEDULER Scheduling days 2,4,5,6 Scheduling the 1st day, also the other days of the week are Caution automatically scheduled. Enable scheduler (see: menu parametres) It is possible to set up to 7 schedules (1 for every day of the Press 2 sec week) (only if the unit is not OFF)
Page 44
Scheduling days 1,3,7 press Scheduling the 1st day, also the other days of the week are automatically scheduled. --:-- 2 4 5 6 Press 2 sec Set event 1 (only if the unit is not OFF) example: Tuesday 05:30 FAN 16.3 C°...
Page 45
Modify scheduling press Example: --:-- day 5 change events 3 and 4 from ON to OFF Set event 1 example: Monday 05:30 FAN Time Event Wedne- press Monday Tuesday Thursday Friday Saturday Sunday sday -- starts flashing 05:30 (OFF) (OFF)
Page 46
press 15:00 press 4 times (= event 4) 15:00 press 3 times starts flashing 003 (= ON) 15:00 select mode 002 (=OFF) confirm 15:00 press 2 times to exit 16.3 C° 17:00...
SERVICE KEYPAD Function keys Main menu Alarm display 10.02.2012 10:15:30 SetPointAttuale 22.0°C Exit Temperatura ripresa 24.0°C Previous level Temperatura mandata 23.0°C Keyboard settings StatoAttuale ModoAttuale Cool Increases value Down Decreases value Confirm Password DISPLAY MEANING installed compressors ActualSetPoint temperature setting...
Page 48
MAIN MENU Select Main index Cmd Local state Cmd Local mode Cool Unit stata Unit parameters Select the Main index menu Cmd Local state Cmd Local mode Cool Confirm Unit stata Unit parameters Cmd Local state ...
Page 49
SCHEDULER KEYBOARD SETTINGS It is possible to set 6 events (Off, Eco, On, Recirculating) for Press 3 sec each week day. Scheduler must be enabled: Select display : actual value = On HMI settings : unit parameters service-maintenance, P0500=1 Confirm local connection Select Main index...
Page 50
To Visualize alarm in progress Press alarm log Caution Reset Passivo 10 Before resetting an alarm identify and remove its cause. + eE001 : Monitore fase : Fault Slide - EE003 : Guasto P1 Util : Ok Repeated resets can cause irreversible damage. + EE003 : Guasto P1 Util : Fault ........
Page 52
Main menù - installer use Cmd local state Cmd local Mode Unit Stata Circuit stata Press 3 sec. Password Circuit 1 stata Circuit 1 I/O stata Password Thermostatic stata 0 - - - General stata Central POL687-IO Expansion POL955 - I/O Thermoregulator insert maintenance password...
Page 54
ALARMIS- tab 2 Description Reset ff105 Overheating below minimum limit fF109 DI Low Pressure ff110 Cool Low pressure Pre-alarm ff111 Low Heat Pressure pre-alarm fF112 AI Low Pressure fF113 DI High Pressure ff114 High pressure pre-alarm ...
Page 55
Statia- tab 1 MENU Short description Description 1 Main Page Machine status Current unit status [0]:Off, [1]:ECO, [2]:ON, [3]:FAN 1 Main Page Machine mode Current unit mode [0]:COOL, [1]:HEAT 1 Main Page Current setpoint Current unit setpoint 1 Main Page No.
Page 56
Stata - tab 2 MENU Short description Description 3002 Expansion POL955 - IO Cmd Addition 2_Q2:DO-955 Addition 2 control 3002 Expansion POL955 - IO Cmd Addition 3_Q2:DO-955 Addition 3 control 3003 Thermoregulator Startup phase Start-up phase ...
Page 57
Stata - tab 3 MENU Short description Description 3003 Thermoregulator CPYCurrent CPY humidifier absorbed current 3003 Thermoregulator CPYIstSteam CPY humidifier output 3003 Thermoregulator Supply Q Air Supply air flow rate 3003 Thermoregulator Return Q Air Return air flow rate 3003 Thermoregulator Supply temp.
Page 58
Stata- tab 4 MENU Short description Description 3102 Circuit C1 -IO Stata T.DischargeC2_B2:AI-985 Compressor 2 discharge temperature 3102 Circuit C1 -IO Stata T.DischargeC3_X2:AI-985 Compressor 3 discharge temperature Source 1 temperature (for machines with reversible air source on 3102 Circuit C1 -IO Stata T.Source1_B3:AI-985 gas = Probe 1 on the source coil.
Page 59
Stata - tab 5 MENU Short description Description 0=Idle (motor off) 1=Init (valve initialised when completely closed) 3200 Thermostatic C1 Stata 1205 EEVMode 2=Manual (valve controlled in manual mode) 3=Control (the valve conducts adjustments to control SH) ...
Page 60
Statia- tab 6 MENU Short description Description 0 = Idle 1 = ECVAlarm 2 = FailSafe 3 = Referencing 4 = Positioning 3201 Thermostatic C2 Stata 2217 ECVState 5 = Positioned 6 = ECVWaiting 7 = FastClosing 4300 ModBus ModBusBios Bios version of the ModBus RTU expansion module 4301 BacNet...
Page 61
M A I N T E N A N C E Saftey Operate in compliance with safety regulations in force. Use single protection devices: gloves, glasses etc. Generality Maintenance must be carried out authorised after-sales assistance centres or by specialised personnel. Maintenance allows: ...
Page 62
Recommended periodical checks sheet intervention frequency (months) presence corrosion panel fixing fans fixing coil cleaning bowl cleaning + sanitisation outflow test air filters cleaning/inspection air flow rate measurement channelling: anti-vibration devices and fastenings check 10 power supply cable isolation and fastening check 11 earth cable check 12 electric control board cleaning 13 power remote controls state...
Page 63
Structure Check the state of the parts constituting the structure. Treat those parts of the unit subject to oxidation, with paints act at eliminating or reducing the oxidation phenomena. Check fastening of the unit external panelling. Bad fastening give rise to anomalous noises and vibrations. Outdoor air coil Accidental contact with the exchanger flaps can cause injuries from cut: use protective gloves.
Page 64
Condensation collection basin Dirt or scale can give rise to clogging. Also, microorganisms and mould can flourish in the bowl. It is very important to foresee periodical cleaning with suitable detergents and, eventually, disinfect with sanitising products. Once cleaning is completed, pour water inside the bowl to check the regular outflow.
Page 65
The electronic adjustment is integrated in the filter; maintenance can be carried out without removing it. Materials necessary for maintenance 1 Acid detergent B01212 (code CLIVET C6460316); 2 Plastic or steel tank (750x750x310 mm) with settling bottom 3 Protective gloves and goggles;...
Page 66
Ionisation wires The impurities can determine oxidation or scaling on the wires, which can be removed using a cloth soaked in alcohol or an abrasive scourer with very fine grain. Due to the high voltage powering them, the ionisation wires are subject to wear.
Humidifier cylinder drainage Cylinder must be drained in these situations: cleaning of the cylinder emptying of the cylinder to avoid ice forming replacement of the cylinder The manual drainage is carried out by means of selector SA7: see ELECTRIC CONNECTIONS chapter.
D E C O M M I S S I O N I N G Disconnection WARNING Before performing any operation, read the warnings found in the Maintenance chapter. Avoid leak or spills into the environment. Before disconnecting the unit, the following must be recovered, if present: ...
R E S I D U A L R I S K S General In this section the most common situations are indicated,as these cannot be controlled by the manufacturer and could be a source of risk situations for people or things. Danger zone This is an area in which only an authorised operator may work.
consequent possible projection of the refrigerant itself or explosion of the circuit parts that remain isolated by the closure of the tap. Do not remain in the vicinity of the safety valve and never leave the refriger-ating system taps closed. Electric parts An incomplete attachment line to the electric network or with incorrectly sized cables and/or unsuitable protective devices can cause electric...
General technical data SIZE 49.4 54.4 60.4 70.4 80.4 90.4 100.4 110.4 HIGH STATIC PRESSURE AIR HANDLING SECTION FANS (OPTIONAL) Type of supply fan No. of supply fans Fan diameter Supply airflow 26000 29000 33000 37000 44000 51000 56000 60000 7222 8056 9167...
Page 73
General technical data Operating range (Cooling) The limits are meant as an indication and they have been calculated by considering: - general and non specific sizes, - standard airflow, - non-critical positioning of the unit and correct operating and maintenance of the unit, - operating at full load.
Page 92
FOR OVER 30 YEARS, WE HAVE BEEN OFFERING SOLUTIONS TO ENSURE SUSTAINABLE COMFORT AND THE WELL-BEING OF PEOPLE AND THE ENVIRONMENT www.clivet.com sales and assistance CLIVET SPA Via Camp Lonc 25, Z.I. Villapaiera 32032 Feltre (BL) ‐ Italy Tel. +39 0439 3131 ‐ Fax +39 0439 313300 info@clivet.it ...
Need help?
Do you have a question about the CSRN-XHE2 and is the answer not in the manual?
Questions and answers