Everidge Thermalrite TQCFM450 Installation, Operation And Care Manual

Modular blast chiller/freezer

Advertisement

Quick Links

Operation and Care Manual
TQCFM1200
Modular Blast Chiller/Freezer
Installation,
TQCFM450
TQCFM850
TQCM450
TQCM850
TQCM1200

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Thermalrite TQCFM450 and is the answer not in the manual?

Questions and answers

Summary of Contents for Everidge Thermalrite TQCFM450

  • Page 1 Installation, Operation and Care Manual TQCFM450 TQCFM850 TQCFM1200 TQCM450 TQCM850 TQCM1200 Modular Blast Chiller/Freezer...
  • Page 2 This appliance is for commercial use only. To avoid electrical shock, this appliance MUST be adequately grounded in accordance with local electrical codes or, in the absence of local codes, with the current edition of the national Electrical Code ANSI/ NFPA no. 70. In Canada, all electrical connections are to be made in accordance with CSA C22.1, Canadian Electrical Code Part 1 or local codes.
  • Page 3: Chapter 3 Warranty

    for people and the environment. It is recommended to CHAPTER 1 dispose of it properly, DO NOT DISPOSE OF ELECTRICAL Operation and Care Manual OR ELECTRONIC EQUIPMENT WITH OTHER MUNICIPAL The operation and care manual is a document issued by WASTE.
  • Page 4: General Safety Precautions

    3. During the warranty period, for any defect in CHAPTER 4 workmanship and material, all parts and labor will be GENERAL SAFETY PRECAUTIONS covered. All warranty claims must be submitted to and 1. Never touch the metal parts of the machine with wet conform by all statements and policies of the or damp hands;...
  • Page 5: Chapter 5 Installation

    CHAPTER 5 INSTALLATION Carefully remove the appliance from the carton or crate. Note: Do not discard the carton and other Because this appliance rapidly moves air in the packaging material until you have inspected the unit for chamber, to remove heat from the product, clearances hidden damage and tested it for proper operation.
  • Page 6 The success or failure of the blast chiller/freezer is greatly impacted by the proper installation of this product. Because the design of the blast chiller/freezer requires it to move a large volume of air through the evaporator coil, to allow the condenser to dissipate that heat outside of the chamber, the clearance specifications must be followed.
  • Page 7 TQCFM 450 or TQCM450 Single Coil System (TREVAASSY01) 4” to 7” Bottom This is the typical single coil system, such as the TCFM450 or TQCM450. This is the master coil (TREVAASSY01) and contains the air temperature and coil sensor. The air temperature sensor is located in the upper right hand corner of the coil.
  • Page 8 TQCFM 850 or TQCM850 Double Coil System (1 – TREVAASSY01 and 1 – TREVAASSY02) Assemble the panels, paying attention to the wall where the coils are to be installed on. There must be a minimum of ½” plywood built into the panels to adequately support the mounting of the coils. Once the mounting surface is identified, find the center of the wall and mark it.
  • Page 9 Slave Master 4” to 7” Bottom This is the typical double coil system, such as the TCFM850 or TQCM850. This setup contains a master (TREVAASSY01) and slave coil (TREVAASSY02). The master coil contains the air temperature and coil sensors. The air temperature sensor is located in the upper right hand corner of the coil. This coil is always mounted closest to the outer door.
  • Page 10 TQCFM 1200 or TQCM1200 Triple Coil System (1 – TREVAASSY01 and 2 – TREVAASSY02) Assemble the panels, paying attention to the wall where the coils are to be installed on. There must be a minimum of ½” plywood built into the panels to adequately support the mounting of the coils. Once the mounting surface is identified, find the center of the wall and mark it.
  • Page 11 Bottom This is the typical triple coil system, such as the TCFM1200 or TQCM1200. This setup contains a master (TREVAASSY01) and 2 slave coils TREVAASSY02). The master coil contains the air temperature and coil sensors. The air temperature sensor is located in the upper right hand corner of the coil. This coil is always mounted in the middle of the cabinet, between the 2 slave coils.
  • Page 12: Refrigeration Piping

    Refrigeration Piping When piping any refrigeration systems in, the rules still apply. Any vertical rise of more than 20 feet, requires an oil trap installed in the suction line. Any refrigeration piping run of more than 50 feet requires increasing the piping diameter by 1 size, i.e.: 1 1/8”...
  • Page 13: Control Panel Mounting

    Control Panel Mounting The control must be mounted in an ambient controlled environment. It cannot be mounted in an excessively hot, cold or a high humidity area. The control panel mounts to the front of the Blast Chiller compartment and should be mounted a minimum of 60”...
  • Page 14: Electrical Box

    Electrical Box The electrical box is to be mounted on the outside ceiling of the box and is where the electrical connections are made. This box must be accessible for service and cannot be in an area affected by high or low temperatures or excessive humidity.
  • Page 15 Fan Motor Connections for Master or Slave Connections. If there is 1 coil, then use coil 1, 2 coils use 1 and 2, 3 coil, use 1, 2 and three (3 pole connector) Defrost Heater Connector (2 pole) Door Switch wires are purple and are labeled, if There are 2 door switches, wire door switches in series.
  • Page 16 The Air Temperature Sensor and Coil Sensor. The Solenoid Cable is wrapped up and labeled. This is for a 208/240VAC Solenoid Valve Coil.
  • Page 18: Master Configuration

    Master Configuration TREVAASSY01...
  • Page 19 26 -Touch Screen Display 27 - Relay Board 28 - Fan Control Board...
  • Page 20: Slave Configuration

    Slave Configuration TREVAASSY02...
  • Page 21 Master and Slave Coil Parts List Number Part Description Quantity Reference No. Thermalrite Part No. Coil Cabinet Top Panel MLR04 Coil Cabinet Upper Deflector MLR06 1/8” Stainless Steel Rivets Left Side Panel Coil Cabinet MLR02 Evaporator, Grey Epoxy, 64” x 20” Prepped RWE605 Reducer Coupling 7/8”...
  • Page 22 Nylon Board Standoffs Richio HPSTOF01 EVCO Fan Speed Module EVDFAN1 AX4723 Copper Tubing 1 3/8” THERMTUBE01 Copper Tubing 3/8” THERMTUBE03 Control Bezel (Not Shown) 8-32x 1 ¼” Black Phillip Head Screws CMPF1.25S #8 Black Flat Washers Insert Rivet Nut 8-32 CRN02 EVCO Cable USB 2.0 .5M JST 1256800336 1256800336...