Soft Starter User Manual
Safety Clauses
1. The general of FWI-SS Series Soft Starter
1.1 The main function
1.2 The main characteristics
2. Code explanation and Check-up before using
3. Usage conditions and Installation directions
3.1 The Usage condition
3.2 The Installation requirement
3.3 The Installation Directions
4. Connection and External terminal
4.1 The diagram connection
4.2 The external terminal
4.3 The diagram of Main circuit connection
4.4 The communication interface
5. Control panel and its operation
5.1 The operation of control panel
5.2 Parameter set and explanation
5.3 The functions of "Programmable relay output"
5.4 The function of Automatic Re-start
5.5 Directions for other set items
5.6 Help message and explanation
6. Protection Functions and directions
6.1 Protection functions and theirs parameter
6.2 Protection classes and explanation
7. Test run and application
7.1 Set up electricity to test run
7.2 Starting modes and application
7.3 Stopping modes and application
7.4 Application example
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the FWI-SS Series and is the answer not in the manual?

Questions and answers

Summary of Contents for VTdrive FWI-SS Series

  • Page 1 Soft Starter User Manual Safety Clauses 1. The general of FWI-SS Series Soft Starter 1.1 The main function 1.2 The main characteristics 2. Code explanation and Check-up before using 3. Usage conditions and Installation directions 3.1 The Usage condition 3.2 The Installation requirement...
  • Page 2 Safety Clauses In the process of using the soft starter, please note the following Safety Clauses Please check this user manual carefully before using the product. Only the technical person is allowed to install the product. To be sure that the motor is correctly matched with the soft starter.
  • Page 3 1. The General of FWI-SS Series Soft Starter FWI-SS series Soft Starter is new type start-up equipment which integrates electric force and electron techniques computer technique and modern control theory. It is the new generation product to replace the conventional Star-delta Starter, Self-coupling voltage-drop Starter and Magnetic control voltage-drop Starter.
  • Page 4 Reliable and high-grade quality This product is designed according to the computer analog test, has the best electromagnetic compatibility. It is proved high quality by the high-temperature ageing test and jigging test which done before the products out of factory.
  • Page 5 FWI-SS series Motor Soft Starter Code FWI-SS3 -5d5-4 Input voltage 3-phase AC460V 60Hz Matched motor 5.5KW Ex-factory code Date of produce Company Name ● Check any damage to the product because of the transport, such as the spare parts are apart from the main body or the shell be damage etc.
  • Page 6 3.2 The installation requirement ● The direction and distance of installation: In order to make sure that the soft starter be in good draft and heat dissipation, please install the product in vertical direction, and be sure the spare around the product is enough.
  • Page 7 The External shape and installation dimensions of 75KW-560KW External shape Installation Power dimensions(mm) dimensions(mm) Specifications (KW) (kg) FWI-SS3-075 <20 FWI-SS3-090 <20 FWI-SS3-115 <20 FWI-SS3-132 <20 FWI-SS3-160 <20 FWI-SS3-185 <20 FWI-SS3-200 <20 FWI-SS3-250 <20 FWI-SS3-280 <20 FWI-SS3-320 <20 FWI-SS3-400 <20...
  • Page 8 FWI-SS3-450 <20 FWI-SS3-500 <20 FWI-SS3-560 <20 4. Connection and External terminal The FWI-SS Soft Starter has three types of connection, as following Main circuit connection: it contains the wiring of 3-phase source input, the output to motor, and the pass -by contactor connection. External terminal connection that is the wire comes from twelve external terminals which including control signal and analogue output signal.
  • Page 9 4.2 The external terminal Please see the diagram 4.2 ● Terminal ① ② are by-pass output, are used to control the by-pass contactor. They are normal open contacts and are closed when finishing starting. The contact capacity is Ac250V/5A ●...
  • Page 10 Terminal ⑾ ⑿ are DC 0-20mA analogue output ,they show the current value of motor when real-time working, 20mA is full-scale value and is four times than rated current of nominal power of soft starter, while, we can contact a 0-20mADC current meter to check.
  • Page 11 4.4 The communication interfaces RJ-45 is the standard web line socket DB9 socket has Rs485 and RS232 interfaces inside Please see the diagram 4.5 The user can choose the following software 1. Computer collector distribution control communication software 2. Device Net interface card and communication software 3.
  • Page 12 Open state: you should not press the "run" key until the ready-lamp lights and ● show “READY" ● Time-delay state: When the ready-lamp or fault-lamp is shining, it means it is interval time delay; and when the Display screen shows "dEXXX", means staring time-delay.
  • Page 13 ● The "Up" and "Down" ("▲"" ▲ ") key :In the Set Menu ,you can press these two keys to choose the Function Code you need when the Colon is not shining and can choose the Parameters under the Colon when Colon is shining ,It is the same as the operation in Help Menu.
  • Page 14 This code is used to set the “soft If the code is set as “0”,the 0-60S starting motor will “staring mode” time” By the count-down way, If set as This code is used “0”, the starter will start up the to set the time of“...
  • Page 15 This code is used The “50-200%”is basic on the nominal current of motor. If the set set the “maximum 50-200% 100% value of this code over 200%,the working current of soft starter will be “inverse time soft starter” heat protection”...
  • Page 16 2: standard level; 3: heavy level; 4: super level. This code is used to set starting time of output of the programmable relay This code is used to set 0-13 Set the detailed in Item 5.4 the “time of re-start”...
  • Page 17 This code is used “The rated current of motor” to set Rated is the same as the current nominal the” rated value current of motor current-of Motor” This code is used to set the “motor Prohibition Set the detailed in Item 5.5 under-load protection”...
  • Page 18 If need programmable relay output time-delay, the delay time is set by F4 code. ●When the FJ is set as 5-9(or 15-19), the programmable operation way is time sequence output, As the following form: ● The way of programmable state output is used to show the working state of soft state, and under this way, the F4 code is un-useful;...
  • Page 19 ● Having stopped because of any fault and delay time for 60 seconds, the soft starter will Re-start automatically ● the total number of times of automatic re-start is "n" times,"n" is set by FE item. ● the function of automatic re-start is effect only when getting electricity and opening again ●...
  • Page 20 Numerical value keyboard External control Communication Note: In the above form,"1"is allowing,"0"is forbidding. For e example, if you forbid any unexpected stopping or starting whether starting is running or in maintenance, you can set the Numerical Value as"7"which means forbidding any starting or stopping operation.
  • Page 21 6. Protection Functions and theirs explanation We make our soft starters have all kinds of protection functions to protect the soft starter and the motor using. Please choose the correct Protection class and parameters according to your usage conditions! Over-heat Protection:when the temperature inside soft starter is up to 80℃±...
  • Page 22 ○ Power voltage failure protection: the delayed time is separately less than 0.5s or 3s when the power voltage is less than half of limited value or less than the set value. ○ Over-voltage protection: the delayed time is separately less than 0.5s or 3s when the power voltage is move than 130% if limited value or more than the set value.
  • Page 23 ● Basic protection includes the protection functions of over-heat, short -current protection and input failure-phrase protection when starting, but no protection of internal connector instantaneous-shop. we can se he protection glade when the motor is no need to be stopped urgently, such as fire pump.
  • Page 24 Motor heat protection curve diagram (Heat state) 7. Test Run and Application Please do some examine before test running as following: ○ If the rated power of Soft Starter is matched with the Motor ○ If the Insulation of Motor is up to the requirement ○...
  • Page 25 ● If the soft starter starts badly , you can check whether the starting mode you choose is fit for your motor . Please see the detailed explanation at 7.2: the starting mode and application ●...
  • Page 26 Note :When the motor starts successfully , the pass-by-lamp will be lighting , that means the pass-by contactor is running . At this time, if the contactor is not closed, the motor will stop running, so you can check whether the connection to the pass-by contactor is right.
  • Page 27 Note: It is normal that When the load equipments are light, the starting time is less than the set time. This mode generally fits for the occasions where the Motor must be started smoothly This mode is often used in the conditions which requires strict limit to the current when starting.
  • Page 28 Note:This mode will cause big-current shock to the motor, so if the Ramp voltage or Limit-current mode can be used, please had better not use the Torque control to start 7.2.4 Ramp Current to start (The F9 item is set as"4", this starting mode is in use) 7.2.5 Double closed loop (Both Ramp Voltage and Limit-current)to start (The F9...
  • Page 29 Output voltage of starter will be reduced gradually so that the Running Speed of Motor can be cut down smoothly in case of the Mechanical Shock. The Output Ending Voltage is the same as the initial Voltage. Soft-stopping Mode can reduce or remove the Surge of the loading equipments such as the Water Pump.
  • Page 30 7.4 Application Examples The parameters of the different loadings are different, please see the Form 7.2 The Parameters above is for reference only.