6.10
Installation and startup
NOTICE!
Installation, operation, and maintenance must be carried out by qualified personnel.
Please note the package leaflet during installation:
Designation
Installation instructions for the electrical installer
EU declaration of conformity
The package leaflet is part of the device's scope of delivery. The documents are available as PDF files
and can be downloaded from the manufacturer's website.
•
When configuring the device as per the safety requirements according to the operating mode table,
observe the switch positions that are not admissible for safety-related applications
•
Connect the device according to the installation instructions
•
Check the functionality of the device with a connected sensor or switch with resistance circuit for cor-
rect function
•
Start up the safety circuit and test for correct function
•
Avoid inadmissible currents by switching an external 4-A(T) fuse on the contact side of the relay
•
Check the external temperature monitoring in an installed state
•
Install the device in a control cabinet with a key lock and at least IP54
•
Test the used voltage supply in order to be able to compensate for brief interruptions (≤ 20 mA)
6 Safety-related applications