PCI DPT-4001 Operation & Maintenance Manual

PCI DPT-4001 Operation & Maintenance Manual

Differential pressure transducer

Advertisement

Quick Links

DPT-4001
Differential Pressure Transducer
Operation & Maintenance Manual
Engineered for accuracy, applicability,
durability and simplicity

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DPT-4001 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for PCI DPT-4001

  • Page 1 DPT-4001 Differential Pressure Transducer Operation & Maintenance Manual Engineered for accuracy, applicability, durability and simplicity...
  • Page 3 DPT-4001 Operation & Maintenance Manual TABLE OF CONTENTS TABLE OF CONTENTS ..........................i INTRODUCTION ..........................1 1.1. DESCRIPTION........................... 1 1.1.1. Field Connections & Output Load Limitations ..............1 1.1.2. Dimensions ......................... 2 CALIBRATION ..........................3 2.1. UNIPOLAR ZERO CALIBRATION ..................3 2.2.
  • Page 4 1.1. DESCRIPTION The DPT-4001 differential pressure transducer sensor operates on the capacitance principal and is capable of sensing ultra low differential pressures. In the capacitance cell, a very lightweight, responsive diaphragm deflects a small amount when pressure is applied. This deflection results in a change in capacitance, which is then detected and processed electronically into an output signal linear to the differential pressure.
  • Page 5 DPT-4001 Operation & Maintenance Manual 1.1.2. Dimensions 35mm Din Rail 1.89" 1.68" 0.16" Dia. 1.32" 1.45" POWER 2.90" PARAGON CONTROLS INCORPORATED 3.33" MODEL: DPT-4001 TAG NO.: W.O.#: 1300 / 1234 RANGE: 0-0.25"W.C. ZERO SPAN POWER: 12-36VDC OUTPUT: 4-20mA (Mount with #8 screws or 35mm Din Rail)
  • Page 6 DPT-4001 Operation & Maintenance Manual 2. CALIBRATION It is recommended that the Zero Calibration be performed upon installation. Span Calibration is not affected by the Zero Calibration. The Span of the unit has been factory calibrated and should only be adjusted using high accuracy test equipment.
  • Page 7 DPT-4001 Operation & Maintenance Manual 3. TROUBLESHOOTING GUIDE TROUBLESHOOTING TABLE SYMPTOM SOLUTION No output reading Verify Power Supply voltage is correct Verify correct wire connections 3. Verify correct pressure connections 4. Verify input pressure differential with a manometer Contact Factory Service Department.
  • Page 8 Paragon Controls Incorporated P.O. Box 99, Forestville, CA 95436 http://www.paragoncontrols.com Phone 707 / 579-1424 Revision Level 002...