Download Print this page

NK TECHNOLOGIES DT Series Instructions

Solid core

Advertisement

Quick Links

Specifi cations
Output Signal
0-20mA, 4-20mA, 0-5VDC or
0-10VDC
Accuracy
1% FS
Frequency Range
DC
Isolation Voltage
3kV (Monitored line to output)
Linearity
0.75% FS
Response Time
160 mS (to 90% of step change)
Repeatability
1% FS
Power Supply
24VAC/DC Option: Power input and output signal are not
isolated. Fuse DC supply at 5 amps,
AC supply at 2.75 amps.
120VAC Option:
Power input and output signal are
isolated.
Power Consumption 2 VA
Enclosure
UL 94V-0 Flammability rated
thermoplastic
Environmental
-4 to +122 F (-20 to 50 degree C)
0-95% RH non-condensing
Pollution Degree 2
Altitude to 2000 meters
Approvals
UL, cUL, CE (Note: Not all models
are CE compliant. See product label
for CE mark)
For products intended for the EU market, the following is
applicable to the CE compliance of the product:
The DT series comply with EN 61010-1 CAT III 600V max
measurement category. Use 24 V input power and fuse at 5
amps. Power source overvoltage category I as defi ned per EN
61010-1.
Caution! Risk of danger
Safe operation can only be guaranteed if the
transducer is used for the purpose for which it was
designed and within the limits of the technical
specifi cations When this symbol is used, it means
you must consult all documentation to understand
the nature of potential hazards and the action
required to avoid them.
Caution! Risk of electrical shock
When operating the transducer certain parts
may carry hazardous live voltage (e.g. Primary
conductor, power supply). The transducer should
not be put into operation if the installation is not
complete.
Model Number Key
DT 0 - 420 - 24U - U - FL
POLARITY:
BP- Bipolar
U- Unipolar
POWER SUPPLY:
24U- 24 VAC or VDC (Universal)
120- 120 VAC
OUTPUT:
005- 0-5 VDC
010- 0-10 VDC
020- 0-20 mA
420- 4-20 mA
RANGE
0- 0 to 5, 10 or 20 Amps DC
1- 0 to 50, 75 or 100 Amps DC
2- 0 to 100, 150 or 200 Amps DC
SENSOR TYPE:
DT - DC current sensor with analog output.
Know Your Power
Other NK Technologies Products Include:
DC Current Switches, Ground Fault Sensors
AC & DC Current Switches, Power Transducers
Current & Potential Transformers (CTs&PTs)
3511 Charter Park Drive, San Jose, CA 95136
800-959-4014 or +1-408-871-7510 Phone
+1-408-871-7515 FAX
sales@nktechnologies.com, www.nktechnologies.com
INSTRUCTIONS
DT SERIES Solid Core
0-20 or 4-20mA; 0-5 or 0-10 VDC Outputs
Quick "How To" Guide
1. Place wire to be monitored through aperture.
Ensure monitored current fl ow matches arrow
on sensor or as noted on fi gure on reverse
side.
2. Mount the sensor.
3. Connect power and output wiring.
A. Use 22-14 AWG copper wires rated 75°C
minimum. Tighten terminals to 5 in-lbs (.6
Nm) torque.
B. For current output models, ensure output
load is no more than 500 Ω.
C. For voltage output models, ensure output
load is at least 10KΩ.
4. Connect Power.
A. Connect the appropriate power supply.
Instr. Sheet DT-FL p/n 291004109 rev 3 04/16

Advertisement

loading

Summary of Contents for NK TECHNOLOGIES DT Series

  • Page 1 CE compliance of the product: on sensor or as noted on fi gure on reverse The DT series comply with EN 61010-1 CAT III 600V max measurement category. Use 24 V input power and fuse at 5 side.
  • Page 2 Description Wiring & Mounting Information Bipolar Unipolar DT Series transducers combine a Hall Effect sensor and Note: Unipolar transducers produce an output signal a signal conditioner into a single package. This provides with current fl owing in one direction only. Bipolar trans- higher accuracy, lower wiring costs, easier installation ducers produce an output with current fl...