PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 1. GENERAL HANDLING 1.1. Unpacking and Inspection The PGR-6150 must only be handled by qualified personnel and special care must be taken to protect its parts from damage during unpacking and installation. Inspect the PGR-6150 at delivery to ensure no damage occurred during transport. Inform Littelfuse Inc.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 3. CONNECTION DIAGRAMS 3.1. Direct Connection MOTOR AUX VOLTAGE GF CT SUPPLY TRIP START STOP PGR-6150 ALARM 3.2. Multiple Pass Connection MOTOR AUX VOLTAGE GF CT SUPPLY TRIP START STOP PGR-6150 ALARM For motors with nominal current below the minimum relay set-point value, multiple turns can be used.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 3.3. External CT Connection AUX VOLTAGE GF CT SUPPLY TRIP START STOP PGR-6150 ALARM For motors with nominal current over the maximum relay current set-point value, combine the relay with current transformers. Set the value I and CT Turns Ratio as explained in Section 6.2.1.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 5. DESCRIPTION 5.1. General The PGR-6150 is a modular system that provides integrated protection, metering and data logging functions. The PGR-6150 base module can operate as a stand-alone unit or with the operator interface PGR-6150-OPI, the voltage module PGA-0160, and the input/output module PGA-0180.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 5.2.4. Inputs and Outputs • One digital input • One trip output relay • One alarm output relay • PTC input • Ground-fault current transformer input • Relay closing time delay • RJ-45 24 Vdc output to PGR-6150-OPI and optional voltage and input/output modules •...
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 6. PGR-6150 PROTECTIVE FUNCTIONS AND CONTROL 6.1. Power Supply • The PGR-6150 comes with a 110/240 Vac/dc, 5 W power supply. The PGR-6150 generates 24 Vdc available through the RJ-45 port to supply auxiliary modules. 6.2.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 6.2.2. Overload The overload function meets international standard IEC 947-4-1 and IEC 255-8. A mathematically based thermal model is used to simulate the motor's thermal condition. The model combines two thermal images: A heating image and a cooling image. The heating image represents the thermal condition of the windings of the stator and rotor, and the cooling image represents the thermal condition of the motor housing.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ The PGR-6150 allows for overload function settings between 1 and 2 times I . Note however that standard IEC-947-4-1 recommends the tap setting to be between 1.05 and 1.20 times I 6.2.3. Phase Unbalance The unbalance function is applied on a three phase system made up of three phase currents (IA, IB, IC).
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ There is only one operating time, regardless of whether the motor is starting up or in operation. Phase loss Description Minimum Maximum Step Unit Default Function enabled yes/no % Unbalance (d2) Time 0.02 0.001 6.2.5.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Description Minimum Maximum Step Unit Default Function enabled yes/no The trip time is 500 ms. The PTC sensor current is 1 mA and a maximum of 2.3 V is used. Maximum cold resistance 1,500 Ω...
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 6.2.9. Calculated Definite-Time Ground Fault This function detects motor ground-fault current based on phase currents. >> GF CALC DEF Description Minimum Maximum Step Unit Default Function enabled yes/no Pickup 0.01 Time 0.02 0.001 This function is enabled after the motor start-up sequence has been completed.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 6.2.11. Measured Definite-Time Ground Fault This option requires a ground-fault current transformer. >> GF MEASURED DEF Description Minimum Maximum Step Unit Default Function enabled yes/no Pickup 15,000 Time 0.02 0.001 This function is enabled after the motor start-up sequence has been completed. Section 6.2.14 6.2.12.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 6.2.13. Undercurrent The undercurrent function is not enabled during motor start-up. I < Undercurrent Description Minimum Maximum Step Unit Default Function enabled yes/no Pickup 0.01 Time 0.02 0.001 Activation is at 100% of the pickup value and reset at 105%. The reset is instantaneous. The accuracy of the operation time is equal to the set time plus a maximum of 30 ms.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ In “Motor first step” and “Motor second step” the start-up time is monitored. If the measured start-up time is greater than the “Motor starting time” selected, the start up will be aborted due to a “Start time exceeded”...
Page 22
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Description Minimum Maximum Step Unit Default OVERLOAD Function enabled yes/no Service factor 0.01 1.15 Trip class 5,10,15,20,25,30,35,40,45 External ventilation Yes/No Alarm UNBALANCE Function enabled yes/no % Unbalance Starting trip time 0.02 0.001 Running trip time 0.02 0.001 PHASE LOSS...
Page 23
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Description Minimum Maximum Step Unit Default > GF CALC INVERSE Function enabled yes/no Curve (2*) Inverse Dial 0.05 1.25 0.01 1.25 Pickup 0.01 1.00 Operating time 0.02 0.001 >> GF MEASURED DEF Function enabled yes/no Pickup 15,000...
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 6.2.16. Overload curves The first graph shows the class 5, 10, 15, 20, 25, 30, 35, 40 and 45 trip curves starting from an initial thermal condition of 0% (cold). The following graphs show individually the class 5, 10, 15, 20, 25, 30, 35, 40 and 45 trip curves with initial thermal conditions of 0% (cold), 60% (hot 60%), 75% (hot 75%).
Page 25
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ OVERLOAD (cold) 10,000 1,000 CLASS 45 CLASS 40 CLASS 35 CLASS 30 CLASS 25 CLASS 20 CLASS 15 CLASS 10 CLASS 5 1.15 I...
Page 26
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ OVERLOAD CLASS 5 10,000.0 1,000.0 100.0 COLD HOT 60% HOT 75% 10.0 Hot 60% I = 0.9I Hot 75% I = I 10.0 11.0 1.15 I...
Page 27
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ OVERLOAD CLASS 10 10,000.0 1,000.0 COLD HOT 60% HOT 75% 100.0 10.0 Hot 60% I = 0.9 I Hot 75% I = I 10.0 11.0 1.15 I...
Page 28
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ OVERLOAD CLASS 15 10,000.0 1,000.0 COLD HOT 60% HOT 75% 100.0 10.0 Hot 60% I = 0.9 I Hot 75% I = I 10.0 11.0 1.15 I...
Page 29
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ OVERLOAD CLASS 20 10,000.0 1,000.0 COLD HOT 60% HOT 75% 100.0 10.0 Hot 60% I = 0.9I Hot 75% I = I 10.0 11.0 1.15 I...
Page 30
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ OVERLOAD CLASS 25 10,000.0 1,000.0 COLD HOT 60% HOT 75% 100.0 10.0 Hot 60% I = 0.9I Hot 75% I = I 10.0 11.0 1.15 I...
Page 31
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ OVERLOAD CLASS 30 10,000.0 1,000.0 COLD HOT 60% HOT 75% 100.0 10.0 Hot 60% I = 0.9I Hot 75% I = I 10.0 11.0 1.15 I...
Page 32
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ OVERLOAD CLASS 35 10,000.0 1,000.0 COLD HOT 60% HOT 75% 100.0 10.0 Hot 60% I = 0.9I Hot 75% I = I 10.0 11.0 1.15 I...
Page 33
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ OVERLOAD CLASS 40 10,000.0 1,000.0 COLD HOT 60% 100.0 HOT 75% 10.0 Hot 60% I = 0.9 I Hot 75% I = I 10.0 11.0 1.15 I...
Page 34
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ OVERLOAD CLASS 45 10,000.0 1,000.0 COLD HOT 60% 100.0 HOT 75% 10.0 Hot 60% I = 0.9 I Hot 75% I = I 10.0 11.0 1.15 I...
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 6.2.17. IEC255-4/BS-142 Curves The PGR-6150 relay complies with the curves in Standard IEC255-4/BS-142: • Inverse Curve • Very Inverse Curve • Extremely Inverse Curve The following equation defines the time, in seconds, as a function of the current: ×...
Page 36
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ IEC INVERSE 1000 Dial 1.2 Dial 1.1 Dial 1.0 Dial 0.9 Dial 0.8 Dial 0.7 Dial 0.6 Dial 0.5 Dial 0.4 Dial 0.3 Dial 0.2 Dial 0.1 Dial 0.05 0.01 10.0 100.0 CURRENT IN MULTIPLES OF PICKUP SETTING...
Page 37
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ IEC VERY INVERSE 1000 Dial 1.2 Dial 1.1 Dial 1.0 Dial 0.9 Dial 0.8 Dial 0.7 Dial 0.6 Dial 0.5 Dial 0.4 Dial 0.3 Dial 0.2 Dial 0.1 Dial 0.05 0.01 10.0 100.0 CURRENT IN MULTIPLES OF PICKUP SETTING...
Page 38
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ IEC EXTREMELY INVERSE 1000 Dial 1.2 Dial 1.1 Dial 1.0 Dial 0.9 Dial 0.8 Dial 0.7 Dial 0.6 Dial 0.5 Dial 0.4 Dial 0.3 Dial 0.2 Dial 0.1 Dial 0.05 0.01 10.0 100.0 CURRENT IN MULTIPLES OF PICKUP SETTING...
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 6.3. Monitoring and control 6.3.1. Metering The following metering options are provided: three phase currents (IA, IB, IC), neutral current (I0) calculated as a digital sum of the phase currents, ground-fault current (IG) measured by a ground-fault current transformer, positive-sequence current, negative-sequence current, average current of the three phases, thermal image measurement (%) and line frequency.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 6.3.2. States The states are real time information regarding the state of the PGR-6150. The PGR-6150 states can be accessed through the PGR-6150-OPI and communications. All the equipment states are listed below: STATES OVERLOAD Alarm Trip...
Page 41
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ STATES Phase A Trip Phase B Trip Phase C Trip Function Trip Phase A Pickup Phase B Pickup Phase C Pickup Function Pickup LOCKED ROTOR Phase A Trip Phase B Trip Phase C Trip Function Trip Phase A Pickup Phase B Pickup...
Page 42
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ STATES I < UNDERCURRENT Phase A Trip Phase B Trip Phase C Trip Function Trip Phase A Pickup Phase B Pickup Phase C Pickup Function Pickup RELAY OUTPUTS Relay K1 Relay K2 DIGITAL INPUT Input 1 MISCELLANEOUS Motor Running...
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ The “Equipment Alarm” consists of the following: Overload: Alarm PTC: Short-circuit PTC: Open circuit Miscellaneous: GF CT Open Miscellaneous: Settings Error Miscellaneous: Configuration Error The “Protection Trip” consists of the following: Overload: Function trip Unbalance: Function trip Phase Loss: Function trip Sequence: Function trip...
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 6.3.5. Reset The three reset types on the PGR-6150 are as follows: • Automatic reset • Automatic time delay reset • Manual reset If automatic reset has been selected, the PGR-6150 is reset when the trip condition is removed. If automatic time delay reset has been selected, the equipment is reset when the trip condition is removed and the reset time has elapsed.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 6.3.10. Commands The following table lists the available commands: PGR-6150: Short press test/reset button Test LED’s PGR-6150-OPI: Short press test/reset button Communication: Control 44 PGR-6150: Test/reset button held down Outputs and LED’s reset PGR-6150-OPI: Test/reset button held down Communication: Control 47 PGR-6150-OPI: Control menu...
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 6.3.13. PGR-6150 Base Module LED’s Constant Equipment OK Flashing Constant Overload trip Jam trip Locked rotor trip Excessive start time Flashing Undercurrent trip Constant Ground-fault trip Flashing CT connection alarm Constant Overtemperature trip Flashing PTC failure Constant...
Page 48
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ • Phase loss: Phase B pick up • Phase loss: Phase C pick up • Phase loss: Pick up • Phase loss: Phase A trip • Phase loss: Phase B trip • Phase loss: Phase C trip •...
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 6.3.15. Self-Diagnostics Diagnostic algorithms are run continuously when the PGR-6150 is operating. The following status bits are associated with this process: Problem in the configurations saved in e2prom. Configuration error Defaults are loaded. Problem in the setting saved in e2prom.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 6.3.19. User Password Settings are protected by a user password. The password consists of four digits. The PGR- 6150 leaves the factory with the password "5555" which can be changed by the user. When a setting is modified, the PGR-6150-OPI requests the user password and initiates a session if the correct password is entered.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 6.3.21. PGR-6150-OPI Operator Interface Test Program The PGR-6150-OPI is equipped with a test menu to test LED’s and programming keys. Deactivated LED 1 off LED 1 Activated LED 1 on Deactivated LED 2 off LED 2 Activated LED 2 on...
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 7. TECHNICAL SPECIFICATIONS AND STANDARDS 7.1. Technical specifications Motor rated current: 4 to 25 A (step 0.01) CT Turns Ratio: 1 to 2,000 General Frequency: 50Hz/60Hz/variable frequency (45Hz – 65Hz) Phase sequence ABC/ACB Time delayed equipment start: 0 to 3,600 s (step 1 s) Function enabled: yes/no Service Factor: 1 to 2 I...
Page 53
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Function enabled: yes/no %Unbalance (d): 10 to 100% (step 1) Operating time: 0.02 to 20s (step 0.001) Phase loss Reference: Average current of phases IA, IB, IC Activation level: (100 – d)% Reset level: (100 – d + 5)% Function enabled: Yes/no Sequence Operating time: 0.02 to 2 s (step 0.001)
Page 54
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Enable function: yes/no Pickup: 0.1 to 1 times I (Step 0.01) IEC 255-4/BS-142 Curves Operating time: Inverse curve, very inverse curve, extremely inverse curve. Defined time : 0.02 to 300 s (Step 0.01 s) Dial: 0.05 to 1.25 >...
Page 55
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Start up threshold: 1 to 8 times I (Step 0.01) Activation level: 100% pickup Motor start monitoring Reset level: 95% pickup Maximum start up time: 1 to 200 s (Step 0.001) RTC memory Real Time Clock –...
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 7.2. Standards • EN 50263 (1999) Electromagnetic compatibility (EMC) – Product standard for measuring relays and protection equipment. • EN 55011 Industrial, scientific and medical (ISM) – Limits and methods of measurement of radio disturbance characteristics.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 8. ACCESSORIES 8.1. Ground-Fault Current Transformer To prevent ground-fault relay trips during high load currents, a minimum pickup current setting is recommended as defined by the following table. Ø CT Ø CT Type Internal diameter (mm (inches)) Minimum pickup (mA) PGC-6035...
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 9. PGR-6150-OPI OPERATOR INTERFACE 9.1. PGR-6150-OPI Front Panel LCD (2x20 Characters) Keypad LED’s 9.2. LED Indicators The module’s front panel is equipped with six LEDs that have user-selectable functions. A blank LED legend overlay is provided. The default LED configuration is shown below: LED 1 POWER...
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ PGR-6150 POWR-GARD Accessing the menus: The keys ▲, ▼, ◄ and ► are used to navigate through the different options and menus. The “OK” key is used to accept and to enter a menu or an option. The “C” key is used to move up through the menu levels.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 9.4.4. Communications Menu The Communication parameters can be viewed by sequentially pressing the “◄”, “▼”, “►”, and “▲ and OK” keys from the standby mode screen. Communication: 19200-N-8-1 • Communication speed • Parity •...
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 9.4.6. Functions Menu "OK" PGR-6150 PGR-6150 POWR-GARD STATES "C" PGR-6150 METERING PGR-6150 SETTINGS PGR-6150 COMMAND PGR-6150 CONFIGURATION PGR-6150 REPORTS PGR-6150 STATISTICS PGR-6150 DATE-TIME PGR-6150 PASSWORD Press the “OK” key to access the first level from the main screen. Use the “◄” and “►” keys to move from one menu section to another in the first level.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 9.4.8. States Menu "OK" "OK" STATES ALARM "C" PGR-6150 "C" OVERLOAD activated/not activated STATES "C" TRIP In the Standby Mode screen, press activated/not activated the “OK” key to access the first line "OK" of menus.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 9.4.9. Settings Menu From the Standby Mode screen, press the “OK” key to access the first line of menus. Use the “◄” and “►” keys to position the cursor over the Settings Menu screen and press “OK”. This takes you to the settings group line.
Page 64
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Navigation through the Settings Menu: "OK" "OK" "C" NOMINAL CURRENT "C" SETTINGS GENERAL ---- "C" CT TURNS RATIO ---- "C" FREQUENCY ---- "C" MOTOR START LIMIT ---- "C" MOTOR STARTING TIME ---- "C" PHASE SEQUENCE ---- "C"...
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 9.4.10. Configuration Menu From the Standby Mode screen, press the “OK” key to access the first line of menus. Use the “◄” and “►” keys to position the cursor over the Configuration Menu and press “OK”. Only the LED’s on the PGR-6150-OPI can be configured.
Page 66
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ "OK" "OK" "C" REPORT 1 IA (A) PGR-6150 "C" 00/00/00 00:00:00 ---- REPORTS "C" IB (A) ---- "C" IC (A) ---- "C" IN (A) REPORT 2 "C" ---- 00/00/00 00:00:00 "C" IG (mA) ---- "C"...
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 9.4.12. Command Menu From the Standby Mode screen, press the “OK” key to access the first line of menus. Use the “◄” and “►” keys to view the Command Menu and press “OK”. Use the “◄” and “►” keys to view the command to execute and press “OK”.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 10. COMMISSIONING 10.1. Checklist for Commissioning A checklist is provided in Section12- APPENDIX. 10.2. Inspection 10.2.1. Visual Inspection Make sure that wiring has been installed as per connection diagrams. 10.2.2. Current Transformers The high voltage that is generated in the secondary circuits of current transformers can cause death and could damage the facility.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 11. MODBUS RTU PROTOCOL This document describes the steps to follow to read and write data to the PGR-6150, using Modbus RTU protocol. The memory map is described in Section 11.8. Only the master can initiate a message transaction. Messages can be addressed to individual slaves or they can be broadcast messages.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 11.1. Modbus Package Format Each device on a communications bus must have a unique address. All the relay ports shall use this address which can be set at a Slave 1 byte value of between 1 and 247. Slave address 0 indicates a Address broadcast message.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 11.3. Error Responses and Exceptions The following error codes are defined by the Modbus protocol: ILLEGAL FUNCTION Message function not supported. The master is attempting to perform an operation to an unsupported ILLEGAL DATA ADDRESS address.
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Number of TYPE Description Registers TYPE_ENUM_CLASS 0: Trip class 5 1: Trip class 10 2: Trip class 15 3: Trip class 20 Num. data 4: Trip class 25 5: Trip class 30 6: Trip class 35 7: Trip class 40 8: Trip class 45 0: Definite time...
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 11.7. Command The following commands are available: Command Description Number Overload set point confirmation Phase unbalance set point confirmation Phase loss set point confirmation Phase sequence set point confirmation PTC set point confirmation Jam set point confirmation Locked rotor set point confirmation Calculated ground-fault definite-time set-point confirmation...
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ To execute a command, write (with function 16) the command number and equipment key in the command area (address 0x4000). The numbers key_0, key_1, key_2 and key_3 are the ASCII relating to the key digit. For example, if the equipment key is “1234”...
Page 75
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Status Number of Address Description Format Registers 0x0042 Phase loss Phase A pick up bit TYPE_BIT_0 Phase B pick up bit TYPE_BIT_1 Phase C pick up bit TYPE_BIT_2 Function pick up bit TYPE_BIT_3 Phase A trip bit TYPE_BIT_4 Phase B trip bit...
Page 76
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Status Number of Address Description Format Registers 0x0048 Calculated ground-fault definite time Pick up bit TYPE_BIT_0 Trip bit TYPE_BIT_1 0x0049 Calculated ground-fault inverse time Pick up bit TYPE_BIT_0 Trip bit TYPE_BIT_1 0x004A Measured ground-fault definite time Pick up bit TYPE_BIT_0 Trip bit...
Page 77
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Status Number of Address Description Format Registers 0x0051 PGR-6150-OPI 1 LED TYPE_BIT_7 PGR-6150-OPI 2 LED TYPE_BIT_8 PGR-6150-OPI 3 LED TYPE_BIT_9 PGR-6150-OPI 4 LED TYPE_BIT_10 PGR-6150-OPI 5 LED TYPE_BIT_11 PGR-6150-OPI 6 LED TYPE_BIT_12 0x0057 Miscellaneous Motor operation bit TYPE_BIT_2...
Page 78
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Settings reading Number of Address Description Format Registers 0x0088 Overload set points 0x0088 Function enabled TYPE_ENUM_ENABLE 0x008A Service factor TYPE_ULONG_100 0x008C Trip class TYPE_ENUM_CLASS 0x008E Independent mechanical ventilation TYPE_ENUM_ENABLE 0x0090 Alarm TYPE_ULONG 0x0092 Unbalance set points 0x0092 Function enabled...
Page 79
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Settings reading Number of Address Description Format Registers 0x00BE Calculated ground-fault inverse time set points 0x00BE Function enabled TYPE_ENUM_ENABLE 0x00C0 Pickup TYPE_ULONG_100 0x00C2 Curve TYPE_ENUM_CURVE 0x00C4 Dial TYPE_ULONG_100 0x00C6 Operating time TYPE_ULONG_1000 0x00C8 Measured ground-fault definite-time set points 0x00C8 Function enabled...
Page 80
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Settings reading Number of Address Description Format Registers 0x00EE Reset set points 0x00EE Enable PGR-6150-OPI TYPE_ENUM_ENABLE 0x00F0 Enable command TYPE_ENUM_ENABLE 0x00F2 Enable input TYPE_ENUM_ENABLE 0x00F4 Reset type TYPE_ENUM_RESET 0x00F6 Reset time TYPE_ULONG_1000 0x00F8 Keys 0x00F8 Key 1...
Page 81
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Settings writing Number of Address Description Format Registers 0x0192 Unbalance set points 0x0192 Function enabled TYPE_ENUM_ENABLE 0x0194 % Unbalance TYPE_ULONG 0x0196 Starting trip time TYPE_ULONG_1000 0x0198 Running trip time TYPE_ULONG_1000 0x019A Phase loss set points 0x019A Function enabled TYPE_ENUM_ENABLE...
Page 82
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Settings writing Number of Address Description Format Registers 0x01C8 Measured ground-fault definite-time set points 0x01C8 Function enabled TYPE_ENUM_ENABLE 0x01CA Pickup TYPE_ULONG_100 0x01CC Operating time TYPE_ULONG_1000 0x01CE Measured ground-fault inverse-time set points 0x01CE Function enabled TYPE_ENUM_ENABLE 0x01D0 Pickup...
Page 83
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Reports Number of Address Description Format Registers 0x0A80 Report 1 0x0A80 Date-time TYPE_DATE 0x0A88 Phase A current measurement TYPE_ULONG_100 0x0A8A Phase B current measurement TYPE_ULONG_100 0x0A8C Phase C current measurement TYPE_ULONG_100 0x0A8E Neutral current measurement I0 TYPE_ULONG_100 0x0A90 Ground-fault-current measurement IG...
Page 84
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Reports Number of Address Description Format Registers 0x0A80 Report 1 continued 0x0AA8 I<: Phase A trip TYPE_BIT_4 I<: Phase B trip TYPE_BIT_5 I<: Phase C trip TYPE_BIT_6 0x0AA9 Button TYPE_BIT_0 Digital Input TYPE_BIT_1 0x0AAA Relay K1 TYPE_BIT_0...
Page 85
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Reports Number of Address Description Format Registers 0x0A80 Report 2 continued 0x0AD1 PTC: Overtemperature TYPE_BIT_1 PTC: Short circuit TYPE_BIT_3 PTC: Open circuit TYPE_BIT_5 0x0AD2 Jam: Phase A trip TYPE_BIT_4 Jam: Phase B trip TYPE_BIT_5 Jam: Phase C trip TYPE_BIT_6...
Page 86
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Reports Number of Address Description Format Registers 0x0A80 Report 3 continued 0x0AF6 Frequency measurement TYPE_ULONG_100 0x0AF8 Average current measurement TYPE_ULONG_100 0x0AFA Positive sequence current measurement TYPE_ULONG_100 0x0AFC Negative sequence current measurement TYPE_ULONG_100 0x0AFE Overload: trip TYPE_BIT_1 0x0AFF...
Page 87
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Reports Number of Address Description Format Registers 0x0A80 Report 3 continued 0x0B0E Motor : Running TYPE_BIT_2 Ground-fault current transformer open TYPE_BIT_3 Motor: Start time exceeded TYPE_BIT_11 Enable outputs TYPE_BIT_13 0x0B13 Report 4 0x0B13 Date-time TYPE_DATE 0x0B1B...
Page 88
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ Reports Number of Address Description Format Registers 0x0a80 Report 4 continued 0x0B35 Locked rotor: Phase A trip TYPE_BIT_4 Locked rotor: Phase B trip TYPE_BIT_5 Locked rotor: Phase C trip TYPE_BIT_6 0x0B37 I0>>: Trip TYPE_BIT_1 0x0B38 I0>: Trip...
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 12. APPENDIX 12.1. Identification: Model: PGR-6150- ..................... Serial No: ........................Software Version: ..................... 12.2. Checks: Wiring Connections: Test menu: PGR-6150 LED 1: PGR-6150 LED 2: PGR-6150 LED 3: PGR-6150 LED 4: PGR-6150 LED 5: PGR-6150 Relay K1: PGR-6150 Relay K2: PGR-6150-OPI LED 1:...
Page 90
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 12.3.3. Unbalance: Function Enabled %Unbalance ………………. % Start up time … … … … … s Operating time … … … … … s 12.3.4. Phase loss: Function Enabled % Unbalance......% Time …...
Page 91
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________ 12.3.11. Measured Ground Fault Definite Time IG>>: Function Enabled Current pickup ……………..mA Time … … … … … s 12.3.12. Measured Ground Fault Inverse Time IG>: Function Enabled Current pickup......mA Curve Definite Inverse Very Inverse...
Page 92
PGR-6150 Motor Protection System Rev. 1 _________________________________________________________________________________...