SHB10 TIKI
Installation and User manual
Indoor module for
air to water split systems
09-02-2021
30122

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SHB10 and is the answer not in the manual?

Questions and answers

Summary of Contents for tiki SHB10

  • Page 1 SHB10 TIKI Installation and User manual Indoor module for air to water split systems 09-02-2021 30122...
  • Page 3: Table Of Contents

    9 Control ____________________39 3 Design of the indoor unit ________ 8 Menu 1 - INDOOR CLIMATE ________________39 Menu 2 - HOT WATER ____________________40 SHB10 _______________________________8 Menu 3 - INFO _________________________40 Dimensions and pipe connections ___________10 Menu 4 - MY SYSTEM ___________________41...
  • Page 4: Important Information

    This appliance can be used by Marking children aged 8 years and above SHB10 is CE marked and has an and persons with reduced phys- IP21 protection rating. ical, sensory or mental capacity or lack of experience and knowl-...
  • Page 5 Electric power supply Connecting communication Perimeter protection Protection, indoor unit Building protection Outdoor temperature sensor Room sensor Current sensor Safety circuit breaker Residual-current device Setting the thermostat to emer- gency mode Miscellaneous Docked to SHB10 TIKI Section 1 | Important information...
  • Page 6: Delivery And Handling

    CAUTION • SHB10-6 - unit dedicated for use with AMS 10-6. The SHB10 unit must be hanged on the wall using • SHB10-12 - unit dedicated for use with AMS 10-8 the included hanger. The device can be installed in and AMS 10-12.
  • Page 7: Installation Location

    Installation location Supplied components SHB10 can be installed in any room protected against • Hanger (1 pc.) temperature drop below 0°C to avoid freezing of the • Rawplugs and bolts (3 pcs) heating medium. 800 mm of free space should be •...
  • Page 8: Design Of The Indoor Unit

    3 Design of the indoor unit SHB10 XL11 AA23 AA2:X4 BT30 K1A-K3A AA27 AA2:X15 AA2:X4 XL10 XL13 XL14 BT12 BT63 BT25 BT71 BT15 QN10 GP12 Section 3 | Design of the indoor unit SHB10 TIKI...
  • Page 9 Rear left cable groomet Rear right cable groomet Lower left cable groomet Lower right cable groomet Nameplate Plate with the designation of the hydraulic connections Serial number SHB10 Software serial number SHB10 TIKI Section 3 | Design of the indoor unit...
  • Page 10: Dimensions And Pipe Connections

    XL11 XL10 XL13 XL14 Pipe connections Connection, heating medium, supply Ø22 mm for SHB10-6 and SHB10-12, Ø28 mm for SHB10-16 Connection, heating medium, return Ø22 mm for SHB10-6 and SHB10-12, Ø28 mm for SHB10-16 Connection, HW heating medium, supply Ø22 mm for SHB10-6 and SHB10-12, Ø28 mm for SHB10-16...
  • Page 11: Pipe Connections

    The SHB 10 unit can be docked to the central heating, mum permissible height difference of 5 m. cooling operation and hot water systems. It is abso- lutely necessary to install the safety assembly on con- nection XL11. SHB10 TIKI Section 4 | Pipe connections...
  • Page 12 Remember to always maintain the minimum required flow in the system - see the subsection “Minimum system flow” . Minimum climate system volumes AMS 10 Minimum climate system vol- 100l ume during heating/cooling Section 4 | Pipe connections SHB10 TIKI...
  • Page 13: Docking The Indoor Unit

    The pipe connections of the climate system are made ing it off the drip tray placed in the lower part of from the top of the appliance except safety assembly. SHB10. Hose should be connected to the WM1 stud. • All required safety devices and shut-off valves...
  • Page 14 Ø6,35 14~18 45~60 Ø 9,52 34~42 30~45 SHB10-12, SHB10-16 Ø12,7 49~61 30~45 SHB10-12 / SHB10-16 Gas pipe (Ø ext.) Liquid line (Ø ext.) Ø 15,88 68~82 15~20 Pipe dimensions Ø15,88 mm (5/8”) Ø9,52 mm (3/8”) Connection Connection – (5/8") Connection –...
  • Page 15 15 m on either side. If the length of the refrigerant pipes exceeds 15 m, extra refrigerant must be added in the amount of 0.02kg/m for SHB 10-6 or 0.06 kg/m for SHB 10-12 and SHB 10-16. SHB10 TIKI Section 4 | Pipe connections...
  • Page 16 0,57 l/s 0,79l/s Min. flow, climate system 0,09 l/s 0,12 l/s 0,15 l/s 0,24l/s Min. flow, cooling system 0,11 l/s 0,16 l/s 0,20 l/s 0,32l/s * Refers to volume associated with undisturbed flow Section 4 | Pipe connections SHB10 TIKI...
  • Page 17: Installation Alternative

    Installation alternative selection tables available on the website. www.tiki. si The sensors BT6 and BT7 should be placed in the CAUTION appropriate places. BT7 sensor in the place that will Temperature sensor BT25 is included with the device. show the highest temperature in the tank. Whereas It should be installed on the installation in accordance the BT6 sensor in 1/3÷1/2 of the coil height meas-...
  • Page 18 Additional accessories and the connection options and -BT3 methods for these are described in the instructions for -QN25 AXC 30 and ECS 40 / ECS 41. -BT12 -BT63 -BT25 -QN10 -BT15 -BT3 -BT71 -GP12 -BP4 Section 4 | Pipe connections SHB10 TIKI...
  • Page 19: Hot Water Circulation

    In the event that the water volume of the central heating system is increased using a buffer vessel, you will need to check the system volume and possibly increase the volume of the existing expansion vessel. SHB10 TIKI Section 4 | Pipe connections...
  • Page 20 -BT71 -GP12 -BP4 -BT7 -BT1 -GP11 -EB101 -BT6 Basic diagram with parallel connection of a buffer tank SHB10 -BT25 -BT12 -BT63 -GP10 -QN10 -BT15 -BT3 -GP12 -BT71 -BP4 -BT7 -BT1 -GP11 -EB101 -BT6 Section 4 | Pipe connections SHB10 TIKI...
  • Page 21 -GP12 -BT71 -BP4 -BT7 -BT1 -GP11 -EB101 -BT6 Diagram of heating and 4-pipe cooling SHB10 -GP13 -BT64 -BT25 -BT12 -BT63 -GP10 -QN10 -QN12 -BT15 -BT3 -GP12 -BT71 -BP4 -BT7 -BT1 -GP11 -EB101 -BT6 SHB10 TIKI Section 4 | Pipe connections...
  • Page 22: Ams 10 Outdoor Unit

    “heavy side” and two people are required to Do not place the AMS 10 heat pump directly on the set the AMS 10 in position. lawn or other unstable surface. Section 5 | AMS 10 outdoor unit SHB10 TIKI...
  • Page 23: Lift From The Pallet To Final Positioning

    Use a siphon for installations where air circula- tion may occur in the condensation water drain- age pipe. • The insulation must be tightly fitted to the bot- tom of the condensation water trough. SHB10 TIKI Section 5 | AMS 10 outdoor unit...
  • Page 24 • The installation length can be adjusted by the size of the siphon. NOTE If none of the recommended options will be used, proper drainage of condensate must be ensured. SHB10 TIKI Section 5 | AMS 10 outdoor unit...
  • Page 25: Dimensions

    Dimensions AMS 10-6 40º 40º AMS 10-8 30º 30º SHB10 TIKI Section 5 | AMS 10 outdoor unit...
  • Page 26 AMS 10-12 Section 5 | AMS 10 outdoor unit SHB10 TIKI...
  • Page 27 AMS 10-16 SHB10 TIKI Section 5 | AMS 10 outdoor unit...
  • Page 28: Installation Location

    AMS 10-6 AMS 10-8 AMS 10-12 AMS 10-16 Sound power levels, according to EN12102 at 7/35°C (rated value)* Sound power level at a distance of 2m (rated dB(A) value)* *Free space Section 5 | AMS 10 outdoor unit SHB10 TIKI...
  • Page 29: Electrical Connections

    The power supply cable should be dimensioned according to the current standards. • Cable lying in SHB10 should be performed with UB cable grommets (marked on the drawing). In UB1 and UB 2, the cables are laid through the AA2:X4...
  • Page 30: Connections

    SHB 10 unit is 9kW. CAUTION In the case of a dual tariff power supply, it is advisa- ble to connect the neutral wire from the power supply circuit (meter). Section 6 | Electrical connections SHB10 TIKI...
  • Page 31 (TB) in AMS 10 and L2 AND L3! Remove the bridge to use dual- to the terminal block (X10) in SHB10 . -tariff control. CAUTION The AMS 10 unit must be earthed before connecting CAUTION the appliance via the cable.
  • Page 32: Settings

    The temperature on the thermostat must be set ac- cording to the system requirements. If the tempera- NOTE ture is too high, it can damage the system. The location of the other sensors is available on page 82. Section 6 | Electrical connections SHB10 TIKI...
  • Page 33: Commissioning And Adjusting

    (FD1) has not de- ployed. Filling and venting Filling and venting the climate system and SHB10 Open the vent valves at the highest point of the climate system. 2. Set all mixing valves to a position which allows flow in all heating/cooling circuits.
  • Page 34: Circulation Pump

    During venting, SHB 10 must be switched heating system, the central heating system should be off. warmed up fi rst, using the additional heat, to a tem- perature of about 20-25 °C. Section 7 | Commissioning and adjusting SHB10 TIKI...
  • Page 35 To view the help text: Use the control knob to select the help symbol. 2. Press the OK button. The help text often consists of several windows that you can scroll between using the control knob. SHB10 TIKI Section 7 | Commissioning and adjusting...
  • Page 36: Control - Introduction

    The control knob can be turned to the right or left. You can: • scroll in menus and between options. • increase and decrease the values. • change page in multiple page instructions (for example help text and service info). Section 8 | Control - Introduction SHB10 TIKI...
  • Page 37: Menu System

    MENU 5. solar heating is active. Required additional equipment ERS. This symbol indicates whether pool heating is active. Required additional equipment POOL 40. This symbol indicates whether cooling is active. SHB10 TIKI Section 8 | Control - Introduction...
  • Page 38 To change and return to the The help text often consists of several windows that original value, press the Back button. you can scroll between using the control knob. Section 8 | Control - Introduction SHB10 TIKI...
  • Page 39: Control

    1.9.4 - room sensor settings 1.9.5 - cooling settings 1.9.6 - fan return time 1.9.7 - own curve 1.9.7 .1 - heating 1.9.7 .2 - cooling 1.9.8 - point offset The ERS additional equipment is necessary. SHB10 TIKI Section 9 | Control...
  • Page 40: Menu 2 - Hot Water

    3.1 - service info 3.2 - compressor info 3.3 - add. heat info 3.4 - alarm log 3.5 - indoor temp. log The accessory AXC 30 is required if the output AA3: X7 is occupied. Section 9 | Control SHB10 TIKI...
  • Page 41: Menu 4 - My System

    4.9.4 - factory setting user 4.9.5 - schedule blocking 4.9.6 - schedule silent mode The POOL 40 additional equipment is necessary. The SMS 40 additional equipment is necessary. The EME 20 additional equipment is necessary. SHB10 TIKI Section 9 | Control...
  • Page 42: Menu 5 - Service

    The OPT additional equipment is necessary. additional equipment is necessary. The ECS The HTS 40 additional equipment is necessary. additional equipment is necessary. The SOLAR 42 The EMK 300 additional equipment is necessary. The MODBUS Section 9 | Control SHB10 TIKI...
  • Page 43: Start Guide

    Factory setting:radiator Factory setting:-15.0 DOT C 7/18 Control of external sensors In this menu we have the possibility to check the al- lowed values for external sensors. More information after selecting " ? ". SHB10 TIKI Section 9 | Control...
  • Page 44 In this menu it is possible to edit the device operation scheme. More information after selecting " ? ". Detailed information on curve settings - see pt. "User settings". IMPORTANT Changing the diagram will cause the device to operate incorrectly. Section 9 | Control SHB10 TIKI...
  • Page 45: Settings For The User

    Setting range: -10 do +10 of the user manual. Factory setting: 0 18/18 Start guide In this menu, we can decide whether the start guide will run again the next time the system is started. SHB10 TIKI Section 9 | Control...
  • Page 46 Use the control knob to set a new value. Confirm the new setting by pressing the OK button. Curve 0 is an own curve created in menu 1.9.7 . This menu is intended for advanced users. This menu has several sub-menus. SHB10 TIKI Section 9 | Control...
  • Page 47 This means that SHB 10 never calculates a temperature lower than that set here. If there is more than one climate system the setting can be made separately for each system. SHB10 TIKI Section 9 | Control...
  • Page 48 " ? ". Factory setting: off When hot water requirement has temporarily increased this menu can be used to select an increase in the hot water temperature to lux mode for a selectable time. Section 9 | Control SHB10 TIKI...
  • Page 49 - Lux mode gives the greatest possible amount of hot water. In this mode the immersion heater may be partially used to heat hot water, which may in- crease operating costs. SHB10 TIKI Section 9 | Control...
  • Page 50 No changes can be made. The information is on several pages. Turn the control knob to scroll between the pag- es. More information after selecting " ? ". Section 9 | Control SHB10 TIKI...
  • Page 51 Change the operating mode by marking the desired mode and pressing the OK button. When an operating mode is selected, it shows what is permitted in the heat SHB10 TIKI Section 9 | Control...
  • Page 52 This setting applies to all climate systems without room sensors. Vacation scheduling starts at 00:00 on the start date and stops at 23:59 on the stop date. Section 9 | Control SHB10 TIKI...
  • Page 53 400 DM diff. between additional steps: 30 DM CAUTION Higher value on "start compressor" gives more com- pressor starts, which increase wear on the compressor. Too low value can give uneven indoor temperatures. SHB10 TIKI Section 9 | Control...
  • Page 54: Cooling Settings

    Factory setting stop temp. normal: 46°C ified personnel. luxury Setting range start temp. lux: 5 – 60°C Factory setting start temp. lux: 45°C Setting range stop temp. lux: 5 – 60°C Factory setting stop temp. lux: 49°C Section 9 | Control SHB10 TIKI...
  • Page 55 Factory setting: speed 4: 100% Set the speed for the five different selectable speeds for the fan here. CAUTION An incorrectly set ventilation flow can damage the house and may also increase energy consumption. SHB10 TIKI Section 9 | Control...
  • Page 56 Factory setting: positioning: before QN10 (REQUIRED) max step Setting range (binary stepping deactivated): 0 – 3 Setting range (binary stepping activated): 0 – 7 Factory setting: 3 binary stepping Setting range: activee / inactive Factory setting: binary stepping: inactive Section 9 | Control SHB10 TIKI...
  • Page 57 (EB101 = Slave 1, CL11 = Pool 1 etc.). Mark “search installed slaves" and press the OK but- ton to automatically find connected slaves for the master heat pump. Hot water charging SHB10 TIKI Section 9 | Control...
  • Page 58 F135 accessory must be installed and activated in the accessories menu 5.2.4. A detailed description of programming the accesso- ries can be found in the instructions for the individual accessories. Section 9 | Control SHB10 TIKI...
  • Page 59 All settings can be reset (including settings available to the user) to default values here. IMPORTANT When resetting, the start guide is displayed the next time the control module is restarted with factory settings. SHB10 TIKI Section 9 | Control...
  • Page 60 Language settings can be made regardless of this heating, hot water, pool, cooling selection. Setting range: auto / manual Factory setting: auto IMPORTANT This option locks after 24 hours, restart of display or program updating. Section 9 | Control SHB10 TIKI...
  • Page 61: Service

    External additional heat is active if it is connected to 1,469 0,758 the emergency mode relay (K1, terminal block X1). 1,246 0,691 Ensure that the heating medium circulates through 1,061 0,607 the external additional heat. 0,908 0,533 0,779 0,469 0,672 0,414 SHB10 TIKI Section 10 | Service...
  • Page 62 OK button is held in during start up until the green lamp starts to illuminate (takes about 10 seconds). Section 10 | Service SHB10 TIKI...
  • Page 63 2. Tick “activated". 3. The present values from the controller are saved in a file in the USB memory at the set interval until “activated" is unticked. IMPORTANT Untick "activated" before removing the USB memory. SHB10 TIKI Section 10 | Service...
  • Page 64 Connect the hose to the XL10 drain valve of the system. 2. Then open the drain valve to empty the heating system. 3. Open the safety valve to remove the created un- derpressure. XL10 Section 10 | Service SHB10 TIKI...
  • Page 65: Disturbances In Comfort

    If the room temperature problem that caused the alarm. The status lamp will therefore continue to be red. is only low in cold weather the curve slope in SHB10 TIKI Section 11 | Disturbances in comfort...
  • Page 66: Additional Heating Only

    Too high set value on the automatic heating con- trol. CAUTION When commissioning without TIKI air/water heat – Enter menu 1.1 (temperature) and reduce the pump, the communication error alarm may appear in offset heating curve. If the room temperature is the display.
  • Page 67: Accessories

    RMU 40 means that control and monitoring of the controller can be carried out in a different part of your More accessories are available on the web- home to where it is located. site https://www.tiki.si Part no. 067 064 SHB10 TIKI Section 12 | Accessories...
  • Page 68: Connecting The Kvr Accessory

    3. Use fuse (F3) depending on the length of the KVR cable in accordance with the below table. Length Fuse (F3) Part no. T100mA/250V 718 085 T250mA/250V 518 900* T500mA/250V 718 086 *Fitted at the factory Section 12 | Accessories SHB10 TIKI...
  • Page 69: Connection Of An Additional Gp10 Pump

    SHB 10 Externt External Zewnętrzne AA2-X4 GP10 Diagram with buffer tank connected in parallel and additional circulation pump GP10. SHB10 -BT3 -GP20 -AA25 -QN25 -BT2 -BT12 -BT63 -GP10 -QN10 -BT15 -BT3 -BT71 -GP12 -BT71 -BP4 SHB10 TIKI Section 12 | Accessories...
  • Page 70: Technical Data

    XL11 XL10 XL13 XL14 Pipe connections Connection, heating medium, supply Ø22 mm for SHB10-6 and SHB10-12, Ø28 mm for SHB10-16 Connection, heating medium, return Ø22 mm for SHB10-6 and SHB10-12, Ø28 mm for SHB10-16 Connection, HW heating medium, supply Ø22 mm for SHB10-6 and SHB10-12, Ø28 mm for SHB10-16...
  • Page 71: Technical Data

    Rated voltage 230V 1N AC 50Hz / 400V 3N AC 50Hz Energy class (in accordance with ErP . at supply temp. 55°C) applies to package AMS 10-6 + SHB10-6, AMS 10-12 + SHB10-12 OR AMS 10-16 + SHB 10-16 Outdoor unit...
  • Page 72 44 (40) contactor K1+K2+K3 connected (recommended fuse rating) Max. operating current of 4.5 kW immersion heater. contactor K1+K2+K3 connected. compressor 19,5 (20) 19,5 (20) 19,5 (20) 19 (20) not running (recommended fuse rating) Section 13 | Technical data SHB10 TIKI...
  • Page 73: Energy Efficiency Label

    139 / 108 142 / 111 144 / 113 climate Water heating energy efficiency, cold climate 252 / 179 225 / 180 229 / 185 235 / 189 Sound power level L outdoors SHB10 TIKI Section 13 | Technical data...
  • Page 74: Energy Efficiency Specifications Of The Package

    The reported efficiency of the system also takes the controller into account. If an external supplementary boiler or solar heating is added to the system, the overall efficiency of the system should be recalculated. Section 13 | Technical data SHB10 TIKI...
  • Page 75: Energy Label

    Energy label Model AMS10-6 + SHB10-6 Type of heat pump Air-water Exhaust-water Brine-water Water-water Low-temperature heat pump Integrated immersion heater for additional heat Heat pump combination heater Climate Average Cold Warm Temperature application Average (55°C) Low (35°C) Applied standards EN14825 / EN16147, EN14511 and EN12102...
  • Page 76 Model AMS10-8 + SHB10-12 Type of heat pump Air-water Exhaust-water Brine-water Water-water Low-temperature heat pump Integrated immersion heater for additional heat Heat pump combination heater Climate Average Cold Warm Temperature application Average (55°C) Low (35°C) Applied standards EN14825 / EN16147...
  • Page 77 Model AMS10-12 + SHB10-12 Type of heat pump Air-water Exhaust-water Brine-water Water-water Low-temperature heat pump Integrated immersion heater for additional heat Heat pump combination heater Climate Average Cold Warm Temperature application Average (55°C) Low (35°C) Applied standards EN14825 / EN16147...
  • Page 78 Model AMS10-16 + SHB10-16 Type of heat pump Air-water Exhaust-water Brine-water Water-water Low-temperature heat pump Integrated immersion heater for additional heat Heat pump combination heater Climate Average Cold Warm Temperature application Average (55°C) Low (35°C) Applied standards EN14825 / EN16147...
  • Page 79: Electrical Wiring Diagrams

    Electrical wiring diagrams SHB10 TIKI Section 13 | Technical data...
  • Page 80 Section 13 | Technical data SHB10 TIKI...
  • Page 81 SHB10 TIKI Section 13 | Technical data...
  • Page 82 Section 13 | Technical data SHB10 TIKI...
  • Page 83 SHB10 TIKI Section 13 | Technical data...
  • Page 84 Section 13 | Technical data SHB10 TIKI...
  • Page 85 SHB10 TIKI Section 13 | Technical data...
  • Page 86 Section 13 | Technical data SHB10 TIKI...
  • Page 88 TIKI HVAC d.o.o. Partizanska cesta 12, 3320 Velenje Email: servis@tiki.si www.TIKI.si...