CONTROLLED CHILLED BEAM PUMP MODULE
PROACTIVE CONTROL
OWNER'S MANUAL

Advertisement

Table of Contents
loading

Summary of Contents for FläktGroup Semco NEUTON

  • Page 1 ENERGY SAVINGS COST SAVINGS CONTROLLED CHILLED BEAM PUMP MODULE PROACTIVE CONTROL OWNER’S MANUAL...
  • Page 2: Table Of Contents

    NEUTON™ PUMP MODULE TABLE OF CONTENTS Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Configurations .
  • Page 3: Introduction

    NEUTON™ INTRODUCTION This manual describes the installation and maintenance of the NEUTON™ controlled chilled beam pump module . The descriptions include all optional equipment and devices for the unit currently available from SEMCO . If optional equipment is required after receiving the unit, please contact: SEMCO LLC 1800 East Pointe Drive Columbia, MO 65201...
  • Page 4: Principle Of Operation

    NEUTON™ PUMP MODULE PRINCIPLE OF OPERATION Cooling Mode (4 pipe primary loop shown) Note: Only one of NEUTON™ is the HVAC industry’s first smart, plug-and- multiple beams in play controlled chilled beam pump module (CCBPM) zone shown. for reducing chilled beam system installation and operational costs .
  • Page 5: Sequence Of Operation

    NEUTON™ SEQUENCE OF OPERATION NEUTON™ receives space conditions and setpoints from either a communicating wall mount ZS Pro Zone Sensor or from the Building Automation System (BAS) . The sequence begins when power is applied to the controller . The BAS can override the controller operation with a stop command .
  • Page 6: Component Parts

    NEUTON™ PUMP MODULE COMPONENT PARTS Integrated electrical, DDC controls panel Electronically Commutated Motor (ECM) high efficiency, variable speed pump Hot water control valve Chilled water control valve Chilled water return Hot water supply Zone loop return connection Chilled water supply Hot water return Zone supply water connection Pete’s plugs for pressure and flow...
  • Page 7 NEUTON™ Main Power Connection Communications Link (field wiring by contractor) (field wiring by contractor) 18-4 Plenum Cable (field wiring by contractor) • The pump, water temperature sensor, control valves, associated electrical and controls are all factory wired and tested • Only field connections required are main power (208/230/1Ph), zone sensor, and BAS (if used) •...
  • Page 8: Dimensions

    NEUTON™ PUMP MODULE DIMENSIONS: NEUTON DUAL VALVE PUMP MODULE 1A. FRONT 1B. TOP 21-9/16" 21-3/8" 7-11/16" 4-1/8" 3-13/16" 1C. SIDE 1D. BACK 10-1/2" 7-5/16" 10-1/2" FIGURE 1. Dimensions of the NEUTON 4 Dual Valve Pump Module from the front (A), top (B), side (C), and back (D) . OWNER’S MANUAL...
  • Page 9 NEUTON™ DIMENSIONS: NEUTON SINGLE VALVE PUMP MODULE 2A. FRONT 17-1/2" 2B. TOP 7-11/16" 4-1/8" 3-13/16" 20-3/4" 2C. SIDE 2D. BACK 10-1/2" 7-5/16" 10-1/2" FIGURE 2. Dimensions of the NEUTON 2 Single Valve Pump Module from the front (A), top (B), side (C), and back (D) . OWNER’S MANUAL...
  • Page 10: Receiving & Inspecting

    NEUTON™ PUMP MODULE RECEIVING & INSPECTION Upon delivery, confirm that the quantity and model(s) received matches the Bill of Lading . If there is any discrepancy, immediately notify SEMCO LLC . Inspect the packages for signs of damage . If damage is suspected, contact SEMCO immediately . If no visible damage is apparent, the unit should be properly stored until installation .
  • Page 11 NEUTON™ venting is complete . FIGURE 4. Venting the Pump Place provided o-rings on all pipe Venting the pump prior to operation ensures that all air connections . is out of the pump rotor can, and the back bearings are lubricated with water .
  • Page 12 NEUTON™ PUMP MODULE OWNER’S MANUAL...
  • Page 13 NEUTON™ OWNER’S MANUAL...
  • Page 14: Controls

    NEUTON™ PUMP MODULE CONTROLS BACnet MS/TP communications are set up at the controller . See the legend in the center of the I/O Zone 583 for baud rate selection and protocol . Available baud rates are 9600, 1 .92 K, 38 .4 K, and 75 .8 K BPS .
  • Page 15 NEUTON™ Zone Sensor Metrics Temperature and Humidity (standard), CO (optional) Occupied indicator Sensing Element Range Accuracy: Temperature 50° F to 104° F (10° C to 40° C) ±0 .5° F (0 .3° C) Humidity 10% to 90% ±1 .8% typical CO2 ±30PPM or +/±3% of reading Power Requirements/Supply: DDC controller supplies the Rnet zone sensor with 12 Vdc @ 210 mA .
  • Page 16 NEUTON™ PUMP MODULE Reading the Display: ZS Pro Zone Sensor Depending on the control program and the type of sensor, you may see any of the following items in the sensor's screens. This item... Indicates... The temperature is Fahrenheit or Celsius. The value shown is percent relative humidity.
  • Page 17 NEUTON™ Making the Zone Warmer or Cooler   From the Home screen, press the button to show the Setpoint Adjustment screen . This screen typically shows one of the following: Cooling setpoint Cooling setpoint Zone Temperature Adjustment amount (initially 0) Heating Heating Setpoint Setpoint...
  • Page 18 NEUTON™ PUMP MODULE To lock the sensor buttons Simultaneously press and hold the 2 buttons shown below for 5 seconds to lock the sensor's buttons . The display shows a lock icon to indicate the locked state . Press and hold the 2 buttons again for 5 seconds to unlock the buttons . NOTE: If you press the button slightly before the...
  • Page 19: Keypad

    NEUTON™ KEYPAD The BACview keypad (See Figure 9) can be used to adjust setup parameters . The keypad can plug directly into the (See Figure 10) or directly into the I/O Zone 583 Controller . If the CO bottom of the wall mount sensor option on the sensor is included, it may be necessary to plug the BACview directly into the I/O Zone 583 controller, and disconnect...
  • Page 20 NEUTON™ PUMP MODULE POINTS LIST, CONTINUED Exp:- Name Description Type Object ID Device ID Object Name I/O Type Zone RH RH value from Zone Sensor ASVI AI:3 DEV:2402 zone_rh_1 Zone Temp Temperature value from Zone Sensor ASVI AI:4 DEV:2402 zone_temp_1 Condensate If a sensor is wired to input #1, BI:1...
  • Page 21 NEUTON™ Exp:- Name Description Type Object ID Device ID Object Name I/O Type Occupied Occupied setpoint lower limit (minimum AV:13 DEV:2402 occ_setpt_lower_ Setpoint Lower heating) received from BAS via comm or limit_1 Limit set through the BACview keypad . Not adjustable at the Zone Sensor ** .
  • Page 22 NEUTON™ PUMP MODULE POINTS LIST, CONTINUED Exp:- Name Description Type Object ID Device ID Object Name I/O Type Unoccupied Unoccupied setpoint upper limit AV:28 DEV:2402 unocc_setpt_ Setpoint Upper (maximum cooling) received from BAS upper_limit_1 Limit via comm or set through the BACview keypad .
  • Page 23 NEUTON™ Exp:- Name Description Type Object ID Device ID Object Name I/O Type zone 4 enthalpy zone enthalpy calculated based on AV:437 DEV:2402 zone_4_enth_1 the temperature and RH input from (selectable) the Zone Sensor or BAS comm input zone 4 grains zone grains calculated based on AV:438 DEV:2402...
  • Page 24 NEUTON™ PUMP MODULE POINTS LIST, CONTINUED Exp:- Name Description Type Object ID Device ID Object Name I/O Type Occ Status If an occupied command BV:7 is ON, or BV:8 DEV:2402 occ_status_1 the occupied dry contact BI:2 is ON, or if the CO2 override BV:3 is ON then the status is occupied and occupied setpoints are used Override On...
  • Page 25: Troubleshooting

    NEUTON™ TROUBLESHOOTING Problem Action Pump Air Locks The pump is vented by rotating the center screw on the pump a single turn counterclockwise (See Figure 11) and allowing a drop of water to escape . Tighten the vent screw when complete . No flow/movement in actuator Check valve and actuator replacement to ensure valve and actuator are aligned properly .
  • Page 26 NEUTON™ PUMP MODULE Valve and Actuator Replacement Should for any reason the control valves need replacing follow this procedure . Note the orientation and rotation of the valve bodies are not the same . Failure to install the valves and actuators properly will result in loss of functionality .
  • Page 27 NEUTON™ Chilled Water 3-Way Valve Actuator Replacement Figure 14 As shown in the chilled water valve is a 3 way mixing valve with the same type Belimo actuator as used on the hot water valve . When replacing the actuator be sure to disconnect power to the unit .
  • Page 28 WWW.SEMCOHVAC.COM | NEUTON™ Owner’s Manual | 20170417 SEMCO is a global leader in air management. We specialize in the design and manufacture of a wide range of air climate and air movement solutions. Our collective experience is unrivaled. Our constant aim is to provide systems that precisely deliver the best indoor air quality and performance, as well as maximize energy efficiency.