Vantage Hearth TF-120 Installation, Operation & Service Manual

Twin fire unitary infrared heater
Table of Contents

Advertisement

Quick Links

FOR YOUR SAFETY
If you smell gas:
1. Open windows.
2. DO NOT try to light any appliance.
3. DO NOT use electrical switches.
4. DO NOT use any telephone in
your building.
5. Extinguish any open flame.
6. Leave the building.
7. Immediately call your local gas
supplier after leaving the building.
Follow the gas supplier's
instructions.
8. If you cannot reach your gas
supplier, call the Fire Department.
WARNING
Fire Hazard
Keep all flammable objects, liquids and
vapors the minimum required clear-
ances to combustibles away from
heater.
Some objects will catch fire or explode
when placed close to heater.
Failure to follow these instructions can
result in death, injury or property
damage.
WARNING
Improper installation, adjustment, alteration, service
or maintenance can result in death, injury or
property damage. Read the Installation, Operation
and Service Manual thoroughly before installing or
servicing this equipment.
Installation must be done by a contractor qualified
in the installation and service of gas-fired heating
equipment or your gas supplier.
© 2021 Roberts-Gordon LLC
Model TF
Unitary Infrared Heater
Installation, Operation &
Service Manual
Please take the time to read and understand
these instructions prior to any installation.
Installer must give a copy of this manual to the owner.
Keep this manual in a safe place in order to provide
your service technician with necessary information.
Roberts-Gordon LLC
1250 William Street
P.O. Box 44
Buffalo, New York 14240-0044
Telephone: +1.716.852.4400
www.robertsgordon.com
Twin Fire
TF-120
TF-160
TF-200
TF-250
TF-300
TF-350
TF-380
Installer
Owner
P/N 190100NA Rev. N 06/21

Advertisement

Table of Contents
loading

Summary of Contents for Vantage Hearth TF-120

  • Page 1 Unitary Infrared Heater 8. If you cannot reach your gas supplier, call the Fire Department. WARNING Installation, Operation & Service Manual TF-120 Fire Hazard TF-160 Keep all flammable objects, liquids and TF-200 vapors the minimum required clear- ances to combustibles away from TF-250 heater.
  • Page 3: Table Of Contents

    TABLE OF CONTENTS SECTION 1: Heater Safety ............1 NOTE: It is required that all vent pipes and connectors be 1.1 Manpower Requirements ..........1 fastened together with sheet metal screws and sealed with 1.2 Safety Labels and Their Placement......1 high temperature silicone sealant approved for at least 550 °F 1.3 California Proposition 65 ..........
  • Page 5: Section 1: Heater Safety

    SECTION 1: H EATER AFETY SECTION 1: HEATER SAFETY 1.1 Manpower Requirements Your Safety is Important to Us! To prevent personal injury and damage to the heater, This symbol is used throughout two persons will be required for installation. the manual to notify you of possi- 1.2 Safety Labels and Their Placement ble fire, electrical or burn hazards.
  • Page 6 TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL FIGURE 1: Top and Bottom Panel Label Placement Logo Label Gas Connection Label Bottom Panel Top Panel Rating Plate Label Lighting Instruction Plate Label Description Part Number Proposition 65 Label Logo Label 91013221 Rating Plate Label 91010401 Gas Connection Label...
  • Page 7 **When installed in the first 10’ (3m) on each side of the burner. *Le dégagement des grilles sécuritaires et grilles des décoratives sont les mêmes que celles du réflecteur standard. **Quand installé dans les 10' (3m) premiers. Model/Modéle A Model/Modéle A Model/Modéle A TF-120 TF-120 TF-120 TF-160 TF-160 TF-160 TF-200...
  • Page 8: Section 2: Installer Responsibility

    TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL SECTION 2: INSTALLER RESPONSIBILITY the proper clearance dimensions in permanent ink according to your model number and configuration in The installer is responsible for the following: the open spaces on the tag. • To install the heater, as well as the gas and elec- 2.2 Corrosive Chemicals trical supplies, in accordance with applicable specifications and codes.
  • Page 9: Section 3: Clearances To Combustibles

    SECTION 3: C LEARANCES TO OMBUSTIBLES SECTION 3: CLEARANCES TO COMBUSTIBLES WARNING 3.1 Required Clearances to Combustibles Clearances are the required distances that combustible objects must be away from the heater to prevent serious fire hazards. Combustibles are materials, that may catch on fire and include common items such as wood, paper, rubber, fabric, etc.
  • Page 10 2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the burner and burner tube connect. FIGURE 4: LEVEL REFLECTOR (inches) (centimeters) Model TF-120 TF-160 TF-200 TF-250 TF-300 TF-350 TF-380...
  • Page 11 2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the burner and burner tube connect. ° FIGURE 7: 45 TILT REFLECTOR (inches) (centimeters) Model TF-120 TF-160 TF-200 TF-250 TF-300 TF-350 TF-380 FIGURE 8: U-TUBE, LEVEL REFLECTOR...
  • Page 12 2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the burner and burner tube connect. ° FIGURE 10: U-TUBE, OPPOSITE 45 REFLECTOR (inches) (centimeters) Model TF-120 TF-160 TF-200 TF-250 TF-300 TF-350 TF-380 FIGURE 11: 2-FOOT DECO GRILLE AND PROTECTIVE GRILLE...
  • Page 13 2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream from where the burner and burner tube connect. FIGURE 13: VENTING (inches) (centimeters) Model TF-120 Unvented Vent TF-160 Pipes TF-200 Radiant Tubes...
  • Page 14: Section 4: National Standards And Applicable Codes

    TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES 4.1 Gas Codes 4.3 Public Garages The type of gas appearing on the nameplate Installation in garages must be in accordance must be the type of gas used. Installation must with the following codes: comply with national and local codes and United States: Refer to Standard for Parking...
  • Page 15: Section 5: Major Components

    SECTION 5: M AJOR OMPONENTS SECTION 5: MAJOR COMPONENTS FIGURE 14: Major Component Descriptions - Standard Reflector Burner with Tube Gasket Standard Reflector Must be installed (Aluminum or with the flame Stainless observation Steel) window facing down. Alternate overlap as shown on overview and on Burner Tube...
  • Page 16 TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL FIGURE 15: Major Component Descriptions - High Efficiency Reflector High Burner with Tube Gasket Efficiency Must be installed Reflector with the flame (Aluminum observation Only) window facing Alternate down. overlap as shown on overview and on Page 22, Figure 18.
  • Page 17: Standard Parts List

    SECTION 5: M AJOR OMPONENTS 5.1 Standard Parts List Table 1: Contents of Burner Carton Part No. Description TF-120 TF-160 TF-200 TF-250 TF-300 TF-350 TF-380 090XXXXX Burner Assembly (Rate and Fuel Varies) 02568200 Gasket (Burner to Burner Tube) 190100NA Installation, Operation and Service Manual...
  • Page 18 TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL Table 2: Contents of Standard Core and Extension Packages Core Packages Extension Packages Hot Rolled Aluminized Aluminized Hot Rolled Aluminized with Aluminized with with with with Stain- with Aluminum Stainless Steel Aluminum Aluminum less Steel Aluminum Reflector...
  • Page 19 Tubing Length Each Side Core Packages (2 Required) Model Minimum Hot Rolled with Aluminized with Aluminized with Standard Aluminum Reflector Standard Aluminum Reflector Standard Stainless Steel Reflector TF-120 20' (6 m) CP20HRS CP20ALUM CP20ALUMSS TF-160 20' (6 m) CP20HRS CP20ALUM CP20ALUMSS...
  • Page 20 Tubing Length Each Side Core Packages (2 Required) Model Minimum Hot Rolled with Aluminized with High Efficiency High Efficiency Aluminum Reflector Aluminum Reflector TF-120 20' (6 m) CP20HRSEF CP20ALUMEF TF-160 20' (6 m) CP20HRSEF CP20ALUMEF TF-200 30' (9 m) CP30HRSEF...
  • Page 21: Section 6: Suggested Layouts

    Tube or Elbow configuration, the following rules must be adhered to: • A minimum of 10' (3 m) of tubing on TF-120/160 and/or a minimum of 15' (4.5 m) of tubing on the TF-200/250/300/350/380 is required between the burner and the Elbow or U Tube.
  • Page 22: Single Elbow Design (Individual Vents)

    TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL 6.4 TF-160 - Single Elbow Design (Individual Vents) 10' Typ. Burner 90° Elbow (3 m) Tube Individual Vent 6.5 TF-160 - Double "L" Design (Individual Vents) 6.6 TF-250 - Combination "L" and "U" Design (Individual Vents)
  • Page 23: Section 7: Heater Installation

    SECTION 7: H EATER NSTALLATION SECTION 7: HEATER INSTALLATION WARNING WARNING Severe Injury Hazard Cut/Pinch Hazard Secure burner to burner tube with nuts and Wear protective gear during installation, lockwashers. operation and service. Hang heater with materials with a minimum Edges are sharp.
  • Page 24 TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL FIGURE 16: Critical Hanger Placement NOTE: Suspension material provided by others. Total Straight Length (both sides) or Length from U-Tube to U-Tube Typical Expansion Minimum “X” Length in a Double "U" Layout Each Side 0’...
  • Page 25 SECTION 7: H EATER NSTALLATION FIGURE 17: Linear Heater Assembly Overview...
  • Page 26 TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL FIGURE 18: Linear Heater Layout Overview Linear layouts showing one side. Use same measurements for the other side. LEGEND Burner Reflector Tube 20' (6 m) Tube Length (Each Side) Tube/Reflector Hanger Coupling Assembly a = 14"...
  • Page 27 SECTION 7: H EATER NSTALLATION FIGURE 19: Linear Heater Layout Overview (Continued)
  • Page 28: Burner Tube Installation

    TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL Step 7.1 Burner Tube Installation NOTE: Offset mounting Tubing requires a downward hole must be slope of 1/2" (13 mm) to the top. per 20' (6 m) away from burner. Weld seam must be to the bottom of the tube.
  • Page 29: Tube Clamp Package Installation

    SECTION 7: H EATER NSTALLATION Step 7.3 Tube Clamp Package Installation Tube Clamp Bolt Flat Washer Description Part Number Tube Clamp Package 0131890X...
  • Page 30 TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL Step 7.3.1 Coupling and Tube Assembly NOTE: Prior to coupling installation review Swirler Installation on Page 29, Step 7.5. Models TF-250 through TF- 380 require swirler tab to be installed under coupling. Swirler installation for these models must be complete prior to coupling installation.
  • Page 31 • Repeat Step 7.3.1 A - D until all tubes are assembled. See Page 27, Section 7 .3.2. Step 7.3.2 Coupling and Tube Assembly (Continued) Minimum Tube Length Model Per Side TF-120 20’ (6 m) TF-160 20’ (6 m) TF-200 30’...
  • Page 32: Turbulator Installation

    2nd 10' Section Each Side TF-160 2nd 10' Section Each Side TF-200 3rd 10' Section Each Side Model Each Side 1 - 03051501 TF-120 & TF-160 4 - 03051502 1 - 03051501 TF-200 2 - 03051502 Description Part Number Note: Turbulator installation...
  • Page 33: Swirler Installation

    SECTION 7: H EATER NSTALLATION Step 7.5 Swirler Installation Swirler installation required for models specified in "Swirler Installation" chart. Swirler Installation Model Tube Section Swirler Qty TF-250 3rd 10' (3 m) Section 2 Starters + 2 Adapters (per side) Begin installing swirler at end of tube section TF-300 4th 10' (3 m) Section 1 Starter (per side)
  • Page 34 TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL FIGURE 20: Swirler Installation Model: TF-250, 30’ Straight Tube; Swirler Package - 20' (6 m) (p/n 03051511K) Note: Swirler installation for this model must be complete prior to coupling installation for proper swirler starter tab placement. Fold swirler tab Note: Swirler installation same over tube as shown...
  • Page 35 SECTION 7: H EATER NSTALLATION FIGURE 21: Swirler Installation Model: TF-250, 30’ U-Tube; Swirler Package - 20' (6 m) (p/n 03051511K) Pivot Point Swirler Starter Section Swirler Adapter Section 10’ (3 m) Tube Vent Adapter Pivot Point Swirler Adapter Section Swirler Swirler Starter...
  • Page 36 TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL FIGURE 22: Swirler Installation Model: TF-300, 40’ Straight Tube; Swirler Package - 5' (1.5 M) (P/N 03051508K) Burner Tube Coupling Note: Swirler installation same for both sides. Swirler Starter Section Vent Adapter FIGURE 23: Swirler Installation Model: TF-300, 40’ U-Tube; Swirler Package - 5' (1.5 M) (P/N 03051508K) Vent Adapter Swirler Starter...
  • Page 37 SECTION 7: H EATER NSTALLATION FIGURE 24: Swirler Installation Model: TF-350, 40’ Straight Tube; Swirler Package - 20' (6 M) (P/N 03051511K) Pivot Point Swirler Adapter Section Swirler Starter Section Burner Tube Coupling Note: Swirler installation same for both sides. Swirler Starter Swirler...
  • Page 38 TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL FIGURE 26: Swirler Installation Model: TF-380, 50’ Straight Tube; Swirler Package - 10' (3 M) (P/N 03051509K) Burner Tube Coupling Note: Swirler installation same for both sides. Swirler Adapter Pivot Point Swirler Section Adapter Section Swirler...
  • Page 39: Reflector Installation

    SECTION 7: H EATER NSTALLATION 7.6 Reflector Installation WARNING Fire Hazard Support reflector with reflector hanger and support strap. Reflector must not touch tube. Failure to follow these instructions can result in death, injury or property damage. NOTE:All tube surfaces must be covered by a reflector, except for a U-Tube.
  • Page 40 TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL Step 7.6.1 Reflector, U-Clip and Reflector Support Installation The pictorial drawings of the heater construction in reflector supports and U-clips depends on the Section 7 are schematic only and provide a general individual installation. Use either pop rivets or sheet guideline of where hangers, reflector supports and metal screws instead of u-clips when installing end U-clips are to be installed.
  • Page 41: Section 8: Optional Heater Accessories

    45° position as shown below. When designing a U- Tube configuration, the following additional rules must be adhered to: • A minimum of 10' (3 m) on TF-120/160 and a min- imum of 15' (4.5 m) on TF-200/250/300/ 350/380 is required between the burner and the U-Tube.
  • Page 42 TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL FIGURE 28: U-Tube Heater Assembly Overview Description Part Number U-Tube Package 03011000 180° U-Tube 01335901 Tube and Reflector Hanger 03090100 Coupling 01312700 Reflector End Cap (2) 02750800 U-Tube Support Bracket 03020501 4" (10 cm) U-Bolts (2) 91912500 Reflector Support Set 03050010...
  • Page 43 SECTION 8: O PTIONAL EATER CCESSORIES FIGURE 29: U-Tube Heater Layout Overview U-tube layouts showing one side. Use same measurements for the other side. LEGEND Burner Reflector Tube 10' (3 m) 20' (6 m) Tube Length* (Each Side) Tube 5' (1.5 m)** Tube/Reflector Hanger Coupling...
  • Page 44 TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL FIGURE 30: U-Tube Heater Layout Overview (Continued)
  • Page 45: Elbow Package Configuration

    PTIONAL EATER CCESSORIES 8.2 Elbow Package Configuration Step 8.2.1 Elbow Installation Minimum Distance Required Between Burner and Elbow Minimum Model Distance Description Part Number TF-120 Elbow Package 0271870X TF-160 90° Elbow 01335801 TF-200 Coupling 01312700 TF-250 Reflector End Cap 0275080X...
  • Page 46 TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL Step 8.2.4 Reflector Joint Installation Step 8.2.5 Reflector Joint Detail FIGURE 31: Reflector Joint Detail...
  • Page 47: Reflector Side Extension

    SECTION 8: O PTIONAL EATER CCESSORIES 8.3 Reflector Side Extension Step 8.3.1 Bracket Installation Tube Reflector Tube and Reflector Hanger Reflector Support Reflector Side Extension Bracket (2 per Reflector) Use additional supports in high air movement applications. Description Part Number Reflector Side Extension Package 0271270X Reflector Side Extension-96"...
  • Page 48: Lower Clearance Shield Installation

    TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL 8.4 Lower Clearance Shield Installation Step 8.4.1 Shield Support Strap Assembly Reflector 12" (30 cm) 17" (43 cm) Align Pilot Holes Lower Clearance Shield Locknuts Washers Description Part Number Lower Clearance Shield Package 01397501 Shield Support Strap 01397500...
  • Page 49 SECTION 8: O PTIONAL EATER CCESSORIES Step 8.5.2 Frame Shield Installation Description Part Number Deco Grille Shield-24" (61 cm) 01365900 Step 8.5.3 Reflector Side Extension Installation for Decorative Grilles Distance "A" Extension Minimum Maximum Part No. Width 2" (4 cm) 6"...
  • Page 50: Protective Grille Installation

    TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL 8.6 Protective Grille Installation Step 8.6.1 Silicone Cap Installation Silicone Cap Description Part Number Grille Section 08050001 Grille Grille End Cap 08050002 Finger Grille Section - EF Reflector 08050003 Grille End Cap - EF Reflector 08050004 Note: Protective Grille NOT APPROVED for Silicone Cap...
  • Page 51: Section 9: Venting

    SECTION 9: V ENTING SECTION 9: VENTING a high temperature silicone sealant. WARNING Maintain a minimum of 6" (15 cm) clearance around all single wall flue pipe. Any portion of vent pipe passing through a combustible wall must have an approved thimble to conform with the above listed codes.
  • Page 52: Unvented Operation

    TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL Canadian Requirements In noncombustible walls only, vent terminal The vent shall not terminate within 6' (1.8 m) of a (P/N 02537801-1P) may be used. mechanical air supply inlet to any building. For 4" (10 cm) vents in either combustible or noncombustible walls, use Tjernlund VH1-4 (P/N The vent shall not terminate within 3' (0.9 m) of a 90502100) or equivalent, insulated vent terminal.
  • Page 53: Unvented Operation Tube Termination

    SECTION 9: V ENTING 9.4 Unvented Operation Tube Termination Subtract 15' (4.6 m) of maximum allowed vent or duct length per vent elbow if more than two are Turndown type vent terminal with a screen must be used. installed at the exhaust end of the tube. Vent terminal design shall not incorporate backdraft flap.
  • Page 54: Vertical Venting (Category Iii) 4'' (10 Cm) Pipe

    TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL 9.8 Vertical Venting (Category III) 4'' (10 cm) Pipe Description Part Number Vent Cap 4" (10 cm) 90502300 NOTE: It is required that all vent pipes and connectors be fastened together with sheet metal screws and sealed with high temperature silicone sealant approved for at least 550 °F (288 °C) (supplied by others).
  • Page 55: Common Side Wall Horizontal Venting (Category Iii)51

    SECTION 9: V ENTING 9.10 Common Side Wall Horizontal Venting (Category III) Description Part Number Vent Tee 91916100 Vent Terminal 6" (15 cm) 90502101 9.11 Common Vertical Venting (Category III) Description Part Number Vent Cap 6" (15 cm) 90502302 NOTE: It is required that all vent pipes and connectors be fastened together with sheet metal screws and sealed with high temperature silicone sealant approved for at least 550 °F (288 °C) (supplied by others).
  • Page 56: Flexible Boot Installation (Common Vent)

    TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL 9.12 Flexible Boot Installation (Common Vent) Rubber Rings Description Part Number Rolled Sleeve 09080000 Flexible Boot 91412801 Boot Clamp 5" (13 cm) 91901301 Vent Tee - 4" Dia. x 4" Dia. x 6" Dia. 91916100 Rubber Ring 91906900...
  • Page 57: Outside Combustion Air Supply

    Seal all combustion air pipe joints. minimum distance of 3' (93 cm) for both vertical and For TF-120 4" (10 cm) single wall pipe or for horizontal venting. TF-160/200/250/300/350/380 5" (13 cm) single wall pipe, PVC pipe, aluminum flex duct, or equivalent 9.13.1 Length Requirements...
  • Page 58 TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL 9.13.3 Horizontal Outside Air Supply Approved Single Wall Vent Cap Vent Pipe Secure with (3) #8 x 3/8 Sheet Metal Screws Burner Description Part Number Tube Vent Cap 5" (13 cm) 90502301...
  • Page 59: Section 10: Gas Piping

    SECTION 10: G IPING SECTION 10: GAS PIPING Install the gas hose as shown on Page 56, Figure 33. The gas hose accommodates expansion of the WARNING heating system and allows for easy installation and service of the burner. A 90° pipe elbow (not supplied) must be installed into the gas valve to ensure proper orientation of the flex gas connector.
  • Page 60 TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL FIGURE 33: Gas Connection with Flexible Gas Hose Shut-Off Valve (included CORRECT POSITIONS with gas hose) must be High Gas Pressure CAUTION parallel to burner gas Regulator to be inlet. The 3" (8 cm) installed upstream of Product Damage Hazard displacement shown is...
  • Page 61: Section 11: Wiring

    SECTION 11: W IRING SECTION 11: WIRING Heaters can be controlled using several methods. Normally thermostats are used to control the heaters DANGER but they can also be controlled by an Energy Management System. Section 11.1 below illustrates the connection for heaters controlled by a line voltage thermostat.
  • Page 62: Low Voltage Thermostat And Relay Wiring

    TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL 11.2 Low Voltage Thermostat and Relay Wiring FRONT VIEW BACK VIEW Transformer Relay Low Voltage Thermostat Black COIL COIL Black 120 V - 60 Hz Supply Circuit White Additional Burners Gnd. Gnd. Gnd. Maximum 6 burners per relay.
  • Page 63: Internal Wiring Diagram

    SECTION 11: W IRING 11.3 Internal Wiring Diagram 11.4 Ladder Diagram...
  • Page 64: Electrical Connection To The Burner

    TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL 11.5 Electrical Connection to the Burner...
  • Page 65: Section 12: Operation And Maintenance

    SECTION 12: O PERATION AND AINTENANCE SECTION 12: OPERATION AND MAINTENANCE WARNING DANGER Electrical Shock Hazard Explosion Hazard Burn Hazard Cut/Pinch Hazard Disconnect electric Turn off gas supply to Allow heater to cool Wear protective gear before service. heater before service. before service.
  • Page 66: Maintenance Checklist

    TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL equipment. To help facilitate optimum performance and safety, 12.5 Maintenance Checklist Roberts-Gordon LLC recommends that a qualified contractor conduct, at a minimum, annual Installation Code and Annual Inspections: inspections of your ROBERTS GORDON equipment ®...
  • Page 67 SECTION 12: O PERATION AND AINTENANCE Tubes Make sure there are no cracks. Make sure tubes are connected and suspended securely. See Page 19, Section 7. Make sure there is no sagging, bending or distortion. Clean or replace as required. Gas Line Check for gas leaks.
  • Page 68: Section 13: Troubleshooting

    SECTION 13: TROUBLESHOOTING DANGER Electrical Shock Hazard Disconnect electric before service. Heater must be properly earthed. Failure to follow these instructions can result in death or electrical shock. WARNING Fire Hazard Explosion Hazard Burn Hazard Cut/Pinch Hazard Keep all flammable Turn off gas supply to Allow heater to cool Wear protective gear...
  • Page 69: Troubleshooting Flow Chart

    13.1 Troubleshooting Flow Chart...
  • Page 71: Manifold Gas Pressure Setting

    13.2 Manifold Gas Pressure Setting Control Side View of Heater Manometer 10.5" 3.5" Natural Propane...
  • Page 72: Section 14: Replacement Parts

    SECTION 14: REPLACEMENT PARTS WARNING DANGER Electrical Shock Hazard Explosion Hazard Carbon Monoxide Hazard Fire Hazard Use only genuine ROBERTS GORDON ® replacement parts per this installation, operation and service manual. Failure to follow these instructions can result in death, electric shock, injury or property damage. See warnings and important information before removing or replacing parts.
  • Page 73 SECTION 14: R EPLACEMENT ARTS Blower with Blower with Door Screen and Gasket Screen and Gasket Switch Burner Cup Viewer Window Burner Tube Gasket Electrode Pressure Pressure Gas Valve Switch Switch Air Collar Transformer Electrode Gasket Ignition Module Indicator Light...
  • Page 74 TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL Part Number Description 90033700 Gas Valve (Natural) 90033700K Gas Valve Kit (LP) (consists of NG gas valve and spring conversion kit) Gasket: 09060000 (160/200/250/300/350/380) 03050900 (120) Screen (160/200/250/300/350/380) 09050000 (120) 03050800 Blower (160/200/250/300/350/380) 90710400-P (120) 90708600-P...
  • Page 75: Section 15: General Specifications

    Heat Input Rate Minimum Minimum Mounting Height* Model (Btu/h) X (1000) Linear U-Tube Space Spot TF-120 20' (6 m) 11'6" (4 m) 12' (4 m) 9' (3 m) TF-160 20' (6 m) 11'6" (4 m) 15' (5 m) 11' (3 m)
  • Page 76 TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL...
  • Page 77: Section 16: The Roberts Gordon ® Vantage ® Tf War- Ranty

    SECTION 16: T ROBERTS GORDON VANTAGE TF W ® ® ARRANTY SECTION 16: THE ROBERTS GORDON The ownership of the ROBERTS GORDON VANTAGE ® ® ® TF is moved or transferred. This warranty is VANTAGE TF WARRANTY ® nontransferable. ROBERTS-GORDON LLC WILL PAY FOR: Roberts-Gordon LLC is not permitted to inspect the damaged equipment and/or component parts.
  • Page 78 TF-S ERIES NSTALLATION PERATION AND ERVICE ANUAL...
  • Page 79 SECTION 16: T ROBERTS GORDON VANTAGE TF W ® ® ARRANTY 2020...
  • Page 81 SECTION 16: T ROBERTS GORDON VANTAGE TF W ® ® ARRANTY...

This manual is also suitable for:

Tf-160Tf-200Tf-250Tf-300Tf-350Tf-380

Table of Contents