Page 2
Dear Customer, We congratulate you on choosing these product Clivet has been working for years to offer systems able to assure the maximum comfort for a long time with highly-reliable, efficient, high-quality and safe solutions. The target of the company is to offer advanced systems, that assure the best comfort and reduce energy consumption as well as the installation and maintenance costs for the entire life-cycle of the system.
1 SAFETY CONSIDERATIONS Pay particular attention to: Manual The manual provides correct unit installation, use and warnings / prohibitions / danger indicating particularly important maintenance. operations or information, operations It is advisable to read it carefully so you will save time during that cannot be done, which compromise operations.
Page 5
1 SAFETY CONSIDERATIONS Modification All unit modifications will end the warranty coverage and the manufacturer responsibility. Breakdown/Malfunction Disable the unit immediately in case of breakdown or malfunction. Contact a certified service agent. Use original spares parts only. Using the unit in case of breakdown or malfunction: ...
Page 6
1 SAFETY CONSIDERATIONS The installer must train the user, particularly on: Start-up/shutdown Set points change Standby mode Maintenance What to do / what not to do in case of breakdown Unit identification The serial number label is positioned on the unit and allows to indentify all the unit features.
2 BEFORE INSTALLATION Reception You have to check before accepting the delivery: That the unit hasn’t been damaged during transport That the materials delivered correspond with that indicated on the transport document comparing the data with the identification label positioned on the packaging.
Page 8
2 BEFORE INSTALLATION Handling Check that all handling equipment complies with local safety regulations (cran, forklifts, ropes, hooks, etc.). Provide personnel with personal protective equipment suitable for the situation, such as helmet, gloves, accident-prevention shoes, etc. Observe all safety procedures in order to guarantee the safety of the personnel present and the of material.
3 SELECTING THE INSTALLATION SITE Positioning Installation must be in accordance with local regulations. If they do not exist, follow EN378 . During positioning consider these elements: customer approval unit weight and bearing point capacity safe accessible position ...
Page 10
3 SELECTING THE INSTALLATION SITE Avoid therefore: obstacles to the airflow exchange difficulties leaves or other foreign bodies that can obstruct the exchange batteries winds that hinder or favour the airflow heat or pollution sources close to the unit (chimneys, extractors etc) ...
4 WATER CONNECTIONS Hydraulic system The pipes must be designed and manufactured to limit pressure drops as much as possible, i.e. optimise performance of the system. Keep the following to a minimum: overall length number of bends ...
Page 12
4 WATER CONNECTIONS Risk of freeze If the unit or the relative water connections can be subject to temperatures close to 0°C: Mix water with ethylene glycol, or The unit must always be protected Safeguard the pipes with heating cables placed under the from freeze.
Page 13
4 WATER CONNECTIONS Water flow-rate Minimum water flow The design water flow-rate must be: inside the exchanger operating limits (see the TECHNICAL INFORMATION chapter) guaranteed also with variable system conditions (for example, in systems where some circuits are bypassed in particular situations) If the system capacity is below the minimum flow, bypass the system as indicated in the diagram.
Page 14
4 WATER CONNECTIONS Flow Switch The flow switch must be present to ensure shutdown of the unit if Flow switch water is not circulating. It has to be installed in a duct rectilinear part, not in proximity of curves that cause turbulences. Operations sequence Before starting the unit pump: 1 Close all vents in the high points of the unit’s water circuit.
Page 15
4 WATER CONNECTIONS Standard unit Unit + pump exchanger chemical cleaning bypass 14 pressure gauge exchanger system cleaning bypass 15 check valve antifreeze heater 10 vent 16 pump water temperature probes 11 drain 17 safety valve 12 water flow switch 18 shut-off valves differential pressur switch 13 system loading safety pressure...
Page 16
4 WATER CONNECTIONS Partial energy recovery Option A configuration which enables the production of hot water free-of- charge while operating in the cooling mode, thanks to the partial recovery of condensation heat that would otherwise be rejected to the external heat source. The maximum capacity available from the partial recovery is equal to the 15% of the rejected heating capacity (cooling capacity + compressor power input)
5 ELECTRICAL CONNECTIONS The characteristics of the electrical lines must be determined by specialized personnel able to design electrical installations; moreover, the lines must be in conformity with regulations in force. The protection devices of the unit power line must be able to stop the presumed short circuit current, whose value must be determined in function of system features.
Page 18
5 ELECTRICAL CONNECTIONS Distribution systems NO systems IT ! The compressors are compatible with TT or TN type systems. They cannot be used in IT systems. Signals / data lines Do not overpass the maximum power allowed, which varies, according to the type of signal.
Page 19
5 ELECTRICAL CONNECTIONS Power supply cables section Size 120.1 160.1 200.1 240.1 250.2 1 x 95 1 x 150 1 x 240 2 x 150 1 x 240 Min. cable section Cu (mm²) 1 x 185 1 x 240 1 x 240 2 x 300 1 x 240...
Page 21
5 ELECTRICAL CONNECTIONS Computer connection Configure P.C. 1 connect P.C. and main module with LAN cable 2 check in the taskbar that the connection is active 3 open Control Panel and select Network and sharing center 4 select Modify board setting 5 select Local area connection (LAN) 6 select Internet protocol version 4 (TPC) IPV4 and enter Property...
Page 22
5 ELECTRICAL CONNECTIONS Remote Control Option 1 Distance up to 350 mt 2 Distance up to 700 mt User interface B=B1 KNX bus, max 350 mt twisted pair with shield, ø 0,8 mm EIB/KNX cable marking recommended PSX - Mains power supply unit power supply unit N125/11 5WG1 125-1AB11 AC 120...230V, 50...60Hz KNX bus, max 350 mt...
Page 23
5 ELECTRICAL CONNECTIONS Modbus - RS485 Option LED BSP communication with AP1 module LED BUS communication with Modbus green communication ok green communication ok yellow software ok but communication with AP1 down yellow startup / channel not communicating flashing: software error communication down fixed: hardware error...
6 START-UP General indicated operations should done qualified technician with specific training on the product. The electrical, water connections and the other system works are by the installer. Agree upon in advance the start-up data with the service centre. Agree upon in advance the star-up data with the service centre.
Page 25
6 START-UP Preliminary checks Unit OFF power supply Yes / No safe access suitable frame to withstand unit weight + people weight functional clearances air flow: correct return and supply (no bypass, no stratification) considered level to be reachable by snow considered main winds lack of chimneys/corrosive atmospheres/pollutants structure integrity fans run freely unit on vibration isolators The unit must be level. unit input water filter + shut-off valves for cleaning vibration dampeners on hydraulic connections expansion tank (recommended volume = 10% system content)
Page 26
6 START-UP Start-up sequence Unit power supply ON Yes / No compressor carter resistances operating at least since 8 hours off-load voltage measure phase sequence check pump manual start-up and flow check refrigeration circuit shut-off valves opening (if applicable) unit ON load voltage measure verify the lack of bubbles in the liquid light (if applicable)
Page 27
6 START-UP Cooling circuit 1 Visually inspect the refrigerating circuit: the presence of oil stains can by a symptom of leakage (caused e.g. by transportation, handling or other). 2 Verify that the refrigerating circuit is in pressure: Using the unit manometers, if present, or service manometers.
Page 28
6 START-UP Voltage Check that the air and water temperatures are within in the operating limits. Start-up the unit. While the unit is operative, i.e. in stable conditions nearing operating ones, check: Power supply voltage Total absorption of the unit ...
Page 29
6 START-UP Demand limit Menu accessible only after having entered the password. Access reserved only to specifically trained personnel. The parameter modification can cause irreversible damages. It is possible to limit the absorbed electric power with an external signal 0-10 Vcc or 4-20mA.
Page 30
6 START-UP Climatica TExt Menu accessible only after having entered the password. Access reserved only to specifically trained personnel. The parameter modification can cause irreversible damages. The setpoint based on the climatic curve and the Water Reset is displayed on the display Only if P0053: En Climatica = 1 Path: Main menu / Unit parameters / Options Path: Main menu / Unit parameters / Climatic TExt...
Page 31
6 START-UP Water reset Menu accessible only after having entered the password. Access reserved only to specifically trained personnel. The parameter modification can cause irreversible damages. It is possible to limit the absorbed electric power with an external signal 0-10 Vcc or 4-20mA.
Page 32
In the event of a compressor breakdown due to operating in the above-mentioned conditions, the warranty shall not be valid and Clivet spa declines any responsibility. Periodically check the average operating times and frequency of compressor start-ups: indicatively the minimum thermal load must be such as to require a compressor to operate for at least ten minutes.
Page 33
6 START-UP Start-up report To detect the objective operational conditions is useful to control the unit over time. With unit at steady state, i.e. in stable and close-to-work conditions, identify the following data: total voltages and absorptions with unit at full load ...
Page 38
7 CONTROL Alarm list - 1 Description ce1108 Critical. Inverter in critical overload status ce1111 Critical. Inverter in critical unvervoltage status ce1112 Critical. Inverter in critical over-temperature status ce1116 Critical. Main CPU HW error ce1117 Critical. Temperature sensor error ce2108 Critical.
Page 39
7 CONTROL Alarm list - 2 Description eE0057 Recovery pump inverter alarm EE0060 Source pump 1 thermal protection active eE0061 Source pump inverter alarm ee0100 Communication error between 98U1 expansion module and POL687 ee0101 Communication error between 98U2 expansion module and POL687 ee0110 Communication error between 98U3 expansion module and POL687 ee0130...
Page 40
7 CONTROL Alarm list - 3 Description ee2106 Fault. Motor in overload protection ee2108 Fault. Inverter in overload protection ee2109 Fault. Inverter in overcurrent ee2110 Fault. Inverter in overvoltage ee2111 Fault. Inverter in undervoltage ee2112 Fault. Inverter in over-temperature ee2113 Fault.
Page 41
7 CONTROL Alarm list - 4 Description iI0002 Utility hydraulic pressure alarm iI0006 User side differential pressure switch/flow alarm II0007 User freeze alarm ii0008 Pumps active in freeze protection II0009 Incongruent differential between user Tin and Tout II0010 Recovery freeze alarm ii0011 Pumps active in recovery freeze protection II0012...
MAINTENANCE General Maintenance must be performed by authorized centres or by qualified personnel The maintenance allows to: maintaining the unit efficient reduce the deterioration speed all the equipment is subject to over time collect information and data to understand the efficiency state of the unit and prevent possible faults WARNING ...
Page 43
8 MAINTENANCE intervention frequency (months) Presence of corrosions Panel fixing Fan fixing coil cleaning Water filter cleaning water: quality, pH, glycol concentration check exchanger efficiency circulation pump Check of the fixing and the insulation of the power lead 10 earth cable check 11 Electric panel cleaning 12 power remote controls status 13 clamp closure, cable isolation integrity...
Page 44
MAINTENANCE Unit booklet Foresee a unit schedule to keep trace of the interventions made on the unit. In this way, it will be easier to adequately schedule the various interventions and facilitate any troubleshooting. On the schedule note: date ...
Page 45
8 MAINTENANCE Water side heat exchanger The exchanger must to be able to provide the maximum thermal exchange, therefore it is essential for the inner surfaces to be clean of dirt and build-up. Periodically check the difference between the temperature of the supply water and the condensation temperature: if the difference is greater than 8°C–10°C it is advisable to clean the exchanger.
Page 46
8 MAINTENANCE Safety valve The pressure relief valve must be replaced : if it has intervened if there is oxidation based on the date of manufacture, in compliance with local regulations. Valve replacing The 3-piece joint allows the valve replacement. ...
Page 47
MAINTENANCE Air coil Accidental contact with the exchanger fins can cause cuts: wear protective gloves. The coil must allow maximum thermal exchange, therefore, the surface must be clear from dirt and scaling. It is recommended a quarterly cleaning of the coils, as the minimum.
Page 48
8 MAINTENANCE Electric fans Check: the fans and the relative protection gridsare well fixed the fan bearings (evident by noise and anomalous vibrations) the terminal protection covers are closed and the cable holders are properly positioned. Screw compressors - Periodical checks...
REFRIGERANT LEAK DETECTOR Option present with compressor box For specific information refer to the component manufacturer's manual.. Maintenance The inspection must be carried out by qualified service personnel. Check the correct operation of the LEDs. Check the correct functioning of the buzzer and relay. ...
DECOMMISSIONING Disconnection WARNING Before performing any operation, read the warnings found in the Maintenance chapter. Avoid leak or spills into the environment. Before disconnecting the unit, the following must be recovered, if present: refrigerant gas Anti-freeze solutions in the hydraulic circuit Awaiting decommissioning and disposal, the unit can also be stored outdoors, as bad weather and rapid changes in temperature do not harm the environment provided that the electric, cooling and hydraulic circuits...
RESIDUAL RISKS General In this section the most common situations are indicated,as these cannot be controlled by the manufacturer and could be a source of risk situations for people or things. Danger zone This is an area in which only an authorised operator may work. The danger zone is the area inside the unit which is accessible only with the deliberate removal of protections or parts thereof.
Page 57
RESIDUAL RISKS Do not remain in the vicinity of the safety valve and never leave the refriger-ating system taps closed. Electric parts An incomplete attachment line to the electric network or with incorrectly sized cables and/or unsuitable protective devices can cause electric shocks, intoxication, damage to the unit or fires.
General technical data Operating range - Excellence Ta (°C) = external exchanger inlet air temperature (D.B.) To (°C) = internal exchanger outlet water temperature Standard unit operating range at full load Standard unit operating range with air flow automatic modulation Operating range - Premium Ta (°C) = external exchanger inlet air temperature (D.B.) To (°C) = internal exchanger outlet water temperature...
Page 74
FOR OVER 30 YEARS, WE HAVE BEEN OFFERING SOLUTIONS TO ENSURE SUSTAINABLE COMFORT AND THE WELL-BEING OF PEOPLE AND THE ENVIRONMENT www.clivet.com CLIVET SPA Via Camp Lonc 25, Z.I. Villapaiera 32032 Feltre (BL) - Italy Tel. +39 0439 3131 - Fax +39 0439 313300 info@clivet.it...
Need help?
Do you have a question about the WDAT-ik4 and is the answer not in the manual?
Questions and answers