OFF position (Default)
Example 1: Conventional Two-Stage Cooling and Heating -
V1 operates in dual stage heat / cool mode using thermostat signals W1, W2, Y1, Y2, and fan signal (G). G1, G2 and G3 are
available but not required.
Example 2: Single-Stage Operation-
If Y2 or W2 is left unconnected or is unavailable from the thermostat
set SW1-1 to the ON position.
RMF-CA200-V1 simulating multiple stage operation using temperature
differential based on W1 / Y1 call and run time.
 
Example 3: Heat Pump Mode Operation -
If Y2 or W2 is left unconnected or is unavailable from the thermostat
set SW1-1 to the ON position.
RMF-CA100-V1 simulating multiple stage operation using temperature
differential based on W1 / Y1 call and run time.
 
Default OFF position configures conventional mode, ON position enables Heat Pump mode
Dipswitch 1-1 set to ON position
This configures single stage operation of
Dipswitch 1-1 set to ON position
This configures single stage operation of
Dipswitch 1-1 set to OFF position (default position) RMF-CA200-
Conventional Mode Connector Pin Layout
Pin
1
2
3
4
5
6
7
8
9
10
11
12
In single stage operation Y2, W2 and 
W3 signals are not used. 
Signal
Description
TC
Common (IN) Transformer
C
Common (Out) To Thermostat
TR
24 VAC (IN) Transformer
R
24 VAC (IN) Thermostat
Y2
Stage 2 Cooling
Y1
Stage 1 Cooling
W2
Stage 2 Heat
W1
Stage 1 Heat
W3
Stage 3 Heat
G
Fan
O
Stage 4 Heat
EO
Error Output (Out)