Download Print this page

United Technologies Kidde VM-ETH Installation Sheet

Ethernet adapter card

Advertisement

Quick Links

VM-ETH Ethernet Adapter
Card Installation Sheet
Description
The VM-ETH Ethernet Adapter Card provides a standard 10/100BaseT
Ethernet network connection for control panel programming and
diagnostics. It also provides transmission of system events to central
monitoring stations (CMSs), computers running FireWorks, and SMTP
email servers.
The following table below describes the available models.
Models
Number
Description
VM-ETH1
Supports panel programming and diagnostics, and
communication with a computer running FireWorks
VM-ETH2
Supports panel programming and diagnostics, and
communication with a computer running FireWorks and a
CMS
VM-ETH3
Supports panel programming and diagnostics, and
communication with a computer running FireWorks, a
CMS, and an SMTP email server
Installation
Install and wire the adapter card in accordance with applicable national
and local codes, ordinances, and regulations.
WARNING:
Electrocution hazard. To avoid personal injury or death
from electrocution, remove all sources of power and allow stored
energy to discharge before installing or removing equipment.
Cautions
Equipment damage hazard. This product is sensitive to
electrostatic discharge (ESD). To avoid damage, follow accepted
ESD handling procedures.
If removing the VM-CPU main board, first pull out the four plungers
securing it to the electronics chassis. Failure to do so can result in
damage to the main board.
P/N 3101794-EN • REV 03 • ISS 15FEB16
To install the adapter card:
1. Plug the card into J3 on the back of the VM-CPU main board. See
Figure 1.
2. Position the restraining bracket recess over the card, and then
insert the bracket hooks into the slots on the VM-CPU. See
Figure 2.
3. Push the plunger (Figure 2, item 2) through the front of the
VM-CPU and into the restraining bracket, and then push the
locking pin (item 1) into the plunger to secure it.
Figure 1: Installing the adapter card
RJ-45
VM-CPU
Figure 2: Mounting the restraining bracket on the adapter card
(1)
(2)
(1) Locking pin
(2) Plunger
Wiring
Connect field wiring as shown if Figure 3.
Notes
Wiring is power-limited and unsupervised.
Maintain 0.25 in. (6 mm) separation between power-limited and
nonpower-limited wiring at all times.
J3
VM-ETH
(3)
(4)
(3) Restraining bracket
(4) Bracket recess
1 / 2

Advertisement

loading

Summary of Contents for United Technologies Kidde VM-ETH

  • Page 1 To install the adapter card: 1. Plug the card into J3 on the back of the VM-CPU main board. See Figure 1. 2. Position the restraining bracket recess over the card, and then insert the bracket hooks into the slots on the VM-CPU. See VM-ETH Ethernet Adapter Figure 2.
  • Page 2 Figure 3: Ethernet wiring Legend (1) RJ-45 Ethernet patch cable, Cat 5e or better (2) To the RJ45 connector on a PC with the VM-CU for panel programming and diagnostics. (3) To the RJ-45 connector on a FireWorks workstation. For wiring details, see the FireWorks documentation.