Fireye 60-2991 Series Manual page 9

Burnerpro wiring harness to replace hw rm7800 series control with burnerpro series
Table of Contents

Advertisement

60-2991-2 Wiring
Honeywell Term
5
L2
F
G
6
7
10
8
9
4
3
20
21
1
Terminal 4 is internally jumpered to terminal 1 via the BurnerPro control.
2
If the Honeywell control used a non-self check UV scanner, then the Honeywell scanner must be removed and the Fireye UV
scanner must be wired into terminals 22 and 23 on the BurnerPro wiring base.
3
The BurnerPro will lockout when the Running Safety Interlock circuit opens. Jumper JR3 on the RM7895 selects recycle or
lockout.
4
Terminal 17 on the BurnerPro provides interrupted operation of the pilot fuel valve. If intermittent operation is required, an
external jumper between terminals 17 and 19 on the BurnerPro wiring base must be added. The jumper could also be installed
between terminals 8 and 21 on the Honeywell wiring base. The timing of terminal 17 can also be programmed via Modbus for
continuous (intermittent) operation.
5
Proof of Closure used on RM7897
6
Delayed Main Valve used on RM7897C
© 2021 Carrier
Function
Line Voltage Supply
Line Voltage Common
2
Flame Rod
Flame Rod Ground
2
UV Scanner
2
UV scanner
Operating Control & Limits
Running Safety Interlock (Air Flow)
Ignition Transformer
Interrupted Pilot Fuel Valve
Main Fuel Valve
Blower Motor
Alarm
Proof of Closure
Delayed Main Fuel Valve
BurnerPro Term
1 & 4
2
24
Earth Ground
22
23
5
3
14
16
4
17
18
6
3
5
12
6
Confirm - 18
1
2
2
3
4
5
6
9