Page 1
La Marche Manufacturing Company www.lamarchemfg.com A36D Series Controlled Ferroresonant Rectifier / Power Supply Installation and Operation Manual 106 Bradrock Dr. Des Plaines 60018-1967 Instruction Drawing Number: P25-LA36DSERIES-2 Tel: 847 299 1188 Fax: 847 299 3061 CPN 129389 Revision A07 Rev. Date: 12/19...
Page 2
Important Safety Instructions Before using this equipment, read all manuals and other documents related to this charger and other equipment connected to this charger. Always have a copy of a charger’s manual on file nearby in a safe place; if a replacement copy of a manual is needed, it can be found at www.lamarchemfg.com.
Page 3
Charger Location • Allow at least 6 inches of free air on all vented surfaces for proper cooling • Allow sufficient clearance to open the front panel for servicing. • Do not operate this charger in a closed-in area or restrict ventilation in any way. •...
Table of Contents Important Safety Instructions ......................... Table of Contents ............................iii Table of Figures ............................iv Model Scope/General Description ........................1 Understanding the Model Number ......................... 1 Optional Accessories Included in the Charger ....................1 Quick Start Guide ............................2 Equipment Handling ..........................
Model Scope/General Description The La Marche model A36D is a controlled ferroresonant float charger designed to power a load while charging the battery. The all solid-state electronic control circuit provides excellent line-load voltage regulation, current limiting, and a power failure relay with light and Form “C” contacts. The A36D is offered with DC output voltages of 12, 24, 48VDC with output currents from 6 to 200 Amps.
A36D Quick Start Guide La Marche A36D Battery Charger: Getting Started WARNING: Please read the Important Safety Instructions before proceeding. Make sure to check for any shipping damages before getting started. 1 – Connect Proper AC Voltage Confirm proper AC voltage against charger nameplate. If charger is multi-tap, refer to AC Input Voltage Tap Configuration table inside the charger or on charger schematic.
Equipment Handling Storing the A36D If the A36D is to be stored for more than a few days after delivery, it should be stored within its shipping container. The location chosen for storage should be within an ambient temperature of -40 to 185° F (-40 to 85° C) with a non-condensing relative humidity of 0 to 95%.
Page 9
Ampere Rating Output Frequency Voltage 75 ADC 100 ADC 150 ADC 200 ADC 200 ADC 300 ADC 400 ADC 33E Case 33E Case 9D Case 9D Case 110 lbs 130 lbs 145 lbs 180 lbs 60 Hz 49.9 kg 59 kg 65.8 kg 81.6 kg 12 VDC...
Installation Mounting the A36D When mounting the A36D in any configuration, consider the size and weight of the charger. The wall, rack, and/or floor must be able to support the weight of the charger as well as an additional safety factor. Verify the weight of the A36D charger using Tables 1, 2 and 3, and the method of mounting using Table 4 below.
2.1.1 Rack-Mounting the A36D The A36D can be installed in most relay racks with standard EIA hole spacing. If a relay rack is needed, they are available for purchase from La Marche. The 4D, 9E, 33, 33E, and 39 enclosures are shipped from the factory with the necessary brackets installed for rear mounting on a relay rack The rack mounting bracket for the 4D and 39 enclosures allow for mounting on a 19”...
2.1.2 Floor-Mounting the A36D Floor-mounting the 43, 44, and 72 enclosures is standard. To floor-mount the A36D, install four to six anchor bolts into the floor. Place the charger on the bolts, add appropriate mounting hardware, and tighten securely. The figure below shows the footprint and the bolt size of each A36D enclosure style. All dimensions are in inches. Case Size Bolt Size 11.5”...
AC Input Connections Before beginning any work inside the charger, ensure that all incoming AC supply power is off at the main breaker box and the charger’s breakers are off. Check that the source voltage and frequency match the voltage and frequency listed on the charger nameplate.
DC Output Connections Before making any of DC output connections, make sure you have read and fully understand the DC Connection Procedure below. Select proper size for the DC wiring from the wire size table on the previous page. If the distance between the charger’s DC output and the DC load exceeds 10 feet, use the Power Cable Guide below to minimize the voltage drop across the wire distance.
Alarm Connections Seven alarm relays (and 9 alarm LEDs) are included as a standard feature of the A36D. The included alarms are Low DC Current, Low DC Voltage, High DC Voltage, High Voltage Shutdown, AC Failure, Open DC Protection, and Summary alarm.
S2A-198 Relay Information Load Resistive Load (P.F. = 1) Relay Function Logic Contact Material Ag (Au clad) Maximum Allowed Current AC Power Fail De-Energize on Fail 0.5 A at 125 VAC Summary De-Energize on Fail Max. Operating Voltage and 0.6 A at 110 VDC High DC Voltage Current Energize on Fail...
2.4.2 Understanding the Alarms HIGH VOLTAGE SHUTDOWN ALARM will trigger and the red “HIGH VOLTAGE SHUTDOWN” LED will turn on if the output DC voltage of the charger rises above the alarm threshold for longer than 20 seconds and there is load on the charger.
External Temperature Compensation (Option 11W/11Y) The natural voltage of a battery changes as a function of temperature change. As the battery temperature rises, the effective voltage of the battery decreases. Without Temperature Compensation, the battery charger will always produce a set constant output voltage. As the battery temperature increases, this constant voltage will then induce a higher output current from the charger.
Load Sharing All A36D chargers include the Load Sharing feature. Load sharing allows the user to parallel with any identical A36D to share a DC load and therefore reduce the strain on each charger. When connected, identical A36D chargers are forced to share the load within ±5% for individual unit outputs greater than 10% of the rated output. MUST Chargers to be paralleled be the same output (voltage and current).
DNP 3.0 / Modbus SCADA Interface (Option 21P/21Q) The optional DNP 3.0 / Modbus SCADA Interface Communication Board, allows the user to remotely connect to the A36D battery charger. The board is equipped with four methods of communication; DNP 3.0, Modbus ASCII, Modbus RTU and Modbus TCP.
Operation Starting the A36D All equipment is shipped from the factory fully checked and adjusted based on the model number. Do not make any adjustments unless the equipment has been powered-up and the settings have been determined to be incorrect. Factory Settings The factory settings of the A36D are based on the model number.
3.1.2 Starting/Stopping the A36D Once proper connections are established, energize the power supply by turning on the charger’s AC breaker (the DC breaker should be off). This will charge the capacitors inside the charger and eliminate heavy arcing when the batteries are connected.
Selecting the Charging Mode The A36D has two different settings for DC output voltage, Float Mode and Equalize Mode. Float charging mode is used for all normal battery charging needs. Equalize Mode is used when it is necessary to Equalize (or balance) the level of charge across all cells present in the battery.
3.4.1 Settings Menu In the Settings Menu, the user can access and change various parameters used by the A36D. To access the Settings Menu, press the MENU button, select “Settings Menu”, and press the ENTER button. Once in the Settings Menu, the user can navigate the menus with the up and down arrows. To enter a submenu, use the ENTER button.
Page 25
Alarm Thresholds The Alarm Thresholds setting allows the user to determine the current or voltage value at which an alarm trigger. The threshold can be changed for Low Current Alarm, Low Current Alarm Reset, Overload Alarm, Low Voltage Alarm, Low Voltage Alarm Reset, End of Discharge Alarm, High Voltage Alarm, and High Voltage Shutdown Alarm. <...
Page 26
Equalize Timer Hours The Equalize timer hours setting changes the amount of time that the charger remains in the Equalize charging cycle once activated. When an Equalize cycle is started the charger will remain in Equalize Mode until the time selected by this setting has passed.
Page 27
Communications Settings The communication settings menu changes depending on the type of communication protocol used in the charger. For details on connection instructions as well as operation instructions, refer to the SCADA Interface instruction manual included with the charger. Chargers with DNP 3.0 Communication Protocol (Option 21P) Setting Default Setting (Selection) DNP Node Address...
Saving Settings At any point, the user can press the BACK button from the main Settings Menu to exit the Settings Menu. When the back button is pressed (on the main Settings Menu), the user is prompted if they would like to “Exit and Save Settings?”...
Output Voltage Adjustments The output voltage of the A36D charger is set to a default value, but should be adjusted to meet the battery manufacturer recommendations. To adjust the Float and Equalize output voltage, refer to Section 3.4.1.1. Adjustments are recommended to be made with no connections on the DC output terminals of the charger, but can also be done with the battery connected.
Frequently Asked Questions : How can I tell what options are included on my A36D charger? : Every charger will have a dedicated manual cover sheet included with the charger manual, which lists all the options included. If the manual that shipped with the charger is no longer available, call La Marche and provide the five-digit accessory code at the end of the model number.
Service All work inside the A36D charger should be performed by qualified personnel. La Marche is not responsible for any damages caused by an unqualified technician. Before working inside the A36D, ensure the AC power is off at the main breaker box and the battery has been removed from the charger’s DC output terminals, either by removing the battery cables or exercising the battery disconnect.
Troubleshooting Procedure Troubleshooting should be performed only by trained service personnel or experienced electricians. Before setting up any complicated testing or making any conclusions, inspect the charger using the guide below. Check the following: 1. Check DC output cables, connections, battery type, and number of cells against the charger’s rating. 2.
Troubleshooting Chart Isolate from all power sources prior to performing any interior verifications or part replacements. Symptom Possible Cause Action Measure AC voltage and verify against Incorrect AC Input Voltage charger nameplate. Verify tap settings using charger AC Input Taps on Power Transformer schematic or input table found on Set Incorrectly charger.
Incorrect, Damaged or Loose Visually inspect and verify all internal Cable/Harness Connections wiring using charger schematic. Measure battery voltage and verify Incorrect Battery Connected against charger nameplate. Incorrect Float/Equalize Voltage Refer to Section 3.4.1.1 for output Settings adjustment instructions. High Output Voltage or Current Contact La Marche Service Defective S2A-341S Control Board Department for further...
5.3.3 Troubleshooting and Replacing Power Silicon Diodes/Modules 1. On the ohmmeter, set the switches on “ohms”, “DC”, and “Rx100” scale and isolate one end of the diode by disconnecting the wires attached to the nipple (or pigtail) end of the diode (only one end of the diode must be disconnected).
Appendix A: A36D Specifications ELECTRICAL 120, 208, 240, 380, or 480VAC AC Input Voltage range +10% / -12% Frequency Range 50Hz or 60Hz ± 5% 10 - 400 ADC DC Output 12, 24, or 48VDC Single Phase - 30mV RMS, with or without battery Output Filtering ±...
Appendix E: Manufacturer’s Warranty F THE INVOICE SHOWS THAT YOU HAVE PURCHASED THE XTENDED ARTS ARRANTY OR IF YOU ARE INTERESTED ’ IN PURCHASING THE XTENDED ARTS ARRANTY SEE THE ANUFACTURER XTENDED ARTS ARRANTY All La Marche Manufacturing Co. equipment has been thoroughly tested and found to be in proper operating condition upon shipment from the factory and is warranted to be free from any defect in workmanship and material that may develop within one year from date of purchase.
Appendix F: Manufacturer’s Extended Parts Warranty HIS IS YOUR ARRANTY IF YOU HAVE PURCHASED THE XTENDED ARTS ARRANTY AS SHOWN ON OUR INVOICE TO YOU OR IF YOU PURCHASE THE XTENDED ARTS ARRANTY ANYTIME DURING THE FIRST MONTHS AFTER THE DATE OF OUR INVOICE All La Marche Manufacturing Co.