La Marche Manufacturing Company www.lamarchemfg.com ODUPS Outdoor UPS Installation and Operation Manual This manual is subject to change without notice. You may obtain the newest version of the manual at www.lamarchemfg.com 106 Bradrock Dr. Des Plaines, IL 60018-1967 CPN 144266...
Important Safety Instructions Before using this equipment read all manuals and other documents related to this UPS and other equipment connected to this UPS. SAVE THESE INSTRUCTIONS – This manual contains important safety and operating instructions for the CUPS. If a replacement copy of a manual is needed, it can be found at www.lamarchemfg.com. Electrical Safety WARNING: Hazardous Voltages are present at the input of power systems.
UPS Location • Allow at least 6 inches of free air on all vented surfaces for proper cooling • Allow sufficient clearance to open the front panel for servicing. • Do not operate this UPS in a closed-in area or restrict ventilation in any way. •...
Table of Contents Important Safety Instructions ........................ii Electrical Safety .................................ii Mechanical Safety ................................ii Battery Safety ..................................ii UPS Location ..................................iii Check for Damages................................iii Returns for Service ................................iii Handling ................................... iii Installation and Setup ........................6 UPS Model ................................6 PTS Module (Optional) ............................
Page 5
Understanding the Model Number The ODUPS model number is coded to describe the options that are included. Find the model number on the nomenclature nameplate of the UPS. Follow the chart to determine the configuration of your UPS.
Installation and Setup NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use. UPS Model The UPS module provides utility power to load when a line is qualified. And an automatic voltage regulator (AVR) is embedded to provide stable power to the load.
13. PTS Control Connector This connector provides power to control the PTS unit. 14. Battery Breaker This over-current protection is used as an on/off switch for the battery power. It must be switched on for proper UPS operation. 15. Battery Voltage Test Points The test points allow you to measure battery voltage.
7. UPS Input Connector This “UPS IN” power cord is connected to AC input connector or terminal blocks on UPS. 8. UPS Output Connector This “UPS OUT” power cord is connected to the AC output connector or terminal blocks on UPS. 9.
Wiring the UPS WARNING: All electrical wiring must be performed by qualified electrician or trained personnel. Make sure the line power is off. Switch off all input and output circuit breakers on the UPS unit before making any electrical connections. 1.5.1 Wiring the PTS to the UPS Wire the PTS to the UPS according to the schematic shown in Figure 5.
1.5.3 Wiring External Batteries Unit supports 48Vdc battery. Connect all battery packs as below chart. It’s suggested to connect at least 100Ah capacity battery. Figure 7: Battery Connection Chart...
Operation To power up the UPS, commissioning to make sure batteries are fully charged and line power is qualified. Switch on UPS in Line mode 1. Switch on battery circuit breaker. All LEDs will be on and LCD will display Startup page, and fan will be on.
Page 12
Function Keys Function Key Description Back to previous menu/page SCROLL Jump to next page or next selection ENTER Enter submenu or confirm selection Default page After power on, Startup page will display. It will automatically switch to default page after 6 seconds. Default page Explanation Date and time...
Menu Page After pressing ENTER button in default page, it will enter menu page. ► 1. Status ▼ Menu Page 2. Event log 3. Setting 4. Control Scroll 5. Help ▲ Figure 11: Menu Page Press SCROLL button to browse all 5 submenus below. Menu Screen Explanation Status...
The total time duration the unit has been in boost mode 16. BstEV: xxxxx ▼ since the latest reset. 17. BstTM: xxxx.xH The status of the dry contact C1 and C2. 18. C1:Off C2:Off The status of the dry contact C3 and C4. 19.
Page 15
Ext Fan Failed Door Unlocked AVR Feature: Enable or disable Buck and Boost function. Factory default setting is “disable”. Line Qualify: Set AC recovery time after the line is qualified. It’s to make sure the line is stable. The selectable options are: 3 seconds, 10 seconds or 30 seconds.
Control Menu Press SCROLL button to switch desired option in Control menu and press ENTER button to confirm new option. Pressing ESC button will return to default page. (To enter in Setting menu use default password: 11111) Control page Explanation Starts the Self-Test.
Trouble Shooting For PTS Module Problem Possible Cause Remedy No output available from AC circuit breaker may be Close the external AC input breaker. External PTS. OPEN. Line AC power is not available. Check if utility is available with the AC voltmeter and contact Utility Company.
For UPS Module Problem Possible Cause Remedy No output. AC input and output circuit Turn on input and output circuit breakers are off. breakers. No line power input. Turn on AC input breaker. Red LED is lit solid on front panel Read fault event under Event Log in LCD indicating fault.
Specifications Line Mode Specifications Rated Power 2000VA/1600W Power factor Nominal battery voltage 48Vdc Utility Voltage Waveform Sinewave (utility or generator) Nominal Input Voltage 120Vac or 230VAC AVR function Enable/ Disable Utility voltage range 88 - 152 VAC or 176 - 300VAC user programmable. Defaults set @ 100 - 130VAC or 200 - 260VAC Nominal Input Frequency 50Hz / 60Hz...
Output Power 2000VA/1600W 1500VA/1200W Power limitation 1250VA/1000W 80 (120Vac model) Temperature(°C) 70 (230/240Vac model) Charger Mode Specifications Appropriate battery type Charging Current 2Amp/ 4Amp/ 6Amp/ 8Amp/10Amp adjustable Charger Current(A) Max charger current limitation Temperature °C Charging Algorithm 3-Step Charger Operating - 20 °C to 50 °C Temperature Range General Specification...
Appendix A: Manufacture Warranty All La Marche Manufacturing Co. equipment has been thoroughly tested and found to be in proper operating condition upon shipment from the factory and is warranted to be free from any defect in workmanship and material that may develop within two (2) years from date of purchase. Any part or parts of the equipment (except fuses, DC connectors, and other wear-related items) that prove defective within a two (2) years period shall be replaced without charge providing such defect, in our opinion, is due to faulty material or workmanship and not caused by tampering, abuse, misapplication or improper...