POWER LIMITER PMM-02
DESCRIPTION
The PMM-02 power limiter auto-
matically isolates supply voltage from the
controlled power loads when they over-
load the set power threshold. The power
threshold can be set smoothly from 0.1
to 3 kW with a potentiometer. The power
threshold trip-on delay of the relay can be
set smoothly from 10 to 90 s.
FEATURES
● Overload protection with a power
threshold setting.
● Electrical system overcurrent protec-
tion.
● Power supply indicator.
● Power overload indicator.
● Stepless trip-off delay setting.
● Wide power load control range.
● Resilient to transient power loads
above the set power threshold.
● Single-module enclosure.
● For installation on a DIN rail.
The device is designed for a
single-phase installation and
must be installed in accord-
ance with standards valid in a
CAUTION
particular country. Installation,
connection and control should be carried
out by a qualified electrician staff, who act
in accordance with the instruction manual
and the device functions. In case of cas-
ing dismantling, the guarantee is lost and
an electric shock may occur. Before instal-
lation make sure the connection cables
are not under voltage. The cruciform head
screwdriver 3,5 mm should be used to in-
stall the device. Improper transport, stor-
age, and use of the device influence its
wrong functioning. It is not advisable to in-
stall the device in the following cases: if any
device part is missing or the device is dam-
aged or deformed. In case of improper func-
tioning of the device contact the producer.
Do not dispose of this device with
other waste! In order to avoid
harmful effects on the environment
and human health, the used device
should be stored in designated
areas. For this purpose, you can
dispose of household waste free
of charge and in any quantity to
a collection point set up, as well
as to the shop when you buy new
equipment.
ZAMEL Sp. z o.o.
ul. Zielona 27, 43-200 Pszczyna, Poland
Tel. +48 32 210 46 65, Fax +48 32 210 80 04
www.zamel.com, e-mail: export@zamel.pl
TECHNICAL DATA
Power input terminals: L; N
Rated supply voltage: 230 V AC
Supply voltage tolerance: -15 ÷ +10 %
Rated mains frequency: 50 / 60 Hz
Rated current load: 26 mA
Power supply indication: green LED
Power threshold setting: 0.1 ÷ 3 kW (with a rotary potentiometer)
Trip-on delay setting: 10 ÷ 90 s (with a rotary potentiometer)
Power overload indication: red LED
Transmitter contact ratings: 1NO 16 A / 250 V AC1 4,000 VA
Wiring terminals: 4
Operating temperature: -20 to +60°C
Installation orientation: any
Enclosure installation type: DIN rail
Protection grade: IP20
Overvoltage category: II
APPEARANCE
Input (supply) terminals
Power supply indicator
Power overload indicator
Time off delay adjustment
Power threshold adjustment
Output (load) terminals
PMM-02
Power off delay: ca. 250 ms
Wiring size: 0.2 ÷ 2.50 mm
2
Pollution class: 2
Dimensions: single module 90 × 17.5 × 66 mm
Weight: 0.077 kg
USER'S MANUAL
plik: pmm-02_instr_ext_gb | modyfikacja: 02.07.2019

Advertisement

loading

Summary of Contents for Zamel EXTA PMM-02

  • Page 1 POWER LIMITER PMM-02 USER’S MANUAL ZAMEL Sp. z o.o. ul. Zielona 27, 43-200 Pszczyna, Poland Tel. +48 32 210 46 65, Fax +48 32 210 80 04 www.zamel.com, e-mail: export@zamel.pl DESCRIPTION TECHNICAL DATA PMM-02 The PMM-02 power limiter auto- matically isolates supply voltage from the Power input terminals: L;...
  • Page 2 4. ZAMEL will review complaints in accordance with existing regulations.; 5. The way a complaint is settled, e.g. replacement of the product, repair or refund, is left to the discretion of ZAMEL. 6. Guarantee does not exclude, does not limit, nor does it suspend the rights of the PURCHASER resulting from the discrepancy be- tween the goods and the contract.