End Of Operational Life (Eol); Specification - S&S Northern MERLIN GDP2X Installation & Operation Manual

Safe area gas detector-x controller
Hide thumbs Also See for MERLIN GDP2X:
Table of Contents

Advertisement

Installation & Operation Manual
Access to the interior of the detector, when carrying out any work, must be conducted by a competent person!
Before carrying out any work ensure local regulations and site procedures are followed!
Always give at least five (5) minutes between testing the same unit or when gas has fully dispersed!
Do not conduct calibration of sensors in conditions outside of any recommended ranges!
To recalibrate a detector, the following procedure and gases must be used!
Calibrated gases must be mixed in accordance with recognised standards such as EN 6142.
If a gas sensor is exposed to a concentration significantly above the measuring range, it should be
recalibrated as soon as possible afterwards!
Contact S&S Northern for more information.

End of Operational Life (EOL)

The typical life of a gas detector depends on its application and intended target gas, in addition, the operational life
can be prolonged if the system and equipment is installed and maintained in accordance the instructions stated within
this manual.
At the end of its predicted operational life – the detector will display an 'End of Life' screen. This
message indicates that the detector has reached its expected operational lifecycle and no gas
levels will be displayed. You must contact your supplier immediately for replacement.
The EOL is approximate from the first five (5) hours of continuous power!
The EOL will depend on the type of gas your detector is targeting and may vary depending on its application
and environmental conditions such as the frequency of exposure to the target gas, poisons or inhibitors!

Specification

General
Product:
Use:
Indicators (2.8" Touch Screen)
Screen Brightness
Mounting
Electrical
Max. Power Consumption
Power Voltage Input Range
Gas Valve Output Range
I/Os
BMS Terminal
Relay(s)
Terminal Wire ratings
Fuse
Construction
Dimensions (H x W x D)
Unit Weight (Approx.)
Housing Material
Environmental
Ingress Protection
Storage Conditions
Operating Conditions
Compliance
CE / UKCA
GDP2X - IOM Iss: 7 03-21
GDP2X: Gas Detection Control Panel
Indoor, Safe Areas (not to be used in potentially explosive atmospheres)
Main Zone Status. ID. Gas Type. Concentration Level. Measured Value. End of Life. Fault. Service.
Adjustable 0-100%
Wall Mounting
20W Max (Full Load)
100-240vac
100-240vac
2x 24vdc Outputs (Detector / Strobe or Sounder)
3x Open/Close Switches (EM Stop / Heat Sensor / Fire Panel)
Volt Free (Normally Closed / Common / Normally Open) 3A Max
2x 24vdc 8A (Latching) Configurable Normally open or Normally Closed (Switch)
Copper 18AWG (0.75mm2) Min. 25 x screw terminals.
3.15A
140 x 190 x 62 mm/ 5.51 x 7.48 x 2.44"
0.72kg / 25.4oz
Polylac - PA765
IP65 (Pre-installation)
Dry. Cool. Flat
-10 ~ 50°C / 14 ~ 122°F 30 ~ 80% rh
EN 61326-1 / BS EN IEC 61010-1
Merlin GDP2X