VES ecovent EVC073-1 Operation & Maintenance Manual page 15

Counterflow heat recovery units

Advertisement

www.ves.co.uk
ecovent Heat Recovery Units
Standard Wiring
5
Con nued
& Fan Installa on
Standard wiring arrangement
Terminal Box
Valve Actuator Terminals
23
Fig.
1
2
3
4
5
6
7
Customer
Valve
N/A
Supply
Air
Sensor
SGS65... Valve Actuator
Warning
To isolate from the main power supply, the system must incorporate a device which disconnects
all the phase conductors
Inlet Eye
an alignment details
F
24
Fig.
Impeller
Prior to star ng the unit it is important to ensure that the fans are free running, and should
any components have moved during transit take care to ensure they are realigned to allow
correct opera on/rota on. A trial spin by hand should indicate if the fan is rubbing. To align,
loosen the fan inlet eye fixings and adjust the pos on so that the gap between inlet and fan are
Important
equidistant. Ensure the fan runs freely in the new posi on, re ghten the fixings, holding the
24
inlet eye in pos on see figure
above. The same should be applied to any wiring looms
which may have become unfastened; ensure that loose wiring is securely stowed away from
any moving components.
The impellers on EVC0/EVCB0 and EVCB1 units are not adjustable; any alignment issues should
be reported to VES.
15