Heating coil ................................16 Trasmission belt of the rotor ..........................16 Seals ..................................16 Overall summary service intervals ........................16 Inspection ............................16 Storage ................................. 17 Unpacking ................................17 Lifting and handling .............................. 18 AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
Page 3
HOW TO CONNECT THE POWER SUPPLY ......................24 Electrical wiring: ..........................25 Description of adjustment control....................26 Symbol Display Description ..........................26 Description Parameters ............................27 Alarm menu ................................31 Description connection external humidistat ......................33 AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
The monitoring operations and maintenance must be performed in strict accordance with the instructions. Not attempt to repair or maintain the dehumidifier and always contact TFT for any repairs or maintenance. Do not modify the unit without written authorization of TFT.
Rivolgersi sempre a TFT per l’assistenza e le riparazioni. TFT liability shall not include defects caused by inadequate maintenance or repairs or by incorrect installation by the Buyer, or else by alterations made without TFT written approval.
Operation, maintenance and/or repair of the electrical panel must only be carry out by personnel trained and qualified to work with electrical devices. GROUNDING This symbol identifies the grounding. RECOVERABLE/RECYCLABLE MATERIAL AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
Process air is dried in the rotor between -30°C and +40°C, the re generation air is beaten by an internal coil up to about 100°C. AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
The fan control process by default is set at a fixed speed, but it can be configured with variable speed and controller by an external signal, or by a pressure sensor. AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
After the dehumidifier has been switched off, wait at least for 15 minutes before going inside in order to allow the dehumidifier to cool. AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
Operators engaged in the installation and maintenance of the machine must wear the appropriate personal protective equipment required by law and listed below. Protective footwear. Eye protection. Protective gloves. Respiratory protection. Hearing protection. AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
You must install the manual dampers on the flows of the process and reactivation air, to maintain the functional efficiency of the unit The total pressure drop of the process and reactivation air ducts should not be higher than the available pressure of the fans. AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
In this case, it’s not necessary the addiction of aspiration channels for the process air; the installation of a protective grille is only required. The dry air produced must be ducted for the distribution inside the dehumidified room. AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
(pre-cooling or pre-heating). The dry air produced can be sent to dehumidified environment or to a system of post-treatment. A control damper can be installed to regulate the flow of dry air. Electrical connections In this regard, see the attached wiring diagrams. AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
Pagina 14 di 35 First start-up Preliminary checks CAUTION! The installation and the first start-up of the unit must be TFT. CAUTION! The power supply is constantly present in the general switch of the unit. Risk of electric shock. For the first start-up, perform the following checks:...
Check once a year the bearings and the surface of the rotor. Electric engines The electric engines are equipped with ball bearings. Maintenance operations of the bearings aren’t necessary. Check the engine and any noise once a year. AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
Every 12 months √ √ NOTE! Always contact TFT for service and repairs. Operational failures can occur if machine maintenance is carried out so insufficient, inadequate or incorrect. NOTE! The inspection of installation/start-up performed by TFT is required to validate the full warranty.
(wood, cardboard, nylon etc.).. Packaging materials should be stored separately and delivered for disposal or possible recycling in order to reduce any impact on the environment. AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
The unit must always be kept horizontal during these operations. CAUTION! The dehumidifier weights over 100kg. To avoid personal injury or unit, always use approved equipment. AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
(*) Sound pressure level calculated in free field, 10 meters from the unit, directional factor Q = 2 according to ISO 9614 Note: For performance to different conditions - contact TFT srl for selection Dimensions PA = Inlet process air - DA = Outlet dry air - WA = Outlet wet air - RA = Inlet reactivation air AD1100TE-STD.EN-00 - Subject to change without notice...
Motor a gear 230V 1Ph 50Hz, 3g/min. grease for low temperature belt rotor V-Sezione trapezoidale tensioning device Process fan DKHR250FSB0714FFIE Reactivation fan R2E225-RA92-09 Heaters stage Elettrica (PTC) 3300W rotor HSG0811 Air Filter process Air filter reactivation G4-GLS400 AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
310 x 540 x 48 290 x 285 x 48 Pressure drop, clean filter Pressure drop, dirty filter HEATER, REACTIVATION AIR Power Type Voltage Number of elements 2 x 3300W Type of elements Heaters PTC AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
1% according to EN 60204. If those tolerances should not be respected, please contact our technical department. The electrical data can change without notice. It is therefore necessary to refer always to the wiring diagram supplied with the unit. AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
To supply electrical power to units AD… remove the top panel; use the special cable in the rear or side panel and connect the power cord to the terminal block in the control cabinet. After connecting, close the top panel carefully. AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
Gas Version (CF02=6, 7): Minimum flame burner or opening valve with regulation 3P Electric version (CF02=4): Indication reactivation resistances with PWM control Indication reactivation fan (flashing, it indicates the post-cooling reactivation) Indication process fan AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
Indication value °C temperature post-treatment °C Only vis. Y_U1 Indication value % control signal of pre-treatment valve Only vis. Y_U2 Indication value % control signal of post-treatment valve Only vis. Software Version 1.5.0 (FW 412.20) AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
Page 28
ON = Post-cooling in temperature rC05 Set-point temperature of the post- cooling reactivation °C 40,0 rC06 Setting time of post- cooling reactivation rC07 Setting time of maximum opening of valve/motor controlling 3 points for burner AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
Page 29
0 = from AIL4 analo input (Input 4…20mA) 1 = from Dewpoint Value calculated (with probe RH% + T) 2 = from absolute humidity value calculated (with probe RH% + T) AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
Page 30
On = The unit stops completely to every anomaly and this signals the general alarm Software Version 1.5.0 (FW 412.20) (*) In order for the change to take effect you need to boot the instrument, remove power, wait a few seconds and turn it. AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
It has been enabled in the control of reactivation mixed Steam/Water + Electrical and control of Post-cooled / Reheating simultaneously. Condition impermissible (CF02> 7 and CF03 and CF14 ≠ 0 = OFF). Software Version 1.5.0 (FW 412.20) AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
Page 32
Pagina 32 di 35 RESET alarms, press the ESC key for about 3 seconds on the terminal display LED, or put the AUTO-0-MAN "0" and bring it back to its previous position. AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
If it takes action only one contact control / command, in this configuration they must be closed both control steps (step 1 and step 2). AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
Page 34
Pagina 34 di 35 Notes: AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...
Page 35
Pagina 35 di 35 By TECNOFRIGO TUSCANY srl Via J.F.Kennedy, 25/27/29 56020 Capanne Z.Ind. Fontanelle (Pisa) Tel. +39 0571467351 Fax +39 0571469217 info@tecnofrigo.it – info@tftdryair.com e-mail: WWW.TFTDRYAIR.COM WWW.TECNOFRIGO.IT AD1100TE-STD.EN-00 - Subject to change without notice TFT DryAir...