Greystone Energy Systems UP Series Installation Instructions Manual

Ultra low pressure transducer

Advertisement

Quick Links

BEFORE INSTALLATION

Read these instructions carefully before installing and commissioning the UP Pressure Transducer. Failure
to follow these instructions may result in product damage. Do not use in an explosive or hazardous
environment, with combustible or flammable gases, as a safety or emergency stop device or in any other
application where failure of the product could result in personal injury. Take electrostatic discharge
precautions during installation and do not exceed the device ratings.

MOUNTING

The Ultra Low Pressure Transducer mounts using the two holes on the base of the unit. See Figure 1. Leave
enough space around the unit to connect the pressure tubing and avoid locations with severe vibrations,
excessive moisture or rapid temperature changes. It should be mounted on a vertical surface with the
pressure ports on the bottom and the cable entrance on the left.
The enclosure has a standard ½" conduit opening and may be installed with either conduit and a conduit
coupler or a cable gland type fitting.
The enclosure has a hinged cover with a latch. Open the cover by pulling slightly on the latch on the
bottom of the enclosure. At the same time pulling on the cover, as illustrated in Figure 2.
A 1/2" NPT threaded connection hole is provided in the bottom of the enclosure. Screw the EMT connector
or cable gland connector in until tight. See Figure 3. It is recommended that weatherproof conduit or
cable gland fittings be used. The F style enclosure includes 1/2" NPT
to M16 thread adapter and cable gland fitting.
Make wiring connections as per the "Wiring" illustrations on Page 2.
Swing door closed until securely latched. For added security, 2
screws are provided that may be installed in the integrated screw
tabs. See Figure 4.
Figure 2
IN-GE-UPXXX-01
07/20
Figure 3
EMT Connector
Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com
Ultra Low Pressure Transducer

INTRODUCTION

The Ultra Low Pressure Transducer is used to measure
differential pressure up to 1"wc or 250 Pa. It combines
precision high sensitivity silicon sensing capabilities and
the latest ASIC technology to substantially reduce offset
errors due to changes in temperature, stability to warm-
up, long term instability and position sensitivity. It is ideal
for monitoring pressure for air or other clean inert gas.
It features bi-directional pressure measurement, an on-
board auto-zero function, a backlight LCD to display the
pressure value and an alarm relay with variable trip points.
The device is field-configurable via the local menu.
Thread adapter and
cable gland fitting
UP Series - Installation Instructions
Figure 1
Figure 4
Page 1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the UP Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Greystone Energy Systems UP Series

  • Page 1 See Figure 4. Figure 4 Figure 2 Figure 3 Thread adapter and cable gland fitting EMT Connector IN-GE-UPXXX-01 07/20 Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com Page 1...
  • Page 2 High RELAY Controller SHIELD ZERO Figure 7 Figure 9 CURRENT MENU DOWN ZERO/UP Remote Zero ZERO Digital Input VOLTAGE Controller IN-GE-UPXXX-01 07/20 Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com Page 2...
  • Page 3 The default pressure range is bi (bidirectional ± max). Use <UP> or <DOWN> to toggle to uni (unidirectional 0-max). Applicable units symbol is displayed. MENU IN-GE-UPXXX-01 07/20 Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com Page 3...
  • Page 4 The alarm test defaults to OFF. It can be set to On using <UP> or <DOWN>. This forces the relay to activate. <MENU> Press to advance to next menu item IN-GE-UPXXX-01 07/20 Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com Page 4...
  • Page 5 For an alarm condition to be reset the pressure value must return to a non-alarm value for more than the alarm off delay time. When the alarm condition is set the relay output will activate. IN-GE-UPXXX-01 07/20 Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com Page 5...
  • Page 6 Approvals ........CE, RoHS Country of Origin ....Canada DIMENSIONS 116.5 mm 4.585" 99.7 mm 112.5 mm 4.43" 3.93" 53.7 mm 2.11" Page 6 IN-GE-UPXXX-01 07/20 Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com...