Electrical Specifications & Wiring - ECR Argo ARH-1 Installation Manual And Operating Instructions

Hydro-air zoning controls
Table of Contents

Advertisement

ELECTRICAL SPECIFICATIONS & WIRING
ELECTRICAL SHOCK HAZARD! Disconnect power be-
fore installing or servicing. Can cause severe personal
injury, death, or substantial property damage if ignored.
All primary wiring must be 14 AWG minimum. Torque terminal
screws 6 to 7 inch pounds.
U.S.A. - National Electric Code and any other national, state, or
local code requirements. Wiring must be N.E.C. Class 1.
CANADA - C.S.A. C22.1 Canadian Electrical Code Part 1 and
any other national, provincial, or local code requirements. Wiring
must be C.S.A. C22.1 C.E.C. Part 1.
Argo
Argo Part
Model
Number
Number
ARH-1
ARH-2
ARH-3
!
GENERAL WIRING NOTICE
Electrical Specifications
Power Input
24VAC/60Hz
Z181
24VAC/60Hz
Z179
120VAC/60Hz
Circulator Power
24VAC/60Hz
Z180
120VAC/60Hz
Circulator Power
WARNING
Thermostat
Current
for
.085A
for
8
!
Supplied Aquastat
3/8" to 3-4" Strap on
Bi-Metal
(ON at 118°F + 5%)
(OFF at 95°F + 5%)