Ansul 100/30 Operation And Maintenance Manual
Ansul 100/30 Operation And Maintenance Manual

Ansul 100/30 Operation And Maintenance Manual

Fire suppression/securing systems

Advertisement

ANSUL
®
FIRE SUPPRESSION/SECURING SYSTEMS
OPERATION AND MAINTENANCE
MANUAL
Part No. 63390-01

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 100/30 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Ansul 100/30

  • Page 1 ANSUL ® FIRE SUPPRESSION/SECURING SYSTEMS OPERATION AND MAINTENANCE MANUAL Part No. 63390-01...
  • Page 3 ANSUL FIRE SUPPRESSING/SECURING SYSTEM MODEL:    100/30 TYCO FIRE PROTECTION PRODUCTS, MARINETTE, WISCONSIN 54143-2542...
  • Page 5 This manual is intended for use with ANSUL Fire Suppressing/ ® Securing Systems. Those who operate, recharge, inspect, or maintain these systems should read this entire manual. Specific sections will be of particu- lar interest, depending upon oneʼs responsibilities. The AFFF (Aqueous Film-Forming Foam) System is designed for use on Class A and Class B fires only.
  • Page 7: Table Of Contents

    TABLE OF CONTENTS ANSUL Fire Suppression/Securing Systems Operation and Maintenance – Model 100/30 2012-MAR-22 REV. 01        PAGE i SECTION PAGE/FORM NO./PART NO. ________ _______________________ Assembly 1 – 2 Operation Recharge 4 – 7 AFFF Recharge Guide Inspection Maintenance 10 – 11 Pressure Regulator Test 12 –...
  • Page 8: Operation And Maintenance - Model 100/30

    EXPLANATION OF SAFETY ALERTS ANSUL Fire Suppression/Securing Systems PAGE ii REV. 01        2012-MAR-22 Operation and Maintenance – Model 100/30 Explanation of safety alerts: DANGER Indicates a hazardous situation in which a person will experience serious personal injury or death if the situation is not avoided.
  • Page 9: 2012-Mar-22

    Remove fill cap and place funnel in opening. Foam) 6% Concentrate into tank. b. Fill tank to rated capacity with only the ANSUL dry chemi- b2. 3% SOLUTION: Place funnel in fill opening and pour 1 gal cal specified on the nameplate. ANSUL dry chemical (3.8 L) of only ANSULITE AFFF 3% Concentrate into tank.
  • Page 10: Assembly

    ASSEMBLY ANSUL Fire Suppression/Securing Systems PAGE 2 REV. 01        2012-MAR-22 Operation and Maintenance – Model 100/30 f. Secure fill cap and hand tighten. (Make certain gasket is in place before reinstalling fill cap.) NOTICE If the fill cap is an indicator model, be...
  • Page 11: Operation

    OPERATION ANSUL Fire Suppression/Securing Systems Operation and Maintenance – Model 100/30 2012-MAR-22 REV. 01        PAGE 3 To operate the ANSUL system: 1. Pull the Quick-Opening operating lever on nitrogen cylinder. 2. Pull ring pin and pull all hose from support.
  • Page 12: Recharge

    Remove fill cap and place funnel in opening. b. Fill tank to rated capacity with only the ANSUL dry chemi- cal specified on the nameplate. ANSUL dry chemical FIGURE 2 should not be more than 6 in.
  • Page 13 RECHARGE ANSUL Fire Suppression/Securing Systems Operation and Maintenance – Model 100/30 2012-MAR-22 REV. 01        PAGE 5 f. Secure fill cap and hand tighten. d2. 3% SOLUTION: Place funnel in fill opening and pour in measured amount of only ANSULITE AFFF (Aqueous...
  • Page 14 ANSUL Fire Suppression/Securing Systems PAGE 6 REV. 01        2012-MAR-22 Operation and Maintenance – Model 100/30 b. Follow with a reverse loop. This is accomplished by twist- e. Thread safety plug fully into cylinder valve outlet. ing the hose so that it passed behind the loop being formed.
  • Page 15 RECHARGE ANSUL Fire Suppression/Securing Systems Operation and Maintenance – Model 100/30 2012-MAR-22 REV. 01        PAGE 7 c. Insert anchor stud through valve body and actuator pivot member. CAUTION The Quick-Opening lever may be moved slightly forward, approximately 1/4 inch (6.4 mm), to permit installation of the anchor stud.
  • Page 16: Afff Recharge Guide

    ANSULITE AFFF RECHARGE GUIDE ANSUL Fire Suppression/Securing Systems PAGE 8 REV. 01        2012-MAR-22 Operation and Maintenance – Model 100/30 DEPTH OF SOLUTION AFFF CONCENTRATE REQUIRED (mm) ____ 34.00 (863) (0.0) 30.75 (781) (0.8) (0.4) 27.50 (699) (1.5) (0.8) 24.25 (616) (2.3) (1.1) 21.00 (533) (1.5)
  • Page 17: Inspection

    Remove fill cap from tank. b. Check that tank is filled with free-flowing ANSUL dry chem- ical to a level of not more than 6 in. (152 mm) from the bot- tom of the fill opening.
  • Page 18: Maintenance

    Make certain tank is filled with only free-flowing ANSUL dry 6. Pull ring pins and operate BLUE Hose Clean-Out Valves to chemical to a level of not more than 6 inches (152 mm) check for free movement.
  • Page 19 MAINTENANCE ANSUL Fire Suppression/Securing Systems Operation and Maintenance – Model 100/30 2012-MAR-22 REV. 01        PAGE 11 8. Return dry chemical tank valve handles to the operating posi- tion: BLUE Hose Clean-Out Valve....Closed BLACK Dry Chemical Valve.
  • Page 20 High pressure nitrogen could cause personal injury or equipment HIGH (PART NO. 7730) RELIEF HIGH PRESSURE damage if proper test kit is not used. Use only ANSUL regulator (PART NO. 78704) PRESSURE INLETS test kit (Part No. 78689) which includes a safety relief valve. INLET The ANSUL Regulator Test Kit (Part No.
  • Page 21 Note: Wheeled unit is shown as an example. 004154 004119 3. For the 100/30 unit, disconnect hoses at tee downstream of regulator on the low pressure side. (Note: Each hose has a swivel at one end only; remove hose at swivel end first.) Plug TO FOAM one side of tee.
  • Page 22 ANSUL Fire Suppression/Securing Systems PAGE 14 REV. 01        2012-MAR-22 Operation and Maintenance – Model 100/30 8. Dead set tolerance for regulator is 195 psi – 215 psi (13.44 bar – 14.82 bar). Minimum flow is 140 psi (9.65 bar).
  • Page 23 PRESSURE REGULATOR TEST ANSUL Fire Suppression/Securing Systems Operation and Maintenance – Model 100/30 2012-MAR-22 REV. 01        PAGE 15 16. Reconnect the low pressure nitrogen hoses to the regulator outlet tee and to tanks if previously removed. Use pipe dope on all nitrogen connections.
  • Page 24: Pressure Regulator Test

    (°C) NITROGEN CYLINDER TEMPERATURE Examples: 2. The nitrogen cylinder on an ANSUL fire suppression system 1. The nitrogen cylinder on an ANSUL fire suppression system indicates a pressure of 1350 psi (93.1 bar) on the pressure indicates a pressure of 1450 psi (100 bar) on the pressure gauge.
  • Page 25: Nitrogen Cylinder Valve

    Note: The converted metric values in this document are provided for dimensional reference only and do not reflect an actual measurement. ANSUL, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited.
  • Page 26: Service And Repair

    The condition usually follows the absorption and later evaporation of an unusual amount of moisture. It is often confused with packing – a condition produced by normal settling, by vibration or by impact. There is no known case in which there is evidence that an ANSUL extinguisher was made inoperative as a result of packing. A simple procedure to determine which condition exists is the Underwriters Laboratories four inch drop to a clean hard surface test.
  • Page 27 SERVICE AND REPAIR Component Disorder Corrective Action Low 3% AFFF (Aqueous Film-Forming 3% – Actual % x Tank Capacity Foam) Premix Solution Concentration = Gallons of 3% ANSULITE AFFF Concentrate EXAMPLE FOR 100 GAL TANK (TESTED AT 2%) 3 – 2 –––––...
  • Page 28 Worn or missing protective cylinder Replace webbing (Part No. 3360) or grommet (Part No. 8688). bracket webbing or grommet Wrong cylinder retaining bracket Replace bracket with type specified by ANSUL only. Pressure Corroded, dented, or otherwise Replace regulator(s). Regulator...
  • Page 29 SERVICE AND REPAIR Component Disorder Corrective Action Nozzle Wrong nozzle Replace with type nozzle recommended by the manufacturer (Tyco Fire Protection Products). Valve body or barrel abraded, Replace valve or barrel if in any way damaged or deformed. corroded, cracked, or dented Operating handle broken, or deformed Replace handle.
  • Page 30: Field Inspection Manual

    Page 1 001330 FOAM CONCENTRATES AND FOAM PRE-MIX SOLUTIONS Field Inspection Manual...
  • Page 31 To maximize life of concentrates stored in atmospheric specific concentrate to be tested. Product Data Sheets can storage tanks, ANSUL recommends that a 1/4 in. (6 mm) be accessed at www.ansul.com. layer of mineral oil be added to the air-exposed surface of The designated inspector should be a responsible, experi- the concentrate.
  • Page 32 FOam sOlUTION CONCeNTRaTION DeTeRmINaTION Page 2 FOam sOlUTION CONCeNTRaTION DeTeRmINaTION Using the graph paper, plot the meter reading on the X axis ReFRaCTIve INDex OR CONDUCTIvITy and the percent concentrate reading on the Y axis. This plotted curve will serve as the known baseline for the This test is used to determine the percent concentrate of a proportioning test.
  • Page 33 TypICal CalIbRaTION CURve ResUlTs WheN UsINg paRT NO. 405713 haNDhelD ReFRaCTOmeTeR Page 3 006876...
  • Page 34 NOTes Page 4 NOTes:...
  • Page 35 FIelD INspeCTION ReCORD Page 5 CUSTOMER/LOCATION: ____________________________________________________________ FILE NO.: ____________ DATE: __________________________________________ TESTED BY: __________________________________________ FOAM CONCENTRATE TYPE / LOT NO.:______________________________________________________________________ METER TYPE:________ CONDUCTIVITY:________ REFRACTOMETER MODEL: __________________________________ CALIBRATION STANDARDS METER READING FOAM CONCENTRATE WATER PRE-MIX #1 — PRE-MIX #2 — PRE-MIX #3 —...
  • Page 36 TYCO FIRE PROTECTION PRODUCTS ONE ST NTON STREET M RINETTE, WI 54143-2542...
  • Page 37 Fill Cap Assembly 30411 Gasket 3461 008829 ANSUL, and the product names listed in this material are marks and/or registered marks. Unauthorized use is strictly prohibited. One Stanton Street Marinette, WI 54143-2542, USA +1-715-735-7411 www.ansul.com © 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.