Download Print this page

GE GCCC024DR Installation Instructions Manual

Advertisement

Quick Links

Introduction
Command Closing Coil:
Command Close coil is used to switch ON the
Power
Circuit
Breaker
commanded it releases the spring charged
mechanism thus ensuring a rapid connection of
the main contacts. The Command Close coil
offers an extended functionality in addition to all
the features of the standard closing coil.
Additional connections allow it to be wired out
through the trip unit to be commanded through
the communications bus. An optional electrical
close pushbutton that fits onto the breaker front
fascia is available to command the accessory
from the breaker directly.
Table 1.
Catalog No
DC Voltage
GCCC024DR
24V
GCCC030DR
30V
GCCC048R
48V
GCCC060DR
60-72V
GCCC120R
110-130V
GCCC208AR
GCCC240R
220-240V
GCCC277R
250V
remotely.
When
AC Voltage
48V
110-130V
208V
220-240V
250-277V
DEH-41418 Installation Instructions
®
EntelliGuard
G Circuit Breaker
Accessories
Command Closing Coil
WARNING: Before installing any accessories, turn the
breaker OFF, disconnect it from all voltage sources,
and discharge the closing spings.
AVERTISSEMENT: Avant d'installer tout accessoire,
mettre le disjoncteur en position OFF, le déconnecter
de toute tension d'alimentation , et décharger les
resorts d'armement
▪ Inrush Power: 350VA
▪ Steady state : 50VA
Use the following procedure to install the
Command Closing Coil accessory into the circuit
breaker.
1. Verify that the rating on the Command Closing
Coil identification plate matches the voltage
rating required for the application, as listed in
Table 1.
2. Turn the breaker off and discharge the closing
springs by depressing the OFF and ON buttons in
the sequence OFF-ON-OFF.
breaker OFF-ON indicator shows OFF on a green
background and that the charge indicator shows
DISCHARGE on a white background. If installing
in a draw-out type breaker remove breaker from
adaptor (cassette) before continuing.
3. Loosen the 6 screws on front cover (fascia)
using a posidrive screw driver as shown in Fig 1.B
Rotate the charging handle down and slide the
front cover over the handle to remove the front
cover as shown in Fig. 1.C.
1
Verify that the

Advertisement

loading

Summary of Contents for GE GCCC024DR

  • Page 1 DISCHARGE on a white background. If installing Catalog No DC Voltage AC Voltage in a draw-out type breaker remove breaker from GCCC024DR adaptor (cassette) before continuing. GCCC030DR GCCC048R 3. Loosen the 6 screws on front cover (fascia) GCCC060DR 60-72V using a posidrive screw driver as shown in Fig 1.B...
  • Page 2 Figure 3. Coil Assembly 6. Tilt the device backwards until the rear hooks engage in the slots on the mechanism top support plate as shown in the Fig. 4. Figure 1. (A) Front Cover (B) ScrewRemoval (C) Handle Rotation 4. Place the coil on the mechanism top plate and assemble the connector marked as CCC from the Command closing coil to the connector marked as CCC in the Trip unit harness as shown...
  • Page 3 Figure 7. EC switch assembly Figure 5. Close Coil Plug assembly 11. Assemble the screw with washer as shown 8. Ensure the plug is inserted properly by the in Fig. 8. Tighten the screw to torque snap in the secondary disconnect. 2Nm(1.47ft-lbs).
  • Page 4 Installation of Push button on the fascia: 13. Remove the existing dummy button by removing the screw as shown in fig 10. 15. Rotate the charging handle down and slide the front cover over the handle to assemble the front cover to housing as shown in Fig. 12. Dummy button Screw Figure 10.
  • Page 5 Reference: Command Closing Coil Connection Scheme: A10 – provides constant control power to the Command Close Coil accessory. A9 – control power return. A11 – Separate local command input. Must be fed from the same source as A10.
  • Page 6 These instructions do not purport to cover all details or variations in equipment nor, to provide contingency to be met in connection with installation, operation, or maintenance. Should further information be desired, or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to GE. 41 Woodford Ave, Plainville, CT 06062 www.geelectrical.com...

This manual is also suitable for:

Gccc030drGccc048rGccc060drGccc120rGccc208arGccc240r ... Show all