Overview
The Vantage LVOS-0-10-PWM-DIN has eight low voltage outputs.
Loads 1-4 may be configured as 0-10V (analog) or PWM (source
only) loads. Loads 5-8 are 0-10V, analog only.
Features
8, independent 0-10V low voltage outputs
Outputs 1-4 can be configured as PWM or 0-10V
Manual control and LED status for all 8 LV outputs on front
High resolution performance when dimming
Communicates via station bus
Assembled in a 9 unit DIN case
Override switch for ON and OFF states of all loads
CE Certification / UL
Station Specifications
General
Dimensions, HWD
Weight
Microprocessor status, configuration, loads
LED Indicators
LED on loads 1-4: Red = 0-10 / GREEN =
Ambient
Operating
Temperature
Relative Humidity
Maximum 90%, non-condensing
Cooling
Firmware
Manual Control
Overlay with control/status for each output
Real-time scheduling provided by
FreeRTOS
Compliance
UL • CUL • RoHS• CE • FCC (see Certifications)
DC Input – Power Supply
Input Voltage
Input Power Draw
Connection Type
Connection Rating
Input / Output Connections (Low Voltage)
Station Bus
Connection
2C, 16AWG / 1.31mm2, twisted, non-
Station Bus Wire
shielded, <30pF per foot. Separate a
Specification
minimum of 12" / 30.5cm from other parallel
communication and/or high voltage runs.
Station Wiring
Station Count
0.35W on IC-24 / 0.55W on IC-36
4 Dry Contacts, (3 and 4 may be used for an
Auxiliary Inputs
IR Receiver and Light Sensor respectively)
Override Inputs
Yes – All ON or All OFF contacts
Low Voltage Output: 0-10V
Specification
Number of
outputs
Output
External source
voltage
Loads Per Output
Resolution
Connection type
Connection rating
Low Voltage Output: PWM
Specification
Number of
outputs
Output voltage
Output current
100mA per channel, 400mA total
Loads Per Output
Resolution
Duty cycle
Frequency
Connection type
Connection rating
Protection
DC input, over current protection
Low voltage 0-10V output over
current protection
Low voltage PWM output over
current protection
©Vantage, 8/12/2016 / IS-0521-B
85.7mm x 157.2mm x 61.9mm
3.38" x 6.19" x 2.44"
237g / 8.36oz.
PWM
32-104°F / 0-40°C
Convection
Upgradeable via station bus
FreeRTOS (www.freertos.org)
13.8 – 36VDC
<15W
0.20" pitch removable plug
300V 10A
24V / 36V Station Bus
Daisy-chain/Star/Branch
IEC 60929 Annex E
8
0-10V @ 100mA sink or source
Typical 10V / Maximum 20V
50@ 2.0mA per load (typical)
>1024 steps
0.20" pitch removable plug
300V 10A
IEC 60929 Annex E
4
12V (source only)
50@ 2.0mA per load (typical)
> 1024 steps
Variable 0% to 99.9%
760Hz
0.20" pitch removable plug
300V 10A
PTC fuse (self resetting)
DIN Low Voltage Output Station — MODEL: LVOS-0-10-PWM-DIN
I N S T A L L A T I O N
DIN Low Voltage Output Station — MODEL: LVOS-0-10-PWM-DIN
Certifications
EN55022 Radiated / Conducted emissions
EN55024 61000-4-2 ESD immunity
EN55024 61000-4-3 Radiated immunity
CE,
EN55024 61000-4-4 Fast transient immunity
FCC
EN55024 61000-4-5 Surge immunity
Part 15,
EN55024 61000-4-6 Conducted immunity
Sub-
EN55024 61000-4-8 Magnetic field immunity
Part B
EN55024 61000-4-11 Voltage dips/interruption immunity
61000-3-2 Harmonics current emissions
610000-3-3 Flicker emissions
Load Configurations
Setting up the
load
configurations,
as shown at
right, is done
in Design
Center
software.
Only loads 1-4
may be
configured as
PWM. Set all
four loads as
PWM or in
sets of two,
e.g., loads 1&2,
or loads 3&4.
Low Voltage
Outputs,
0-
10V (analog)
Low Voltage Controls 1-8 and Ground are used to control devices
that work with an analog 0-10V signal. Ground provides the
negative reference for the output voltages. All Grounds are
connected internally to each other. Each control output, 1-8 can
sink or source 0-100mA at any voltage from 0-10VDC. The load
level sets the percentage between the minimum and maximum
voltage that is selected for that load. LED load indicators are
for all loads in 0-10V mode; loads 5-8 are only 0-10V.
PWM Outputs, 12V (Source)
Low voltage outputs 1-4 may be configured as PWM (Pulse Width
Modulation). Only use combinations 1-4, 1&2, or 3&4 as illustrated
for PWM outputs. PWM Duty Cycles are programmed using Power
Profiles from 0%-Minimum On to 100%- Maximum On (99.9%
actual). The load level is a percentage between the minimum and
maximum duty cycle (Power Profile Minimum On and Maximum
On). The output can be reversed in Design Center through the
Power Profile. For example, a 0% duty cycle can either be load ON
or load OFF. LED load indicators 1-4 are
mode.
NOTE: Loads 1 – 8, Low Voltage outputs, should be
limited to 250 feet / 76.2 meters for each wire run, using
a minimum of 18AWG / 0.823mm2 gauge wire. All
connections use 4.4 inch pound torque. Stranded wire
recommended.
Software/Firmware
Design Center Software version 3.x or higher and accompanying
Firmware, are compatible. For new projects it is recommended that
software and firmware be kept to the most current release.
Power Profiles / Power Outages
The Dimmer Station stores Power Profile configuration data locally
so that it will continue to operate correctly if communication with
the system is lost. This information includes: load profile-duty cycle
settings, last load level, and PWM or 0-10V power profiles. If a
station is moved to a new location or if the load type connected is
changed from a 0-10V load to a PWM load, or vice-versa,
remember to change the load type in Design Center, to avoid
unwanted results. Before testing new load type via the local
buttons on the front, program the station to the system so the new
load type is active in the station's output.
If a power outage occurs, when power is restored the station will
return the loads to the last load level with all profiles at there last
known settings. This occurs whether or not the station is
connected to the Controller.
Actuator Buttons
The actuator buttons on the front of the station are for local
control only and are not programmable through Design Center
software. In Diagnostics, these eight buttons and the four dry-
contacts have not been implemented in Button Press Monitor.
V A N T A G E I N S T A L L G U I D E S
red
green
for loads in PWM
page 1 of 2

Advertisement

loading

Summary of Contents for Vantage Hearth LVOS-0-10-PWM-DIN

  • Page 1 V A N T A G E I N S T A L L G U I D E S 2168 West Grove Parkway, Suite 300, Pleasant Grove, UT. 84062 USA DIN Low Voltage Output Station — MODEL: LVOS-0-10-PWM-DIN Telephone: 801 229-2800 ● Fax: 801 224-0355...
  • Page 2 Load Operation PSU36-DIN 36VDC or ACPDXXSM2 24VDC power supplies*. This Action provides power for the LVOS-0-10-PWM-DIN and is required for 1. The load ramps to 100% or fades to 0% over the station to operate. Use 16AWG / 1.31mm wire between power three seconds, alternating with every other supply and stations using a daisy-chain topology.