INSTY-PAC EXTERNAL MOUNT
SPLIT & CUFFED MULTIPLE
Flexible steam
supply line
(or hard piped
by others in field)
Typical PURE
Humidifier Co.
humidifier
"H"
water
seal
1. Steam supply piping should be pitched two inches (2") per foot, back to the humidifier.
2. Install the assembly so that the injection tubes are level within the duct or AHU.
Open sanitary
3. Install tube with orifices injecting steam up.
drain
4. All drain piping is by others.
5. Each condensate connection must have it's own water seal. Condensate connections cannot be combined
together to a common water seal.
6. A common condensate drain line can be used after the individual water seals.
"Read and Save These Instructions"
TUBE ASSEMBLY
INSTALLATION
AND
ASSEMBLY INSTRUCTIONS
Fig. 1
AHU/duct
Tube support
Stainless steel
tube header
"H"
"H"
water
water
seal
seal
Open sanitary
Open sanitary
drain
drain
Injection tube
AHU/duct width
3/4" SW drain piping
(by others)
"ES"/ "EC" Water Seal Height
Total KW
"H"
3 thru 19.5
water
22 thru 33
seal
39 thru 49.5
58.5 thru 102
Open sanitary
drain
INSTALLATION
1
Sheet No.
EMIPSC
Typ. centers
AHU/duct height
Secure end bracket
to AHU/duct
casing with 3/8-16
UNC bolts
"SX"/ "GX" Water Seal Height
Total lbs./hr (kg/hr)
"H"
"H"
8" (20 cm)
Up to 60 (27.2)
8" (20 cm)
11" (28 cm)
61 to 99 (44.9)
11" (28 cm)
17" (43 cm)
100 to 150 (68.0)
17" (43 cm)
19" (48 cm)
151 and above
19" (48 cm)
The water seal height may have to be increased
if excessive duct static pressure exists.
08/08

Advertisement

loading
Need help?

Need help?

Do you have a question about the INSTY-PAC Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Pure Humidifier INSTY-PAC Series

  • Page 1 Sheet No. “Read and Save These Instructions” EMIPSC INSTY-PAC EXTERNAL MOUNT SPLIT & CUFFED MULTIPLE TUBE ASSEMBLY INSTALLATION ASSEMBLY INSTRUCTIONS Fig. 1 AHU/duct Injection tube Tube support Typ. centers AHU/duct height Flexible steam supply line (or hard piped by others in field) Stainless steel tube header Secure end bracket...
  • Page 2 The PURE Humidifier Co. Warranty PURE Humidifier Co. guarantees its products to be free from defects in material and workmanship for a period of two years from the date of shipment; provided the product is properly installed, serviced, and put into the service for which it was intended.
  • Page 3 Steam Supply Piping Examples Pitch Use two 45° elbows for (see Note 1) hard piping or wide 90° for flexible steam hose 1/4”/1’ 2”/1’ Supply piping connectors (see Note 3) Pitched Towards Steam Generator Pitched Towards Tube Assembly Drain Tee (see Note 7) 2”/1’...
  • Page 4 Unpack the components from the shipping container. Verify all components are checked off according to the packing list and the COMPONENTS IDENTIFICATION DRAWING (Fig. 2). Report any missing pieces to your local PURE Humidifier Co. representative immediately. Location Mount the injection tube assembly in the AHU or duct work as shown on the project plans or as indicated by the engineer.
  • Page 5 External Mount Insty-Pac Tube Assembly Component Identification ITEM DESCRIPTION QUANTITY Supply/condensate header Injection tubes varies with order Tube mounting bolts 1 per tube Duct plate (injection tube) 1 per tube Tube support bracket 1 per tube bank Flexible connector 1 per tube Fig.
  • Page 6 Header & Support Bracket Mounting Detail AHU casing or duct wall Cut openings for injection tubes. Seal with duct plates. End bracket Injection tube Supply/ condensate header Steam supply inlet End bracket mounting bolts Mount tubes level within the duct or AHU 3/4”...
  • Page 7 Controls Fan Interlock Switch PURE Humidifier Co. recommends the use of an air flow proving switch or fan interlock to prove air flow prior to humidifier cooperation. Humidifier operation without air flow will result in over-saturation of the air stream. Air flow proving switches are available as optional equipment from your PURE Humidifier Co.
  • Page 8 Troubleshooting Too Much Humidity 1. Humidity controller out of calibration. 2. Humidifier oversized. 3. Check humidifier (GX, SX, ES, EC) for proper operation. Too Little Humidity 1. Humidity controller out of calibration. 2. Undersized humidifier. 3. Check humidifier (GX, SX, ES, EC) for proper operation. 4.
  • Page 9 Maintenance 1. Header– No maintenance required. 2. Injection Tube – No maintenance required. 3. Water Seal – Should be inspected periodically to make sure the traps are clear.
  • Page 10 Non-Wetting Distance With a Insty-Pac Tube Assembly Having 3” Centers 30” 15” 13” 11” 8” 7” 5.5” 2” 1” 15” 11” 10” 9” 7” 5” 4” 1” 10” 8” 7” 6” 5” 3” 2” 8” 6” 5” 4” 3” 1" 6”...
  • Page 11 Maximum Steam Supply Piping Capacities (Atmospheric Applications Only) Type lbs/hr (kg/hr)* Type lbs/hr (kg/hr)* Type lbs/hr (kg/hr)* 1 1/4” (59) Schd’l 40 Pipe 1 1/2” (68) 1 1/2” (59) 1 1/2” (68) Flexible Copper/ Schd’l 40 Hose SST Tubing Pipe 2”...
  • Page 12 141 Jonathan Blvd. North Chaska, MN 55318 Tel: (952) 368-9335 Fax: (952) 368-9338 www.purehumidifier.com...

This manual is also suitable for:

Insty-pac