Sheet No. “Read and Save These Instructions” EMIPSC INSTY-PAC EXTERNAL MOUNT SPLIT & CUFFED MULTIPLE TUBE ASSEMBLY INSTALLATION ASSEMBLY INSTRUCTIONS Fig. 1 AHU/duct Injection tube Tube support Typ. centers AHU/duct height Flexible steam supply line (or hard piped by others in field) Stainless steel tube header Secure end bracket...
Page 2
The PURE Humidifier Co. Warranty PURE Humidifier Co. guarantees its products to be free from defects in material and workmanship for a period of two years from the date of shipment; provided the product is properly installed, serviced, and put into the service for which it was intended.
Page 3
Steam Supply Piping Examples Pitch Use two 45° elbows for (see Note 1) hard piping or wide 90° for flexible steam hose 1/4”/1’ 2”/1’ Supply piping connectors (see Note 3) Pitched Towards Steam Generator Pitched Towards Tube Assembly Drain Tee (see Note 7) 2”/1’...
Page 4
Unpack the components from the shipping container. Verify all components are checked off according to the packing list and the COMPONENTS IDENTIFICATION DRAWING (Fig. 2). Report any missing pieces to your local PURE Humidifier Co. representative immediately. Location Mount the injection tube assembly in the AHU or duct work as shown on the project plans or as indicated by the engineer.
Page 5
External Mount Insty-Pac Tube Assembly Component Identification ITEM DESCRIPTION QUANTITY Supply/condensate header Injection tubes varies with order Tube mounting bolts 1 per tube Duct plate (injection tube) 1 per tube Tube support bracket 1 per tube bank Flexible connector 1 per tube Fig.
Page 6
Header & Support Bracket Mounting Detail AHU casing or duct wall Cut openings for injection tubes. Seal with duct plates. End bracket Injection tube Supply/ condensate header Steam supply inlet End bracket mounting bolts Mount tubes level within the duct or AHU 3/4”...
Page 7
Controls Fan Interlock Switch PURE Humidifier Co. recommends the use of an air flow proving switch or fan interlock to prove air flow prior to humidifier cooperation. Humidifier operation without air flow will result in over-saturation of the air stream. Air flow proving switches are available as optional equipment from your PURE Humidifier Co.
Page 8
Troubleshooting Too Much Humidity 1. Humidity controller out of calibration. 2. Humidifier oversized. 3. Check humidifier (GX, SX, ES, EC) for proper operation. Too Little Humidity 1. Humidity controller out of calibration. 2. Undersized humidifier. 3. Check humidifier (GX, SX, ES, EC) for proper operation. 4.
Page 9
Maintenance 1. Header– No maintenance required. 2. Injection Tube – No maintenance required. 3. Water Seal – Should be inspected periodically to make sure the traps are clear.