HS-100
INSTALLATION
Required material:
1 watertight grommet (compression gland)
1 4-conductor cable, color-coded, 22 AWG wire gauge with
an operating temperature of 175°F (80°C).
Grommet
4-wire cable
M 890-00092
rev. 08
Failure to comply with the required material and
with the following mounting instructions will void
the warranty.
REV. 02

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HS-100 and is the answer not in the manual?

Questions and answers

Summary of Contents for AP HS-100

  • Page 1 HS-100 INSTALLATION Required material: 1 watertight grommet (compression gland) 1 4-conductor cable, color-coded, 22 AWG wire gauge with an operating temperature of 175°F (80°C). Grommet 4-wire cable Failure to comply with the required material and with the following mounting instructions will void the warranty.
  • Page 2: Mounting Instructions

    1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 1 2 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 Top view Side view HS-100, rev.08...
  • Page 3: Maintenance

    HS-100 Maintenance The HS-100 humidity probe is an im- 1- After 6 months of operation: portant part of humidity control man- Replace the filter (replacement agement for livestock. Best results part # 070-10280). are obtained if the following mainte- nance program is carried out. Every...
  • Page 4: Filter Replacement

    Clean the sensing element care- tighten. fully using a clean, damp cloth. Do not use water or other sol- vents. • Push the replacement filter over the sensing element until firmly seated against the ridge on the probe body. HS-100, rev.08...
  • Page 5: Probe Replacement

    1 2 3 4 5 6 7 8 9 0 1 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9 0 1 • Carefully twist and pull the probe Plastic Ridge through the grommet. Probe Connector HS-100, rev.08...
  • Page 6: Wiring Diagram

    HS-100 WIRING DIAGRAM Humidity Probe BLACK WHITE GREEN Conductor color- coding may vary according to manufacturer. Environmental Controller HS-100, rev.08...
  • Page 7: Electrical Specifications

    Response time for 80% change in RH: 9 minutes or less, depending on air flow Output: 4 to 20mA current loop (50% = 12mA) Maximum terminating impedance: 350 Ohms, one side connected to ground Filter: sintered bronze, 20-micron aperture, replaceable Indicator lights: one for power (green), one to indicate cleaning required (red) HS-100, rev.08...
  • Page 8 NOTES...