APPLICATION
The Aquastat IQ Option Card provides electronic
temperature sensing in a UL limit-rated control with a
single sensing probe. The Aquastat IQ Option Card
replaces auxiliary high limit Aquastats such as
L4006A, L4008A, L4006E and L4008E.
This product may be applied to either gas or oil fired
steam or hot water boilers equipped with the IQ
Control System. The Aquastat IQ Option card may
be simply "plugged in" to the IQ Option Panel and
only requires sensor and well installation to become
operational.
GENERAL
The Aquastat IQ Option Cards are available in
automatic or manual reset models. Automatic reset
versions automatically reset when temperature return
to safe levels.
Manual reset models require user
intervention to reset a temperature condition after the
temperature returns to safe levels.
SPECIFICATIONS
Listings/Approvals
UL353 Limit Controls for both US (UL) and
Canada (CUL)—Component Recognized
UL 1998 Software Safety Standards as a Class 2
device.
Add a Manual Reset Aquastat IQ Option Card,
p/n
102720-01,
temperature control to be Fully compliant with
CSD-1 requirements for temperature controls in
the US and Canada
102715-01-6/09
to
the
factory
mounted
Dimensions: 4.5 in. x 1.5 in. (fits onto IQ Option Panel)
Operating temperature: -4°F to 150°F
Shipping and Storage: -40°F to 175°F
Humidity 0 to 95% R.H. Non-condensing
Input ratings: 24 VAC 60 Hz
Reset: Automatic or manual reset modes
Sensor: Dual Sensor, Limit Rated, p/n102295-01
(Honeywell p/n 50001464-004)
with sensor clip 102422-01
Well: p/n
80160456, (Honeywell p/n 123869A),
Spud Size:1/2 inch NPT
Insertion: 3 inches
Insulation: 1-1/2 inches
Instruction Sheet

Advertisement

loading

Summary of Contents for Burnham Aquastat IQ Option Card

  • Page 1 APPLICATION The Aquastat IQ Option Card provides electronic temperature sensing in a UL limit-rated control with a single sensing probe. The Aquastat IQ Option Card replaces auxiliary high limit Aquastats such as L4006A, L4008A, L4006E and L4008E. This product may be applied to either gas or oil fired steam or hot water boilers equipped with the IQ Control System.
  • Page 2: Installation

    Aquastat IQ Option Card – Instruction Sheet INSTALLATION When Installing this Product…. 1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. Save instructions for future use. 2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
  • Page 3 7. Insert the sensor element into the well until it bottoms. See Sensor Installation diagram above for details 8. Insert sensor clip to hold the sensor against the bottom of the well. 9. Rout sensor wire and connect to Aquastat IQ Option Card 10. Turn power ON.
  • Page 4: User Interface

    Checkout Check to make certain that the Aquastat IQ Option Card has been installed and adjusted to the proper settings. Put the system into operation and observe the action of the device through several cycles to make certain that it provides proper control of the system as described in the Operations section.
  • Page 5 Aquastat IQ Option Card – Instruction Sheet USER INTERFACE (continued) Using IQ Option Panel Display Showing View Mode Options The IQ Option Panel display along with Up , Down In view mode the user may look at (but not change) status and “...
  • Page 6 Aquastat IQ Option Card – Instruction Sheet USER INTERFACE (continued) Entering Adjustment Mode How To Reset The Aquastat In Adjustment Mode, the user can adjust the High Limit or To Reset the Manual Reset Type Aquastat Card: Differential, change measurement units or reset a high temperature condition for Manual Reset models.
  • Page 7: Ordering Information

    Aquastat IQ Option Card – Instruction Sheet ORDERING INFORMATION Part Number Description Aquastat Limit Control IQ Option Card, 130-220 Deg F, Manual Reset for use with 102720-01 Option Control Panel, temperature sensor, well, sensor clip, instructions, Unit Pack Aquastat Limit Control, IQ Option Card, 130-220 Deg F, 15 Deg F Adjustable...

This manual is also suitable for:

Aquastat 102720-01Aquastat 102717-01Aquastat 102292-01Aquastat 102293-01