ECL Series L
Figure 1:
From left to right: large enclosure with HOA switches, large enclosure without HOA, and small enclosure with operator interface.
Product Description
This document describes the hardware installation procedures for the ECL Series L
The Distech Controls ECL Series controllers are designed to control and monitor various HVAC equipment such as roof top units, air handling units as
well as chillers, boilers, and central plant applications. Moreover, these controllers are suitable for any lighting control and power measurement applica-
tions. This product line includes the following controllers: ECL‑203, ECL‑300, ECL‑400 Series, ECL‑600 Series.
For controllers equipped with an operator interface (ECL-x50 models), refer to the ECL‑x50 and ECB‑x50 Series Controller User Guide for how to use
the this interface.
The ECL‑600 Series are compatible with the IO Extension Module product line, which includes the following modules: ECx‑400, ECx‑410, and ECx-420
(refer to the ECx‑400 series IO Extension Module Hardware Installation Guide).
Each controller uses the L
W
ON
ORKS
This document describes the hardware installation procedures for the following controllers: ECL‑203, ECL‑300, ECL‑400 Series, and ECL‑600 Series
controllers only.
£
These controllers are all built on a similar platform, but have different numbers of inputs and outputs. Moreover,
each individual model has different amounts of digital and/or universal outputs. For more information on the
specific layout and functionality of each controller, please refer to their individual datasheets.
£
The following controllers are housed in small enclosures: ECL‑203 Series and ECL‑300 Series.
£
The following controllers are housed in large enclosures: ECL‑400 Series and ECL‑600 Series.
General Installation Requirements
For proper installation and subsequent operation of the device, pay special attention to the following recommendations:
£
It is recommended that the controller(s) be kept at room temperature for at least 24 hours before installation to allow any condensation that may
have accumulated due to low temperature during shipping/storage to evaporate.
£
Upon unpacking, inspect the contents of the carton for shipping damages. Do not install a damaged device.
£
The device is designed to operate under environmental conditions that are specified in its datasheet.
£
Ensure proper ventilation of the device and avoid areas where corroding, deteriorating or explosive vapors, fumes or gases may be present.
£
Record the 12-character Neuron
£
Allow for proper clearance around the device's enclosure and wiring terminals to provide easy access for hardware configuration and maintenance.
£
When installing in an enclosure, select one that provides sufficient surface area to dissipate any heat generated by the device and by any other de-
vices installed in the enclosure. A metal enclosure is preferred. If necessary, provide active cooling for the enclosure.
£
Orient the controller with the ventilation slots and power supply/output terminal block connectors towards the top to permit proper heat dissipation.
£
The device's plastic enclosure has a back plate that is separable from the front plate allowing the back plates (with the connectors) to be shipped di-
rectly to the installation site while all the engineering is done in the office.
£
The device's datasheet specifies the power consumption (amount of heat generated), the operating temperature range, and other environmental
conditions the device is designed to operate under.
£
Ensure that all equipment is installed according to local, regional, and national regulations.
£
Do not drop the device or subject it to physical shock.
£
If the device is used and/or installed in a manner not specified by Distech Controls, the functionality and the protection provided by the device may
be impaired.
W
ON
ORKS
TP/FT-10 communication protocol.
®
ID located on either end of the device (shown on a sticker below the barcode), for later commissioning.
 Controllers
W
controllers.
ON
ORKS
I n s t a l l a t i o n G u i d e

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LonWorks ECL-203 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Distech LonWorks ECL-203 Series

  • Page 1 £ Do not drop the device or subject it to physical shock. £ If the device is used and/or installed in a manner not specified by Distech Controls, the functionality and the protection provided by the device may be impaired.
  • Page 2: General Wiring Recommendations

    Any type of modification to any Distech Controls product will void the product’s warranty Take special care to keep the front and back plate aligned when separating and joining them. Before installation of the Wireless Receiver, verify that local communication regulations allow the installation of wireless devices and available frequencies to be supported in your area.
  • Page 3 Controller Dimensions & Components Figure 2: Rear view of large enclosure Figure 3: Rear view of small enclosure Figure 4: Side view of large and small enclosure 3 / 16...
  • Page 4: Mounting Instructions

    Mounting Instructions The controllers can be mounted on a DIN rail to speed up the installation procedure. They are also equipped with two mounting holes 0.25” x 0.165” (6.35mm x 4.191mm). The controllers can be mounted in a panel or on a wall by using appropriate screw types (use sheet metal, thread forming, or self-tapping screws accordingly).
  • Page 5: Power Wiring

    Power Wiring Voltage: 24VAC/DC; ± 15%, Class 2 This is a Class 2 Product. Use a Class 2 transformer only (rated at 100VA or less at 24VAC) to power the controller(s). The Network Guide provides extensive information and requirements for powering a controller that uses a L network for communications.
  • Page 6 Jumper Identification and Configuration Controllers have the following onsite configurable jumpers. Wireless Port Net to Subnet Settings Enabled Disabled * Subnet Net Port Port * Factory- default position Figure 8: ECL-203 Controller Jumper Locations Wireless Port Universal Outputs (UO) 0- 10V / 0- 20 mA Select 0-10V* 0- 20mA Network Board...
  • Page 7: Input Wiring

    Input Wiring Before connecting a sensor to the controller, refer to the installation guide of the equipment manufacturer. £ For a wire length less than 75’ (23m), either a shielded or unshielded 18AWG wire may be used. £ For a wire up to 200’ (61m) long, a shielded 18AWG wire is recommended. £...
  • Page 8 Sensor Input Type Input Connection Diagram ECL‑300, ECL‑400, and ECL‑600 Series: Jumper To Analog- £ 0 to 20mA input used with a 2-wire, 0 to 20mA sensor powered by the controller’s internal Setting 0-10V To-Digital 15VDC power supply. +15VDC Converter 0-20mA £...
  • Page 9: Output Wiring

    Output Wiring Before connecting an output device (actuator, relay, etc.) to the controller, refer to the datasheet and installation guide of the equipment manufacturer. £ For a wire length less than 75’ (23m) long, either a shielded or unshielded 18AWG wire may be used. £...
  • Page 10: Communications Wiring

    Guide for extensive information and requirements for the connection of the Allure Series. It contains information about network topology and length, cable type, setting the Subnet ID, etc. It can be downloaded from the www.distech-controls.com website. See also the Hardware Installation Guide sup- plied with the Allure Series.
  • Page 11: Wireless Installation

    For more information and detailed explanations on network topology and wire length restrictions, refer to the Network Guide, which can be downloaded from our website. It is important to use proper network terminators depending on the type of network topology used. Failure to do so may result in communication errors between controllers.
  • Page 12: Maintenance

    Connecting the Wireless Receiver The Wireless Receiver is connected to the controller using a 2m (6.5ft) telephone cable with 4P4C modular connectors at both ends. Do not exceed this cable length. The Wireless Receiver’s telephone socket is located inside the device. To locate it, open the Wireless Receiver by separating its front and back plates.
  • Page 13: North American Emissions Compliance

    Directive applies to standalone products, for example, products that can function entirely on their own and are not a part of another system or piece of equipment. For this reason Distech Controls products are exempt from the WEEE Directive. Nevertheless, Distech Controls products are marked with the WEEE symbol , indicating devices are not to be thrown away in municipal waste.
  • Page 14 Typical Air Handling Unit Application Wiring Diagram Supply Return Heat Cool Damper Humidifier Starter Starter 4A Fuse 0-10 0-10 0-10 0-10 Transformer Fast Acting 24VAC OPTIONAL: Connect to Electrical System Ground Service PIN Button ECL-600 ® ORKS PORT Back of Allure EC-Smart-Vue * 249 ohm resistor built-in for inputs configured as 4-20mA EOL Enabled at...
  • Page 15: Troubleshooting Guide

    Troubleshooting Guide Controller is powered but does not turn on Fuse has blown Disconnect the power. Check the fuse integrity. Reconnect the power. Power supply polarity Verify that consistent polarity is maintained between all controllers and the transformer. Ensure that the 24VCOM terminal of each controller is connected to the same terminal on the secondary side of the transformer.