Direct ignition combination gas controls

Advertisement

Quick Links

V8205, VR8205 Direct Ignition
Combination Gas Controls
APPLICATION
These direct ignition gas controls are used in gas-fired
appliances with up to 200 cfh capacity on natural gas.
They include safety shutoff, a manual valve, one or two
automatic operators and a pilot adjustment. See Table 1
for model differences and Table 2 for temperature
ranges and regulator types.
These gas controls are factory-set for natural (and
manufactured) gas or LP gas. Do not attempt to use a
control set for natural (manufactured) gas on LP gas, or
a control set for LP on natural (manufactured) gas.
Model
Voltage/Frequency
V8205
24V/60 Hz
VR8205
24V/60 Hz
Table 2. Model Number Suffix Letter Designation.
Model No.
Temperature
Suffix Letter
A
0° F to 175° F
[-18° C to 79° C]
C
H
K
-40° F to 175° F
[-40° C to 79° C]
M
P
Table 3. Flange Part Numbers.
Inlet/Outlet
Pipe Size
Flange Type
3/8 inch
Straight
NPT
Elbow
1/2 inch
Straight
NPT
Elbow
3/4 inch
Straight
NPT
Elbow
Table 1. Direct Ignition Combination Gas Control Models.
Number of Automatic Operators
One
Two
Ambient
Regulator
Range
Type
Standard
Step-opening
Slow-opening
Standard
Step-opening
Part Number
Without Hex
With Hex
Wrench
Wrench
393690-1
393690-11
393690-2
393690-12
393690-6
393690-16
393690-3
393690-13
393690-4
393690-14
393690-5
393690-15
INSTALLATION INSTRUCTIONS
Controls with standard or slow opening regulators can
be converted from one gas to the other with a
conversion kit (ordered separately). Order part no.
393691 to convert from natural (manufactured) to LP
gas; order part no. 394588 to convert from LP to natural
(manufactured) gas. Controls with step opening
regulators cannot be converted.
Body Pattern: Straight through with 1/2 in. inlet and
1/2 in. outlet.
Pipe Adapters: Angle and straight adapters available for
3/8, 1/2 and 3/4 in. pipe. See Table 3.
Gas Control Knob Positions
OFF-ON
OFF-ON
NOTE:
Flange Kits include one flange with attached O-
ring and four mounting screws. Kits include a
9/64 in. hex wrench, as noted.
Approvals:
American Gas Association design certificate:
L2025006.
Canadian Gas Association design certificate:
L2025006.
Australian Gas Association design certificate: 4214.
Approved for Delta C applications.
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a haz-
ardous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable
for your application.
3. The installer must be a trained, experienced ser-
vice technician.
4. After installation is complete, check out product
operation as provided in these instructions.
Current Draw
0.30A
0.5A
69-0329-05

Advertisement

loading
Need help?

Need help?

Do you have a question about the V8205 and is the answer not in the manual?

Questions and answers

Summary of Contents for resideo V8205

  • Page 1 V8205, VR8205 Direct Ignition Combination Gas Controls INSTALLATION INSTRUCTIONS Controls with standard or slow opening regulators can APPLICATION be converted from one gas to the other with a conversion kit (ordered separately). Order part no. These direct ignition gas controls are used in gas-fired 393691 to convert from natural (manufactured) to LP appliances with up to 200 cfh capacity on natural gas.
  • Page 2 V8205, VR8205 DIRECT IGNITION COMBINATION GAS CONTROLS Flanges WARNING 1. Choose the appropriate flange for your application. 2. Remove seal over gas control inlet or outlet. Fire or Explosion Hazard 3. Make sure the O-ring fits into the flange groove. If...
  • Page 3 V8205, VR8205 DIRECT IGNITION COMBINATION GAS CONTROLS • Cover gas control if appliance is cleaned with water, steam, or chemicals or to avoid dust and grease DROP accumulation. PIPED • Avoid locating gas control where exposure to HORIZONTAL CONTROL corrosive chemical fumes or dripping water are likely.
  • Page 4 V8205, VR8205 DIRECT IGNITION COMBINATION GAS CONTROLS WHEN FLANGE IS USED WHEN FLANGE IS NOT USED APPLY WRENCH APPLY WRENCH TO FLANGE ONLY FROM TOP OR BOTTOM OF GAS CONTROL TO EITHER SHADED AREA M3084A Fig. 5. Proper use of wrench on gas control with and without flanges.
  • Page 5: Startup And Checkout

    V8205, VR8205 DIRECT IGNITION COMBINATION GAS CONTROLS Gas Leak Test 1. Paint all pipe connections upstream of the gas DUAL VALVE S89C,G,J/S890C,G,J COMBINATION HOT SURFACE control with a rich soap and water solution. Bub- GAS CONTROL IGNITION CONTROL bles indicate a gas leak.
  • Page 6 V8205, VR8205 DIRECT IGNITION COMBINATION GAS CONTROLS 3. If necessary, adjust the pressure regulator to 3. If necessary, adjust the pressure regulator to match the appliance rating. Refer to Table 5 or 6 for match the appliance rating. Refer to Table 5 or 6 for...
  • Page 7 V8205, VR8205 DIRECT IGNITION COMBINATION GAS CONTROLS 1. Turn off gas supply. Instructions To The Homeowner (For 2. Set the thermostat or controller above room tem- Your Safety, Read Before Lighting) perature to call for heat. 3. Watch for ignition spark or for glow at hot surface igniter either immediately or following prepurge.
  • Page 8: To Turn Off Appliance