Kidde KI-PCD Installation Sheet page 4

Ntelligent photoelectric smoke detector with co sensor

Advertisement

Specifications
Operating voltage
Current
Normal operating
Alarm
Vibration level
Wall mount distance from
ceiling
Compatible bases
Standard
Relay
Isolator
Audible
Compatible detector testers
Operating environment
Temperature
Relative humidity
Storage temperature
Environmental compensation
[1] Required for those installations that must provide separate CO
(TC4) and fire (TC3) patterns from the sounder base. Refer to
GSA-T3T4 installation sheet p/n 3102073-EN.
Regulatory information
UL smoke
0.53 to 3.94%/ft. (1.7 to 12.35 %/m) obscuration
sensitivity range
UL CO alarm level
70 ppm 60 to 240 minutes [1]
150 ppm 10 to 50 minutes [1]
400 ppm 4 to 15 minutes [1]
UL CO False
30 ppm 30 days[1]
alarm level
70 ppm 60 minutes[1]
North American
UL 268, UL 2075
standards
Note: This detector has been evaluated to the CO
alarm sensitivity limits of UL 2034.
FCC compliance
This device complies with part 15 of the FCC
Rules. Operation is subject to the following two
conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any
interference received, including interference that
may cause undesired operation.
[1] Sensitivity per UL 2034
Contact information
For contact information, see www.kiddelifesafety.com.
4 / 4
15.20 to 19.95 VDC
51 µA
68 µA
10 to 35 Hz, with an amplitude of
0.01 in.
12 in. (305 mm) max.
KI-SB, KI-SB4, GSA-SB, GSA-SB4
KI-RB, KI-RB4, GSA-RB
KI-IB, KI-IB4, GSA-IB, GSA-IB4
KI-ABDT [1], KI-ABLT [1]
GSA-SBT [1]
Testifire 2000
32 to 120°F (0 to 49°C)
0 to 90% noncondensing
−4 to 140°F (−20 to 60°C)
Automatic
P/N 3102469-EN • REV 003 • 04JUN18