Ediseja 21 LSU 110/32 User Manual

Local signalization unit

Advertisement

Quick Links

Device:
LSU 110 / 32
Local Signalization Unit
Document:
Code:
User manual LS3MUE01
LSU 110 / 32
User manual
LSU 110 / 32
Date:
15.08.2020

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LSU 110/32 and is the answer not in the manual?

Questions and answers

Summary of Contents for Ediseja 21 LSU 110/32

  • Page 1 LSU 110 / 32 Local Signalization Unit User manual LSU 110 / 32 Device: Document: Code: Date: LSU 110 / 32 User manual LS3MUE01 15.08.2020...
  • Page 2: Table Of Contents

    LSU 110 / 32 - Local Signalization Unit User manual Content PREFACE.......................3 DESCRIPTION....................5 OPERATION....................6 3.1 POWER ON.......................... 6 3.2 NORMAL OPERATION......................6 3.3 OPERATION DURING TEST....................7 3.4 LAMPS, BUTTONS, BINARY INPUTS AND OUTPUTS DESCRIPTION......8 SETTINGS......................9 IEC 60870-5-103 PROTOCOL..............18 5.1 INFORMATION TABLE...................... 18 5.2 EXAMPLES OF REQUEST RESPOND SEQUENCES .............19 SCHEMATICS....................21 INSTALLATION....................22...
  • Page 3: Preface

    Tel: 00 386 51 643 411, 051 643 411 Email: grega.flander@ediseja21.com www.ediseja21.com Copyright Copyright © Ediseja 21, 2019. All rights reserved. Explanation of the symbols Read the instructions! Device was tested with AC 2,5 kV voltage to check the device insulation.
  • Page 4 LSU 110 / 32 - Local Signalization Unit User manual Danger indicates that death, severe personal injury or substantial property damage will result if proper precautions are not taken. Warning indicates that death, severe personal injury or substantial property damage can result if proper precautions are not taken.
  • Page 5: Description

    LSU 110 / 32 - Local Signalization Unit User manual DESCRIPTION LSU 110 / 32 device is intended for local signalization in power distribution substations. It is also called alarm annunciator. Power supply and binary inputs are made for standard voltages in substations; DC 24 V, DC 48 V, DC 110 V, DC 220 V or AC 230 V depends on ordering.
  • Page 6: Operation

    LSU 110 / 32 - Local Signalization Unit User manual OPERATION POWER ON After power is applied, lamp »Power/Error« illuminate red. After all lamps are illuminated one by one, »Power/Error« lamp illuminate green. When »Power/Error« lamp is green, device is ready to operate and DO6 is activated (only device without special option (see ordering option 2)).
  • Page 7: Operation During Test

    LSU 110 / 32 - Local Signalization Unit User manual Operation of DO6: device without special option (see ordering option 2): DO6 has device ready function device with special option 6 (see ordering option 2): ack. lamp depends on device setting (see chapter „SETTINGS“) button »ACK LAMP«...
  • Page 8: Lamps, Buttons, Binary Inputs And Outputs Description

    LSU 110 / 32 - Local Signalization Unit User manual LAMPS, BUTTONS, BINARY INPUTS AND OUTPUTS DESCRIPTION Each lamp 1-32 has its dependent binary input 1-32. Lamp lightning depends on state of binary input and software settings. Additional two colour lamp »POWER/ERROR« signalize state of device. Red lamp means device is starting or device is not operating correctly.
  • Page 9: Settings

    LSU 110 / 32 - Local Signalization Unit User manual SETTINGS Setting procedure: Press and hold button »ACK HORN« for approximately 3 s.  All lamps goes ON for 1 s.  Device is now in set lamp flashing speed mode. All lamps are flashing except first, second, ...
  • Page 10 LSU 110 / 32 - Local Signalization Unit User manual Change the speed of lamp flashing with button »ACK HORN«.  Lamp flashing speed setting is confirmed with button »ACK HORN«. All lamps goes ON for  1 s. Device is now in set lamp logic mode. Lamp logic setting: ...
  • Page 11 LSU 110 / 32 - Local Signalization Unit User manual Move to lamps by pressing button »ACK HORN«.  Single lamp logic setting is changed with button »ACK LAMP«.  When all lamps logic are set press and hold button »ACK HORN« for approximately 3 s. ...
  • Page 12 LSU 110 / 32 - Local Signalization Unit User manual All lamps goes ON for 1 s. Device is now in set rising edge mode.  Rising edge setting:  lamp flashing means lamp we are currently set (lowest right) ...
  • Page 13 LSU 110 / 32 - Local Signalization Unit User manual Move to lamps by pressing button »ACK HORN«.  All lamps goes ON for 1 s. Device is now in set time delay mode.  First left lamp is ON and it marks the lamp (binary inputs) to be set. Last righ lamp is ...
  • Page 14 LSU 110 / 32 - Local Signalization Unit User manual Move between time settings by pressing button »ACK HORN«.  Page: Device: Document: Code: Date: LSU 110 / 32 User manual LS3MUE01 15.08.2020...
  • Page 15 LSU 110 / 32 - Local Signalization Unit User manual Select / deselect time setting by pressing button »ACK LAMP«. If lamp is ON, selected time  delay is active. If lamp is OFF, selected time delay is not active. Move between lamps by pressing button »TEST«.
  • Page 16 LSU 110 / 32 - Local Signalization Unit User manual When time delays for all lamps are set press and hold button »ACK HORN« for  approximately 3 s. All lamps goes ON for 1 s.  Page: Device: Document: Code: Date: LSU 110 / 32...
  • Page 17 LSU 110 / 32 - Local Signalization Unit User manual First row marks the device address (on the picture device adress = 3). Second row marks  station address. Last righ lamp in second row is flashing. Flashing lamp marks the setting position.
  • Page 18: Iec 60870-5-103 Protocol

    LSU 110 / 32 - Local Signalization Unit User manual IEC 60870-5-103 PROTOCOL INFORMATION TABLE Communication Protocol IEC 60870-5-103 (slave) link reset, class I, class II, general interrogation, time Supported responds synhronization (broadcast & single device), general command Device address 1 - 255 1 - 255 Station address...
  • Page 19: Examples Of Request Respond Sequences

    LSU 110 / 32 - Local Signalization Unit User manual Device IEC 60870-5-103 information table digital input 19 digital input 20 digital input 21 digital input 22 digital input 23 digital input 24 digital input 25 digital input 26 digital input 27 digital input 28 digital input 29 digital input 30...
  • Page 20 LSU 110 / 32 - Local Signalization Unit User manual 68 0E 0E 68 08 01 01 81 09 01 F0 A0 01 E5 01 33 11 00 50 16 10 5A 01 5B 16 68 0E 0E 68 08 01 01 81 09 01 F0 A1 01 72 05 33 11 00 E2 16 10 7A 01 7B 16 68 0E 0E 68 08 01 01 81 09 01 F0 A2 01 6C 09 33 11 00 E1 16 10 5B 01 5C 16...
  • Page 21: Schematics

    LSU 110 / 32 - Local Signalization Unit User manual SCHEMATICS Picture 1: LSU 110 / 32.x.x.V.x.N.x.5 schematic (4DIs in group (9 groups), 5 - RS485 & RS232) LSU 110 / 32.x.x.V.x.N.x.N schematic (4DIs in group (9 groups), N - no commun. port) Picture 2: LSU 110 / 32.x.x.V.x.S.x.5 schematic (S - separated DIs (36 groups), 5 - RS485 &...
  • Page 22: Installation

    LSU 110 / 32 - Local Signalization Unit User manual INSTALLATION Warning! Hazardous voltage is present inside the device during operation. Disregarding of safety rules can result in severe personal injury or property damage. Only qualified personnel may work with described devices after being familiar with warnings and safety notices in this paper and other safety regulations.
  • Page 23 LSU 110 / 32 - Local Signalization Unit User manual Picture 4: LSU 110 / 32 inserted papers dimensions Device: Document: Code: Date: Page: LSU 110 / 32 User manual LS3MUE01 15.08.2020...
  • Page 24: Commissioning And Maintenance

    LSU 110 / 32 - Local Signalization Unit User manual COMMISSIONING AND MAINTENANCE COMMISSIONING Warning! Hazardous voltage is present inside the device during operation. Disregarding of safety rules can result in severe personal injury or property damage. Only qualified personnel may work with described devices after being familiar with warnings and safety notices in this paper and other safety regulations.
  • Page 25: Technical Data

    LSU 110 / 32 - Local Signalization Unit User manual TECHNICAL DATA Power supply LSU 110 / 32.1..DC 24 V LSU 110 / 32.2..DC 48 V DC 110 V Rated input voltage LSU 110 / 32.3..LSU 110 / 32.4..DC 220 V LSU 110 / 32.5..
  • Page 26 LSU 110 / 32 - Local Signalization Unit User manual Binary input LSU 110 / 32.x.5..AC 180 V – 253 V all types 1,2 mA Input current Frequency 50 Hz screw type „MSTB“ Phoenix 5 pin Connector type crossection 0,5 –...
  • Page 27 LSU 110 / 32 - Local Signalization Unit User manual Device Class Overvoltage category up to 2000 m Altitude Device: Document: Code: Date: Page: LSU 110 / 32 User manual LS3MUE01 15.08.2020...
  • Page 28: Dimensions

    LSU 110 / 32 - Local Signalization Unit User manual DIMENSIONS Picture 5: LSU 110 / 32 dimensions Page: Device: Document: Code: Date: LSU 110 / 32 User manual LS3MUE01 15.08.2020...
  • Page 29: Ordering

    LSU 110 / 32 - Local Signalization Unit User manual ORDERING ORDERING CODE: LSU 110 / . c- Number of lamps: number of lamps*..............32 Power supply voltage: DC 24 V ..................1 DC 48 V ..................2 DC 110 V-125 V ................ 3 DC 220 V ...................
  • Page 30 LSU 110 / 32 - Local Signalization Unit User manual Contact: Ediseja 21, razvoj elektronskih naprav, d.o.o. Ediseja 21 d.o.o. Stegne 21C 1000 Ljubljana Slovenia – EU Phone: 00 386 51 643 411 grega.flander@ediseja21.com www.ediseja21.com Page: Device: Document: Code: Date:...