1.0 Purpose and Applicability

1.0
Purpose and Applicability
This document covers the installation and operation of the DCX
1.1

1.1 Product Model

Product Model
This document applies to Alpha products in the following model configurations:
Table 1. DCX Model Configurations - Switch Only Versions (No Current Limiting)
DESCRIPTION
400A DCX Battery Disconnect; -48VDC; w/shunt
600A DCX Battery Disconnect; -48VDC; w/shunt
800A DCX Battery Disconnect; -48VDC; w/shunt
1000A DCX Battery Disconnect; -48VDC; w/shunt
1200A DCX Battery Disconnect; -48VDC; w/shunt
Table 2. DCX Model Configurations - Magnetic Trip Versions
DESCRIPTION
400A DCX Battery Disconnect; -48VDC; w/shunt
600A DCX Battery Disconnect; -48VDC; w/shunt
800A DCX Battery Disconnect; -48VDC; w/shunt
1000A DCX Battery Disconnect; -48VDC; w/shunt
1200A DCX Battery Disconnect; -48VDC; w/shunt
For a list of mounting kit and accessory part numbers, refer to Section 6 on Page 17.
2.0

2.0 Theory of Operation

Theory of Operation
The DCX disconnect product family includes multiple amperage ratings and installation mounting schemes to provide a
DC or Battery source disconnect device for use in Telecom +24 or -48VDC systems as well as solar-alternate energy
or other DC applications. The primary application for the DCX system is to provide over-current protection for battery
sourced equipment and wiring. The secondary function is to provide a service disconnect in order to maintain batteries or
to shut down the battery source connection in an emergency.

2.1 Circuit Breaker Trip Ratings

2.1
Circuit Breaker Trip Ratings
The DCX product family includes circuit breaker trip ratings of 400, 600, 800, 1000, and 1200A. The electrical
configuration allows for both positive and negative connected systems as factory configured options. The DCX system
includes a circuit breaker or switch, an internal input and output copper bus structure, a steel inner housing, a circuit
board, and a flame retardant plastic outer housing.
2.2
2.2 Mounting Configurations
Mounting Configurations
Several different mounting bracket option kits provide battery top terminal mounting configurations for numerous battery
manufacturer's cell configurations.
5
Series top terminal battery disconnect system.
PART NUMBER
C016-1001-10
C016-1003-10
C016-1005-10
C016-1007-10
C016-1009-10
PART NUMBER
C016-198-10
C016-195-10
C016-199-10
C016-196-10
C016-207-10
C048-699-30 R03, Rev. B (01/2021)

Advertisement

Table of Contents
loading

Table of Contents