Analog Command Value Card VT-SWKA-1
Product Description and Commissioning Instructions
RE 30 255-B/05.00
Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK
Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HYQUIP VT-SWKA-1 and is the answer not in the manual?

Questions and answers

Summary of Contents for Mannesmann HYQUIP VT-SWKA-1

  • Page 1 +44 (0)1204 699 959 enquiries@hyquip.co.uk www.hyquip.co.uk/web/index Analog Command Value Card VT-SWKA-1 Product Description and Commissioning Instructions RE 30 255-B/05.00 Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389...
  • Page 2: Table Of Contents

    +44 (0)1204 699 959 enquiries@hyquip.co.uk www.hyquip.co.uk/web/index Product description and commissioning instructions VT-SWKA-1 Table of contents Table of contents 1. General 1.1 Features 1.2 Technical data 2. Block circuit diagram 3. Functional description / commissioning notes 3.1 General 3.2 Command value preselection 3.3 Current input 3.4 Command value call-ups 3.5 External command value potentiometer...
  • Page 3: General

    +44 (0)1204 699 959 enquiries@hyquip.co.uk www.hyquip.co.uk/web/index Product description and commissioning instructions VT-SWKA-1 1. General 1. General 1.1 Features – Analog command value card (without power part) for controlling valves with integral electronics → For controlling valves without integral electronics, a suitable additional amplifier is required.
  • Page 4: Technical Data

    +44 (0)1204 699 959 enquiries@hyquip.co.uk www.hyquip.co.uk/web/index Product description and commissioning instructions VT-SWKA-1 1. General 1.2 Technical data For applications outside these parameters, please consult us! Operating voltage 24 VDC + 40 % – 20 % Operating range: – Upper limit value 35 V –...
  • Page 5: Block Circuit Diagram

    +44 (0)1204 699 959 enquiries@hyquip.co.uk www.hyquip.co.uk/web/index Product description and commissioning instructions VT-SWKA-1 2. Block circuit diagram 2. Block circuit diagram RE 30 255-B/05.00 Hyquip Limited New Brunswick Street Horwich Bolton Lancashire BL6 7JB UK Company Registered in England No: 4167649 VAT Registration No: 732 5692 25 BS EN ISO 9001:2008 No: LRQ 0964389...
  • Page 6: Functional Description / Commissioning Notes

    +44 (0)1204 699 959 enquiries@hyquip.co.uk www.hyquip.co.uk/web/index Product description and commissioning instructions VT-SWKA-1 3. Functional description / commissioning notes 3. Functional description / 3.1 General The command value card is designed as printed circuit board in Euro-format 100 x 160 mm commissioning notes and is suitable for installation in a rack.
  • Page 7: Ramp Generator

    +44 (0)1204 699 959 enquiries@hyquip.co.uk www.hyquip.co.uk/web/index Product description and commissioning instructions VT-SWKA-1 3. Functional description / commissioning notes 3.8 Ramp generator [9] The ramp generator limits the increase of the control variable. Downstream step-functions and amplitude attenuators do not shorten or extend the ramp time. Jumper J2 can be used to set the ramp time to minimum (<...
  • Page 8: Ramp Time Selection Logic

    +44 (0)1204 699 959 enquiries@hyquip.co.uk www.hyquip.co.uk/web/index Product description and commissioning instructions VT-SWKA-1 3. Functional description / commissioning notes 3.11 Ramp time selection logic [10] a) Operating mode "4-quadrant operation" When 4-quadrant operation is activated (24V signal “4Q”), the electronics automatically recognizes the command value polarity and the direction of change of the command value and assigns a ramp time to the current signal status.
  • Page 9: Fault Recognition

    +44 (0)1204 699 959 enquiries@hyquip.co.uk www.hyquip.co.uk/web/index Product description and commissioning instructions VT-SWKA-1 3. Functional description / commissioning notes 3.14 Fault recognition [14] This features monitors internal operating voltages, voltage outputs and, if jumper J7 (1-2) is plugged, the current output for cable break. When no fault is present, the green “ready for operation”...
  • Page 10: Indicator / Adjustment Elements

    +44 (0)1204 699 959 enquiries@hyquip.co.uk www.hyquip.co.uk/web/index Product description and commissioning instructions VT-SWKA-1 4. Indicator / adjustment elements 4. Indicator / adjustment elements J5 → current input J1 → inversion J4 → step function 1-2 2-3 1-2 2-3 1-2 2-3 4 mA •...
  • Page 11: Adjustment Recommendation

    +44 (0)1204 699 959 enquiries@hyquip.co.uk www.hyquip.co.uk/web/index Product description and commissioning instructions VT-SWKA-1 5. Adjustment recommendation 5. Adjustment recommendation The system-specific circuit must be provided. Signal Adjustment Command value call-up – Select the potentiometer to be adjusted using the measuring point selector switch –...
  • Page 12: Pin Assignment

    +44 (0)1204 699 959 enquiries@hyquip.co.uk www.hyquip.co.uk/web/index Product description and commissioning instructions VT-SWKA-1 6. Pin assignment 7. Engineering / maintenance notes / supplem. information 6. Pin assignment Row d Row b Row z Command call-up 1 Command value 1 Reserved (Potentiometer connection ± 10 V) (24V input) Command call-up 2 Command value 2...