MX14-5 MO-0141-ING Doc. N° 1. GENERAL UTILIZATION AND COMMISSIONING DIRECTIONS Always make reference to the specific description of the product and to the Manufacturer's instruction. Carefully observe the following warnings. 1.1 - Storage And Transportation must comply with the environmental conditions stated on the product's instruction or by the applicable IEC standards.
MX14-5 MO-0141-ING Doc. N° a. Before removing a module, ensure that you are at the same electrostatic potential as the equipment by touching the case. b. Handle the module by its front-plate, frame, or edges of the printed circuit board. Avoid touching the electronic components, printed circuit tracks or connectors.
A second RS485 serial communication port, MODBUS RTU protocol at 9600bps, (terminal blocks 1..2) allows the MX14-5 to be connected to a central supervision system. This port is active only when the front panel port is not in use (cable physically disconnected) and makes the internal data base available to the central supervision system.
MX14-5 MO-0141-ING Doc. N° 2.5 - Last events’ recording – time stamping. The last 50 events (opening/closing of any input/output) are time stamped with a 10ms resolution and stored into a non-volatile (E PROM) memory. All the recorded events are available via the serial communication interface with MSCom program.
MX14-5 MO-0141-ING Doc. N° 2.6 - Logic matrix. The output contacts are operated according to a programmable AND/OR matrix (see Figure 1) by the following inputs: Digital inputs I1..I14. Front panel push buttons (On and Off). Internal fault diagnostic signal (I.R.F.) Note that in remote operation mode, the front panel push buttons are ignored and they can be operated only via the serial communication interface.
Page 8
I1 is NOT TRUE AND I2 is TRUE. If we now want to program the MX14-5 to implement the XOR function, we just reserve two AND rows for statements (1) and (2) and then connect those rows to the OR column corresponding to output O1.
: In this mode the inputs can only be controlled via the relevant terminals of the (Local mode) MX14-5. In the local mode N° change of configuration or test command via push buttons or serial port is accepted. : In this mode all the inputs are sill controlled via the relevant terminals but their...
MX14-5 MO-0141-ING Doc. N° 2.9 - Signalizations and controls. 2.9.1 - Leds I1 – I14 Lit-on when the corresponding physical inputs are ON (logic state 1). 2.9.2 - Leds O1 – O5 Lit-on when the corresponding outputs are active (LOGIC state 1) and during the reset time delay.
MX14-5 MO-0141-ING Doc. N° 2.10 - Real time clock. The unit features a built in clock calendar with Years, Months, Days, Hours, Minutes, Seconds, Tenths of seconds and Hundredths of seconds. 2.10.1 - Clock synchronization. The clock can be synchronized via the serial communication interface.
MX14-5 MO-0141-ING Doc. N° 3. PROGRAMMING The configuration of the logic matrix can be programmed by the serial port RS232 on the front connected to the PC through the connection cable (see § 5) with the support of MSCom software.
MX14-5 MO-0141-ING Doc. N° 3.2 – Input and Output Configuration At the end of the matrix programming, activate function “Settings”. Herebelow window will be displayed. 3.2.1 – Output relay configuration Output relays can be programmed to be normally energized or normally deenergized, activating or not activating the correspondent box.
MX14-5 MO-0141-ING Doc. N° 3.3 – Selection of remotely controlled inputs Select the inputs to be remotely controlled by activating the correspondent box. 3.4 – Activation of the remotely controlled inputs The inputs selected for remote control can be forced from status “ 0 “ to status “ 1 “ activating the correspondent box.
MX14-5 MO-0141-ING Doc. N° 6. CABLE FOR FRONT PANEL SERIAL PORT (SCE1593 Rev.2) 7. MAINTENANCE No maintenance is required. Periodically a functional check-out can be made by operating the TEST button on relay’s front. In case of malfunctioning please contact Microelettrica Scientifica Service or the local Authorised Dealer mentioning the relay's Serial No reported in the label on relays enclosure.
MX14-5 MO-0141-ING Doc. N° 9. DIRECTION FOR PCB'S DRAW-OUT AND PLUG-IN 9.1 - Draw-out Rotate clockwise the screws and in the horizontal position of the screws-driver mark. Draw-out the PCB by pulling on the handle 9.2 - Plug-in Rotate clockwise the screws ...