Summary of Contents for FRIEDHELM LOH RITTAL CMC III DK 7030.202
Page 1
CMC III Access Control DK 7030.202 Assembly and operating instructions...
Page 2
Foreword Foreword Dear Customer, Thank you for choosing our CMC III Access Control (referred to hereafter as "Access Control")! We wish you every success. Yours, Rittal GmbH & Co. KG Rittal GmbH & Co. KG Auf dem Stuetzelberg 35745 Herborn Germany Tel.: +49(0)2772 505-0 Fax: +49(0)2772 505-2319...
Contents Contents Notes on documentation ...... 4 Storage and disposal ......19 CE labelling ............4 Storage ............19 Storing the documents ........4 Disposal ............19 Symbols used in these operating instructions ... 4 Technical specifications ...... 20 Associated documents ........4 Area of validity ..........
1 Notes on documentation Notes on documentation Note: Additional compatible base systems can be CE labelling found on the internet at www.rittal.com for Rittal GmbH & Co. KG hereby confirms that the CMC III model no. DK 7030.202. The term "base systems"...
2 Safety instructions Safety instructions General safety instructions Please observe the subsequent general safety instruc- tions for the installation and operation of the system: – Use only original Rittal products or products rec- ommended by Rittal in conjunction with the Access Control.
3 Product description Product description – Use of impermissible tools. – Improper operation. – Improper rectification of malfunctions. Functional description and components – Use of accessories not approved by Rittal GmbH & 3.1.1 Function Co. KG. The Access Control serves to monitor rack doors via an infrared access sensor.
4 Transport and handling Transport and handling Transport The unit is delivered in a carton. Unpacking ◾ Remove the unit's packaging materials. Note: After unpacking, the packaging materials must be disposed of in an environmentally friendly way. They consist of the following materials: Polyethylene film (PE film), cardboard.
5 Installation Installation that depend on the set value for "sensitivity" specified in the following table. Safety instructions Min. clearance Max. clearance ◾ Please observe the valid regulations for installation Sensitivity [mm] [mm] in the country in which the Access Control is in- stalled and operated, and the national regulations for accident prevention.
5 Installation ◾ Optionally secure the bracket using the two screws included in the scope of delivery. Fig. 6: Optional securing of the bracket 5.3.3 Installation with the provided bracket on a system chassis The provided bracket is used for installation on a sys- tem chassis.
5 Installation Fig. 10: Rear of the Access Control Legend CAN bus connection, 24 V CAN bus connection, 24 V Connection for RJ 12 handle Connection for CMC III reader unit The following CAN bus connection cables from the CMC III accessories range can be used: –...
Page 11
5 Installation ◾ If necessary, connect another component (e.g. another sensor type) to the second, free CAN bus interface of the Access Control (Fig. 10, item 5). Status change display: – The two green and the two red CAN bus LEDs on the CAN bus connection flash.
6 Operation Operation 6.3.2 LED displays on the CAN bus connection A red and a green LED are located on the CAN bus connection. They display the status of the CAN bus. Activating the Access Control After connecting the Access Control to a neighbouring Colour Status component using a CAN bus connecting cable, the...
6 Operation A new line is added to the end of the table. ◾ Click the Delete button. All selected access authorisations are immediately deleted without a confirmation prompt. To configure an access authorisation (transpond- er card or access code): Note: ◾...
6 Operation Note: Note: If no access module is activated in the The time interval within which the two users must register can also be specified directly "Use" column, the reader unit will be as- in the "access.cmc3" file (see section 6.7 signed to all access modules.
6 Operation Parameter Explanation Sensitivity Distance between the sensor and the door (1 = small, 3 = large). Entering the value "0" deactivates the integral access sensor ("Closed" status) and the status is controlled using the "Command" param- eter. Delay Time delay after which the status display changes.
6 Operation Parameter Explanation Parameter Explanation Value Current status of the handle used (0 = Status Indicates whether a coded lock or handle closed, 1 = handle open). transponder reader has been connected (active) or not (inactive), or the reader unit Status Current locking status.
6 Operation Note: If the "access.cmc3" file is removed from the folder, access is only then possible using the three predefined access codes "1001", "1002" and "1003". All other access authorisations have to initially be added again to a newly created file. 6.7.1 Downloading the file Note:...
6 Operation Note: Parameter Explanation Each line contains the parameter "Key" or Handle Serial number of the Access Control or "Crd" depending on whether the line applies (virtual) access controller to which the to a coded lock or transponder reader. access module to be switched is connect- ed.
7 Storage and disposal Storage and disposal Storage If the device is not used for a long period, Rittal recom- mends that it be disconnected from the mains power supply and protected from damp and dust. Disposal Since the Access Control consists mainly of the "housing"...
8 Technical specifications Technical specifications Technical specifications CMC III Access Control Model no. DK 7030.202 W x H x D (mm) 110 x 30 x 40 Operating temperature range 0 °C…+55 °C Storage temperature -45 °C…+85 °C Operating humidity range 5%…95% relative humidity, non-condensing Protection category IP 30 to IEC 60 529 Inputs and outputs CAN bus (RJ 45)
Page 21
9 Customer service addresses Customer service addresses For technical queries, please contact: Tel.: +49(0)2772 505-9052 E-mail: info@rittal.de Homepage: www.rittal.com For complaints or service requests, please contact: Tel.: +49(0)2772 505-1855 E-mail: service@rittal.de Rittal CMC III Access Control...
Page 24
◾ Enclosures ◾ Power Distribution ◾ Climate Control ◾ IT Infrastructure ◾ Software & Services You can find the contact details of all Rittal companies throughout the world here. www.rittal.com/contact RITTAL GmbH & Co. KG Auf dem Stuetzelberg · 35745 Herborn · Germany Phone +49 2772 505-0 E-mail: info@rittal.de ·...