Technical Data - S+S Regeltechnik AERASGARD AC02-SD-TYR2 Operating Instructions, Mounting & Installation

On-wall c02 sensors and measuring transducers, with multi-range switching and active /switching output
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 6
G
®
AERASGARD
ACO
The maintenance-free, microprocessor-controlled AERASGARD
is used to detect CO
content as well as gas temperature. The measurement signals are converted to standard signals of 0 -10 V.
2
The CO
content of the air is measured using an optical NDIR sensor (non-dispersive infra-red technology). The detection range of the CO
2
calibrated for standard applications such as monitoring residential rooms and conference rooms. Room ventilation on an as-needed basis, improved
well-being and customer benefit, increased comfort as well as reduced operating costs through energy conservation are just some of the benefits of
®
employing AERASGARD
CO
2
A measuring system based on NDIR (non-dispersive infra-red technology) for CO
range of wavelengths of light radiated by the source is damped and absorbed by CO
the receptor.

TECHNICAL DATA

Voltage supply:
Average power consumption:
CARBON DIOXIDE (CO
)
2
Sensor, CO
:
2
Measuring range, CO
:
2
Output, CO
:
2
Measuring accuracy, CO
:
2
Temperature dependence:
Pressure dependence:
Long-term stability:
Gas exchange:
TEMPERATURE
Measuring range, temperature:
Output, temperature:
Warm up time:
Ambient temperature:
Humidity:
Response time:
Electrical connection:
Enclosure:
Dimensions:
Cable gland:
Process connection:
Protection class:
Protection type:
Standards:
ACCESSORIES
WS-03
- SD - TYR2
2
sensors.
24 V AC ⁄ DC
< 3 VA at 24 V DC
optical NDIR sensor
(non-dispersive infra-red technology)
dual-beam measuring system
with automatic calibration
multi-range switching
(selectable via DIP switches)
0...2000 ppm ⁄ 0...5000 ppm
0 -10 V
up to 2000 ppm: ± 70 ppm plus 5 % of measured value
up to 5000 ppm: ± 70 ppm plus 10 % of measured value
approx. 10 ppm ⁄ K at +25 °C
± 1.5 % of measured value ⁄ kPa
(referred to standard pressure)
± 2 % of final value ⁄ year
by diffusion
0...+50 °C
0 -10 V
approx. 1 hour
+10...+50 °C
< 95 % r. H., non-precipitating air
approx. 2 minutes
0.14 - 1.5 mm
2
, via screw terminals
plastic, material polyamide,
30 % glass-globe reinforced,
with quick-locking screws
(slotted ⁄ Phillips head combination),
colour traffic white (similar to RAL 9016)
126 x 90 x 50 mm (Tyr 2)
M 16 x 1.5; including strain relief,
exchangeable
via screws
III (according to EN 60 730)
IP 65 (according to EN 60 529)
CE conformity,
electromagnetic compatibility according to EN 61 326,
EMC Directive 2014 ⁄ 30 ⁄ EU
Weather and sun protection,
200 x 180 x 150 mm, stainless steel
®
ACO
- SD - TYR2 or ATM - CO
2
measurement consists of a light source and a receptor. A certain
2
molecules in the measured section. This damping is detected by
2
- SD - TYR2 is designed for on-wall installation and
2
Rev. 2017 - V11 GB
sensor is
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents