DESCRIPTION
The Viconics R820 series SCR power controls are designed
for cost effective, precise modulation of electric loads for
most electric heating applications.
( Applicable on resistive loads only )
The R820 series consists of SCR's power controls, c/w
factory assembled heatsink for surface or in-panel mounting.
FEATURES
Microcomputer based.
Dip switch configurable
Integrated over temperature thermostatic protection (self
resetting) Auto shut off when SCR ambient temperature
is above 82°C ( 180°F )
Complete with factory installed heatsink
For surface or in-panel mounting
CSA approved for Canada and USA
UL recognized
Pulse status led for servicing & trouble shooting
2 years warranty
They are compatible with many industry standard signals. A
typical application would be to control a modulating electric
duct heater with a 0 to 10 Vdc control signal from an analog
room thermostat. The R820 power controller also contain
four dip switch to adjust to the following control signals:
• 0 to 10 Vdc control signal ( 2 to 10 Vdc control range )
• 4 to 20 mA control signal
• 0 to 135 Ω control signal
HOW TO ORDER
Models Available
R820-211
R820-213
R820-321
R820-323
R820-341
R820-343
R820-421
R820-423
R820-441
R820-443
R820-471
R820-621
R820-623
R820-641
R820-643
R820-671
** Only 2 legs of the circuit are controlled on 3 phase systems.
SCR POWER CONTROLS
240 Vac up to 600 Vac models
10 Amps up to 75 Amps models
1 phase or 3 phase models
Maximum Voltage
Up to 240 V.
Up to 240 V.
Up to 347 V.
Up to 347 V.
Up to 347 V.
Up to 347 V.
Up to 480 V.
Up to 480 V.
Up to 480 V.
Up to 480 V.
Up to 480 V.
Up to 600 V.
Up to 600 V.
Up to 600 V.
Up to 600 V.
Up to 600 V.
R820 SERIES
SCR INSTALLATION
Important.
All external safety devices like: contactors, relays, flow
switch & thermal protections are to be supplied and
installed by other.
When the SCR is installed inside a panel, the enclosure
needs to be adequately louvered for proper ventilation
and heat dissipation. Call the factory for the derating
amperage curves for these specific applications.
Electronic controls require special care for wiring and
startup. To avoid problems, carefully follow the
procedures below.
Look at the wiring diagrams, and study them carefully. Be
sure that you understand how the system is supposed to
work.
A) Location:
1- Can be installed inside a louvered approved cabinet
or with the heatsink mounted externally.
2- Must be installed away from excessive heat source.
3- Nothing must restrain air circulation to the heatsink.
B) Installation:
1-
If installed completely inside a cabinet, use the
mounting tabs on the heatsink to secure the SCR to
the back plate of the panel.
2-
If installed with heatsink outside the cabinet, use the
proper model mounting template for the cut out
dimensions and to check for mounting obstructions.
3-
Respect mounting orientation
( this side up ).
4-
Mount the heatsink vertically on the side of the
cabinet for proper heat dissipation.
5-
Do not relocate the power switching modules on the
heatsink.
Maximum Amperage
10 A.
10 A.
25 A.
25 A.
45 A.
45 A.
25 A.
25 A.
45 A.
45 A.
75 A.
25 A.
25 A.
45 A.
45 A.
75 A.
Phase
1 Phase
3 Phase
1 Phase
3 Phase
1 Phase
3 Phase
1 Phase
3 Phase
1 Phase
3 Phase
1 Phase
1 Phase
3 Phase
1 Phase
3 Phase
1 Phase
1

Advertisement

loading

Summary of Contents for Viconics R820 Series

  • Page 1 1 phase or 3 phase models DESCRIPTION SCR INSTALLATION Important. The Viconics R820 series SCR power controls are designed for cost effective, precise modulation of electric loads for All external safety devices like: contactors, relays, flow most electric heating applications.
  • Page 2: Specifications

    SPECIFICATIONS HIGH VOLTAGE WIRING Operating 0°C to 80°C ( 32°F to 176°F ) General cautions: Conditions: 0 % to 95 % R.H. non-condensing See power derating curves document • High voltages are present on the terminals of these devices. Please read all the instruction in this manual carefully. Thermostatic Self resetting.
  • Page 3 R820 single phase Weight (LBS) R820-211 4.5 " 2.25” 0.375” 3.75” 1.80 R820-321 4.5 " 2.25” 0.375” 3.75” 1.80 R820-341 6.5 " 3.25” 1.375” 3.75” 2.40 R820-421 4.5 " 2.25” 0.375” 3.75” 1.80 R820-441 6.5 " 3.25” 1.375” 3.75” 2.40 R820-471 10.0 "...
  • Page 4: Typical Applications

    DIP SWITCH ADJUSTMENTS PER APPLICATIONS INPUT SIGNAL SWITCH #1 SWITCH #2 SWITCH #3 SWITCH #4 0 to 10 Vdc control signal ( 2 to 10 Vdc control range ) 4 to 20 mA control signal 0 to 135 Ω control signal TYPICAL APPLICATIONS 0 To 10 Vdc Room Or Duct Thermostat Control Dip switch position...
  • Page 5: 24 Vac Power & Wiring

    Common of the power supply of the SCR controller card. • Use a Class 1 ( properly fused ) or Class 2, CSA or UL recognized transformer. Viconics Electronics Inc. 9245, Langelier Blvd, St-Leonard, Quebec, Canada H1P 3K9 www.viconics.com sales@viconics.com...

This manual is also suitable for:

R820-211R820-213R820-321R820-323R820-341R820-343 ... Show all