Summary of Contents for Middleby Bluezone 450
Page 1
Document #: BPI-PM004-01 Installation, Operation and Service Manual Bluezone® Model 450 Air Purification System The Middleby Corporation 20360 SW Avery Court, Tualatin, OR 97062 ● ● 503-626-1802 www.Bluezone.com support@evoamerica.com...
Page 2
Document #: BPI-PM004-01 Do not operate the Bluezone Model 450 IMPORTANT SAFEGUARDS while fogging with chlorine bleach or other READ AND SAVE THESE INSTRUCTIONS disinfectant solutions. Disinfectants can poison the Bluezone catalyst and reduce its Safety effectiveness. This manual contains important instructions and safety information about the Bluezone Air •...
Page 3
2’x4’ tile or two 2’x2’ ceiling tiles with Input Voltage 120 VAC 1 Phase a ceiling mounting kit, installed into Bluezone by Middleby cabinetry, or located on a shelf. The Bluezone Model 450 draws in air 240 VAC 1 Phase containing viruses, mold, spores or fungus,...
Page 5
Document #: BPI-PM004-01 Electrical System A wiring diagram of the Model 450 is shown in Figure 2. The wiring diagram applies to both the 120V and 240V SKUs of the Model 450. The asset tag on the Model 450 identifies the required voltage.
Page 6
Warning: To avoid risk of injury conditioning or mini-split outlet to avoid from bumping into the unit, use the forcing excessive air flow through the ceiling mount kit, Bluezone by Middleby Bluezone unit. cabinetry, or mount on shelf above head level.
Page 7
Document #: BPI-PM004-01 Mechanical Installation The Bluezone unit can be installed into a A drawing showing overall dimensions and ceiling mount kit or placed on a shelf. A mounting dimensions of the Model 450 is ceiling mount kit is available for purchase. provided in Figure 3.
Page 8
Document #: BPI-PM004-01 Figure 4: Illustration of the Shelf Mount Figure 5: Bluezone Ceiling Mount Kit Dimensions (fits in a 2’x4’ drop ceiling tile or two 2’x2’ ceiling tiles)
Page 9
Document #: BPI-PM004-01 Figure 6: Rendering of the Bluezone 450 Installed into a Ceiling Mount Kit...
Page 10
Document #: BPI-PM004-01 Electrical Installation The Bluezone unit is equipped with a power Warning The power cord is attached entry module. to the front of the unit and may be caught Model 450-052 must be connected to 120V, and pulled during activities in the space. 60Hz.
Page 11
Document #: BPI-PM004-01 Operation Circuit Breaker Power Switch Power Entry Module (AC Inlet) Bulb Counter Reset / Fan Speed Toggle Figure 7: Control Panel on Bluezone Unit Once the Model 450 is mounted and wired, it can be turned ‘On’ using the power switch on the control panel.
Page 13
Document #: BPI-PM004-01 Fault Conditions and Fault Codes If there are issues with the operation of the Model 450, the onboard diagnostics will indicate the nature of the problem. Display Screen codes are shown in Table 2. Table 2: Display Screen Status Indicator Fault Codes Display Color Display Text Fault...
Page 14
Document #: BPI-PM004-01 Troubleshooting Restart the unit. a. Power “Off” unit by pressing If the Display Screen has no light or text the power switch located on then the Model 450 is not being the control panel. powered. Check the following list for b.
Page 16
Document #: BPI-PM004-01 New Equipment Warranty Online warranty registration form must be All Bluezone products have been tested by completed to validate your New Equipment independent labs and in many facilities, Warranty. Please visit proving the performance as described in our www.BluezoneFresh.com to complete the literature.
Page 17
Document #: BPI-PM004-01 Service BULBS NEED TO BE REPLACED AFTER 8,800 HOURS OF USE. BULB KITS MUST BE PURCHASED DIRECTLY FROM BLUEZONE PRODUCTS OR AN AUTHORIZED PARTNER AS THEY ARE PROPRIETARY BULBS. Bulbs must be replaced at 8,800 hours of Please call 503-626-1802 or email operation.
Page 18
Document #: BPI-PM004-01 Hold replacement bulbs by the ceramic end and push the pins into Instructions for Bulb Replacement: the slots in the receptacle. They need to be pushed in until a “click” is heard and Toggle the power switch located on the unit’s control panel to OFF.
Page 28
Document #: BPI-PM004-01 Technical Support is provided by: Evo America, LLC A Middleby Company Our Ventless and Air Purification Experts 20360 SW Avery Court Tualatin, OR 97062 503-626-1802 866-626-1802 Toll-Free support@evoamerica.com...